MODEL: R3-AS4  
Remote I/O R3 Series  
CAUTION  
UNUSED INPUT CHANNELS  
Set the unused channels to -20 – +20 mA or 0 – 20 mA  
range. Otherwise, set them as "Unused" with PC  
Configurator software: R3CON. Unused channels left open  
with 4 – 20 mA setting are equal to the input lower than -15  
%, which sets a data abnormality at the PLC or the host  
device.  
DC CURRENT INPUT ALARM MODULE  
(4 points, isolated)  
27.5 [1.08]  
Open circuit with the input range set to ±20 mA means 50  
% of the full-scale. An alarm setpoint must be set to a value  
that does not trip an unwanted alarm.  
130  
[5.12]  
109  
[4.29]  
GENERAL SPECIFICATIONS  
Connection  
mm [inch]  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: M3 separable screw terminal (torque 0.5 N·m)  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
MODEL: R3-AS4[1][2]  
ORDERING INFORMATION  
• Code number: R3-AS4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-AS4W/CE/Q)  
Isolation: Input 1 to input 2 to input 3 to input 4 to internal  
bus or internal power  
Input range: Selectable with the side DIP SW  
Conversion rate: Selectable with the side DIP SW  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with input circuit abnormality (AD converter response  
failure);  
• Specify the specification for option code /Q  
(e.g. /C01)  
NO. OF CHANNELS  
4: 4  
[1] COMMUNICATION MODE  
Green in normal operating conditions.  
S: Single  
W: Dual  
INPUT SPECIFICATIONS  
DC Current: -20 – +20 mA, 0 – 20 mA, 4 – 20 mA DC  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Input resistance: 20 Ω resistor incorporated  
INSTALLATION  
/CE: CE marking  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
R3-AS4 SPECIFICATIONS  
ES-8439 Rev.7 Page 1/4  
https://www.m-system.co.jp/  
MODEL: R3-AS4  
(0.0 to 99.0 sec.; factory set to 5.0)  
PERFORMANCE  
Conversion accuracy: Refer to the table at the end of this  
The alarm output start functioning in the preset time after  
the power has been turned on.  
section.  
This setting is common to all four points.  
ALARM HOLD TIME  
Conversion rate: 80 / 40 / 20 / 10 msec. selectable  
Data allocation: 1  
(0.0 to 99.0 seconds; factory set to 1.0)  
The alarm output is held for the preset time even if it is  
reset in shorter time.  
Current consumption: 60 mA  
Temp. coefficient: ±0.03 %/°C (±0.02 %/°F)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to input 3 to input 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
This setting is common to all four points.  
RATE  
80 msec. 40 msec. 20 msec. 10 msec.  
RANGE  
0.05%  
0.1%  
0.1%  
0.1%  
0.2%  
0.2%  
0.2%  
0.4%  
0.4%  
0.4%  
0.8%  
0.8%  
-20 – +20 mA  
0 – 20 mA  
4 – 20 mA  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
ALARM SETTING  
The following parameters are programmable using the PC  
Configurator Software (model: R3CON).  
ALARM TRIP POINT (-15.00 to +115.00 %;  
factory set to A1: 80.00, A2: 60.00, A3: 40.00, A4: 20.00)  
Four alarm setpoints are selectable per each input.  
ALARM TYPE  
(High or Low; factory set to A1: High, A2: High, A3: Low,  
A4: Low)  
High or Low alarm is selectable for each alarm trip point.  
High alarm: An alarm is set when the input signal goes  
above the setpoint.  
Low alarm: An alarm is set when the input signal goes below  
the setpoint.  
DEADBAND (HYSTERESIS)  
(0.00 to 100.00 %; factory set to 5.00)  
Deadband (deviation between the points where the alarm is  
set and reset) is selectable for each alarm trip point.  
ALARM ON DELAY TIME  
(0.0 to 99.0 seconds; factory set to 1.0)  
The alarm output is set when the preset time elapses after  
the input has entered in the alarm range.  
This setting is common to all four points.  
POWER ON DELAY TIME  
R3-AS4 SPECIFICATIONS  
ES-8439 Rev.7 Page 2/4  
https://www.m-system.co.jp/  
MODEL: R3-AS4  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
Functions  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SW3  
ON  
SW2  
SW1  
Range  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)  
or  
Input 4 (SW2)  
Conv.  
Rate  
Input 1 (SW1)  
or  
Input 3 (SW2)  
ON  
ON  
OUTPUT DATA DESCRIPTIONS  
Four alarm setpoints are selectable per each input. One (1) word (16 bit) data is transmitterd to the PLC or the host device via  
the R3 network module.  
15  
0
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Input 1  
Input 2  
Input 3  
Input 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
1
11  
2
20–M3  
SCREW  
12  
3
13  
4
14  
5
15  
6
16  
7
17  
8
18  
9
19  
10  
20  
TERMINAL  
COVER  
R3-AS4 SPECIFICATIONS  
ES-8439 Rev.7 Page 3/4  
https://www.m-system.co.jp/  
MODEL: R3-AS4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Input Circuit  
INTERNAL BUS A  
Communication  
Circuit  
+
+
+
+
1
2
INTERNAL BUS B*  
INPUT 1  
INPUT 2  
INPUT 3  
INPUT 4  
Input Circuit  
Input Circuit  
Input Circuit  
Control  
Circuit  
3
INTERNAL POWER  
4
6
5
7
10  
15  
20  
8
9
11  
12  
13  
14  
16  
17  
18  
19  
*For dual redundant communication.  
Specifications are subject to change without notice.  
R3-AS4 SPECIFICATIONS  
ES-8439 Rev.7 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

R3-AS4S/Q

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4W

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4W/CE

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4W/Q

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8S

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8S/CE

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8S/Q

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8W

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8W/CE

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8W/Q

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AV4

Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE
MSYSTEM