R1D-GH2T-M2 [MSYSTEM]

Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE;
R1D-GH2T-M2
型号: R1D-GH2T-M2
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE

输入元件
文件: 总5页 (文件大小:165K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R1D-GH2  
Remote I/O R1X Series  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
THERMOCOUPLE & DC INPUT MODULE  
(16 points; DeviceNet)  
/C02: Polyurethane coating  
/C03: Rubber coating  
Functions & Features  
• 16-point thermocouple or DC inputs  
• DeviceNet interface  
RELATED PRODUCTS  
• Resistor module (model: REM3-250)  
• R1X configurator software (model: R1CON)  
• EDS file  
175 (6.89)  
The EDS file and configurator software are downloadable at  
M-System’s web site.  
40  
(1.57)  
115  
(4.53)  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
mm (inch)  
MODEL: R1D-GH2T-[1][2]  
GENERAL SPECIFICATIONS  
Connection  
ORDERING INFORMATION  
• Code number: R1D-GH2T-[1][2]  
Specify a code from below for each [1] and [2].  
(e.g. R1D-GH2T-M2/Q)  
Power input, DeviceNet: Euro type connector terminal  
(applicable wire size: 0.2 to 2.5 mm  
2
(AWG24 to 12),  
stripped length 7 mm)  
Input: M3 screw terminals (torque 0.6 N·m)  
Configurator: 2.5 dia. miniature jack; RS-232-C level  
Screw terminal: Nickel-plated steel  
• Specify the specification for option code /Q  
(e.g. /C01)  
• Use Ordering Information Sheet (No. ESU-5956). Default  
setting will be used if not otherwise specified.  
Factory default setting  
Housing material: Flame-resistant resin (gray)  
Isolation: Input to DeviceNet to power  
Power indicator: Green LED turns on with power supplied.  
Input type: DC Voltage ±5 V  
Burnout protection: No burnout  
DeviceNet COMMUNICATION  
Transmission cable: Approved for DeviceNet  
Node address setting: Rotary switch or software; 00 – 63  
Baud rate setting: DIP switch or software  
MS (Module Status) indicator: Bi-color (green/red)  
LED indicates device status.  
Cold junction compensation: No  
FIELD TERMINAL TYPE  
T: M3 screw terminals  
NS (Network Status) indicator: Bi-color (green/red)  
LED indicates status of the communication link.  
Device Profile: Generic Device  
[1] POWER INPUT  
AC Power  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
DC Power  
INPUT SPECIFICATIONS  
Thermocouple or DC input, 16 points  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
(Common negative for DC input)  
•Measuring range ±20 V, ±5 V, ±1 V: Atten. SW ON (3)  
•Measuring range ±0.8 V, ±0.2 V, ±50 mV, ±10m V: Atten.  
SW OFF (1)  
[2] OPTIONS  
blank: none  
Input resistance: 300 kΩ  
/Q: With options (specify the specification)  
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P  
Sampling rate: 150 millisec./16 points  
A/D conversion output: 16-bit signed binary (negative  
range represented by 2’s complements)  
R1D-GH2 SPECIFICATIONS  
ES-5958 Rev.8 Page 1/5  
http://www.m-system.co.jp/  
MODEL: R1D-GH2  
Engineering unit value is converted into A/D conversion  
data as shown below.  
PERFORMANCE (% of measuring range)  
Accuracy  
Input type & range: A/D data (decimal)  
±20 V: ±20000  
DC input: ±0.3 %  
Thermocouple input: See the table on the end of this  
section.  
±5 V: ±5000  
±1 V: ±10000  
Cold junction compensation error: ±3°C or ±5.4°F max.  
(at 20°C ±10°C or 68°F ±18°F)  
±0.8 V: ±8000  
±0.2 V: ±20000  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
±0.05 %/°C (±0.03 %/°F) for 10 mV range and T/C B (RH)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input to DeviceNet to power to FG)  
±50 mV: ±5000  
±10 mV: ±10000  
Thermocouples: Temperature × 10  
In order to change input type and range after shipment, the  
R1X configurator software (model: R1CON) is required.  
Thermocouple Accuracy  
15  
14 13 12 11 10  
9
8
7
6
5
4
3
2
1
0
USABLE RANGE ACCURACY CONFORMANCE  
T/C  
SIGN  
BIT  
Ch. (1st)  
INPUT 1 A/D CONVERSION DATA  
INPUT 2 A/D CONVERSION DATA  
INPUT 3 A/D CONVERSION DATA  
INPUT 4 A/D CONVERSION DATA  
(°C)  
(%)  
RANGE (°C)  
(PR)  
K (CA)  
E (CRC)  
J (IC)  
T (CC)  
B (RH)  
R
0 to 1770  
-270 to +1370  
-270 to +1000  
-210 to +1200  
-270 to +400  
100 to 1820  
-.0 to +1760  
-.0 to +1760  
0 to 2320  
0ꢀ.  
0ꢀ3  
0ꢀ7  
0ꢀ7  
10  
400 to 1770  
0 to 1370  
0 to 1000  
0 to 1200  
0 to 400  
700 to 1820  
400 to 1760  
400 to 1760  
0 to 2320  
0 to 1300  
0 to 600  
0 to 900  
0 to 139.  
SIGN  
BIT  
Ch. (1st+1)  
Ch. (1st+2)  
Ch. (1st+3)  
SIGN  
BIT  
SIGN  
BIT  
0ꢀ7  
0ꢀ7  
0ꢀ7  
0ꢀ7  
0ꢀ.  
0ꢀ.  
0ꢀ3  
0ꢀ.  
S
C (WRe .-26  
)
SIGN  
BIT  
Ch. (1st+7)  
Ch. (1st+11)  
Ch. (1st+15)  
INPUT 8 A/D CONVERSION DATA  
INPUT 12 A/D CONVERSION DATA  
INPUT 16 A/D CONVERSION DATA  
N
-270 to +1300  
-200 to +600  
-200 to +900  
0 to 139.  
U
L
P
(Platinel II)  
SIGN  
BIT  
USABLE RANGE ACCURACY CONFORMANCE  
T/C  
(PR)  
(°F)  
(%)  
RANGE (°F)  
32 to 3218  
-4.4 to +2498  
-4.4 to +1832  
-346 to +2192  
-4.4 to +7.2  
212 to 3308  
-.8 to +3200  
-.8 to +3200  
32 to 4208  
0ꢀ.  
0ꢀ3  
0ꢀ7  
0ꢀ7  
10  
7.2 to 3218  
32 to 2498  
32 to 1832  
32 to 2192  
32 to 7.2  
1292 to 3308  
7.2 to 3200  
7.2 to 3200  
32 to 4208  
32 to 2372  
32 to 1112  
32 to 16.2  
32 to 139.  
K (CA)  
SIGN  
BIT  
E (CRC)  
J (IC)  
T (CC)  
The R1D reserves 16 words at the Output Data Area (data  
sent from the R1D to the master) for the specified node address  
and sets the input data at this area. The Input Data  
Area (data sent to the R1D from the master) for the same  
node address is only reserved but unused.  
B (RH)  
0ꢀ7  
0ꢀ7  
0ꢀ7  
0ꢀ7  
0ꢀ.  
0ꢀ.  
0ꢀ3  
0ꢀ.  
R
S
C (WRe .-26  
)
N
U
L
-4.4 to +2372  
-328 to +1112  
-328 to +16.2  
32 to 139.  
INSTALLATION  
Power consumption  
P (Platinel II)  
Note: CJC error is not includedꢀ  
AC: Approx. 6 VA  
DC: Approx. 2 W  
Supply voltage to network: 11 – 25 V DC supplied through  
the network terminal block  
Supply current to network: 50 mA max.  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 380 g (0.84 lb)  
R1D-GH2 SPECIFICATIONS  
ES-5958 Rev.8 Page 2/5  
http://www.m-system.co.jp/  
MODEL: R1D-GH2  
EXTERNAL VIEW  
A
B
C
D
E F G  
H
NAME  
FUNCTIONS  
A
B
C
D
Power terminal block  
Network terminal block  
Baud rate setting  
For power input  
For wiring to DeviceNet  
125, 250, 500 kbps (factory set to: 125 kpbs)  
Selectable within 00 – 63 (factory set to: 00)  
Node address setting  
COLOR  
FUNCTIONS  
ON: Critical communication error  
blinking: Minor communication error  
ON: Communication established  
blinking: Communication down  
OFF: Power Not supplied  
FUNCTIONS  
E
NS (Network Status)  
indicator LED  
Red  
Green  
----  
COLOR  
Red  
F
MS (Module Status)  
indicator LED  
ON: Critical failure  
blinking: Minor failure  
Green  
ON: Normal conditions  
blinking: Device Not configured  
----  
OFF:  
Power Not supplied  
COLOR  
Green  
----  
FUNCTIONS  
G
H
Power LED  
ON:  
Power supplied  
Power Not supplied  
OFF:  
Configurator jack  
2.5 dia. miniature jack; RS-232-C level  
R1D-GH2 SPECIFICATIONS  
ES-5958 Rev.8 Page 3/5  
http://www.m-system.co.jp/  
MODEL: R1D-GH2  
CONNECTION DIAGRAM  
DC INPUT T/C INPUT  
+
+
Comm.  
Circuit  
+
1
V+  
ext. wire  
INPUT 1  
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
2
CAN_H  
Drain  
CAN_L  
V–  
To Other  
DeviceNet Devices  
3
INPUT 2  
INPUT 3  
INPUT 4  
INPUT 5  
INPUT 6  
INPUT 7  
INPUT 8  
INPUT 9  
INPUT 10  
INPUT 11  
INPUT 12  
INPUT 13  
INPUT 14  
INPUT 15  
INPUT 16  
4
5
6
Power  
Circuit  
7
T6  
T7  
T8  
U (+)  
POWER  
V (–)  
8
9
FG  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
JACK  
CONFIGURATOR  
Input  
Circuit  
CJC  
Sensor  
Unused  
Unused  
Note 1: This device is not designed to cancel noise included in the input signals.  
Be careful to eliminate such noise by using shielded cables.  
Note 2: Be sure to maintain the same potential at all the common negative  
terminals for DC input.  
Caution: FG terminal is NOT a protective conductor terminal.  
R1D-GH2 SPECIFICATIONS  
ES-5958 Rev.8 Page 4/5  
http://www.m-system.co.jp/  
MODEL: R1D-GH2  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
175 (6.89)  
165 (6.50)  
15.5 (.61)  
3–5 (.20) dia.  
MTG HOLES  
CAN_H Drain CAN_L  
T6 T7 T8  
V+  
V–  
DIN RAIL  
35 mm wide  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18  
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35  
3 (.12)  
40 (1.57)  
163 (6.42)  
[6 (.24)]  
FOR WALL MOUNT.  
CJC SENSOR (model: CJM)  
6.2 (.24)  
36–M3 INPUT TERMINALS  
Specifications are subject to change without notice.  
R1D-GH2 SPECIFICATIONS  
ES-5958 Rev.8 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

R1D-GH2T-M2/Q

Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE
MSYSTEM

R1D-GH2T-R

Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE
MSYSTEM

R1D-GH2T-R/Q

Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE
MSYSTEM

R1D-XX05

1 Watt SMD Single & Dual Output
RECOM

R1D-XX09

1 Watt SMD Single & Dual Output
RECOM

R1D-XX12

1 Watt SMD Single & Dual Output
RECOM

R1D-XX15

1 Watt SMD Single & Dual Output
RECOM

R1D-XX24

1 Watt SMD Single & Dual Output
RECOM

R1D-XX3.3

1 Watt SMD Single & Dual Output
RECOM

R1D10-0505

1 Watt SMD Single & Dual Output
RECOM

R1D10-0505/P-R

CONV DC/DC 1W 05VIN +/-05VOUT
ETC

R1D10-0505P

1 Watt SMD Single & Dual Output
RECOM