R3-NEIP1 [MSYSTEM]

Remote I/O R3 Series EtherNet/IP INTERFACE MODULE;
R3-NEIP1
型号: R3-NEIP1
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series EtherNet/IP INTERFACE MODULE

文件: 总6页 (文件大小:178K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-NEIP1  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
Remote I/O R3 Series  
EtherNet/IP INTERFACE MODULE  
Functions & Features  
• Converts analog and discrete I/O data to the open network  
fieldbus (EtherNet/IP)  
GENERAL SPECIFICATIONS  
Connection  
Ethernet: RJ-45 Modular Jack  
Typical Applications  
Internal bus: Via the Installation Base (model: R3-BSx)  
Internal power: Via the Installation Base (model: R3-BSx)  
RUN contact output: M3 separable screw terminal (torque  
0.5 N·m)  
• Remote I/O for DCS and PLC  
27.5 [1.08]  
Screw terminal: Nickel-plated steel  
Isolation: EtherNet/IP to internal bus or internal power to  
RUN contact output  
130  
[5.12]  
Input error data setting: Input value setting at input module  
error with side DIP SW  
Dual communication setting: Set with the side DIP switch  
Data allocation setting: Set with the side DIP switch  
RUN CONTACT OUTPUT  
109  
[4.29]  
mm [inch]  
RUN contact: Turns ON when both MS and NS LEDs are  
green (EtherNet/IP in normal communication).  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
MODEL:R3–NEIP1[1]  
(Less than 50 V AC to conform with EU Directive)  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
ORDERING INFORMATION  
• Code number: R3-NEIP1[1]  
Specify a code from below for [1].  
(e.g. R3-NEIP1/CE/Q)  
Mechanical life: 2 × 10 cycles (300 cycles/min.)  
7
• Specify the specification for option code /Q  
(e.g. /C01)  
When driving an inductive load, external contact protection  
and noise quenching recommended.  
[1] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
EtherNet/IP COMMUNICATION  
Communication Standard: IEEE 802.3u  
Transmission: 10BASE-T, 100BASE-TX  
Baud rate: 10/100 Mbps (Auto Negotiation function)  
Max. number of socket connections: 3  
Connection type: Exclusive owner, Listen only, Input only  
Protocol: EtherNet/IP  
/CE: CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
Transmission media: 10BASE-T (STP, Category 5)  
100BASETX (STP, Category 5e)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Max. length of fieldbus segment: 100 meters  
IP address: 192.168.0.1 (factory setting); Selectable with PC  
Configurator Software (model: R3CON)  
BOOTP and DHCP available  
/C02: Polyurethane coating  
/C03: Rubber coating  
Port No.: 44818  
I/O data area size: Input and output data area size set with  
side DIP SW  
RELATED PRODUCTS  
• PC configurator software (model: R3CON)  
• EDS file  
Required data words:  
Input: 35, 67, 131, 252 words  
The EDS file and configurator software are downloadable at  
M-System’s web site.  
Output: 35, 67, 131, 252 words (3 words are used only for  
R3-NEIP1 SPECIFICATIONS  
ES-8466 Rev.6 Page 1/6  
https://www.m-system.co.jp/  
MODEL: R3-NEIP1  
status)  
Ethernet indicator LED: TX/RX, LINK  
MS (Module Status) indicator: Bi-color (green/red) LED  
indicates device status.  
NS (Network Status) indicator: Bi-color (green/red) LED  
indicates status of the communication link.  
Note: Not connectable beyond router.  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Current consumption: 130 mA  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(EtherNet/IP to internal bus or internal power to RUN contact  
output)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
MS Indicator LED  
NS Indicator LED  
Functions  
SW3  
ON  
SW2  
SW1  
Ethernet Indicator  
Configuration Jack  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
RJ-45 Modular Jack  
LINK  
TX/RX  
1
4
2
ON  
ON  
5
3
6
R3-NEIP1 SPECIFICATIONS  
ES-8466 Rev.6 Page 2/6  
https://www.m-system.co.jp/  
MODEL: R3-NEIP1  
TRANSMISSION DATA DESCRIPTIONS  
The DIP SW located at the side of the module specifies each I/O module's data allocation (occupied data area and size of the I/O data area).  
For example, when the data areas are assigned as shown below:  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
4
4
4
1
1
1
1
I/O data area: 252 words each for input and output.  
Then the I/O data are assigned as in the figures below:  
INPUT DATA  
OUTPUT DATA  
The figure below shows the allocation of the data sent from  
the master to the network module.  
The figure below shows the allocation of the data sent from  
the network module to the master.  
15  
0
15  
0
Begin  
Address +0  
Begin  
Address +0  
Module 1  
Module 2  
Module 3  
Module 1  
Module 2  
Module 3  
+2  
+4  
+2  
+4  
+6  
+6  
+8  
+8  
+10  
+12  
+14  
+16  
+10  
+12  
+14  
+16  
Module 4  
Module 5  
Module 6  
Module 7  
Module 4  
Module 5  
Module 6  
Module 7  
:
:
:
:
+249  
+251  
Module Status  
Error Status  
+249  
Data Error Status  
+251  
The area enclosed with bold line is assigned for I/O data  
Module Status, Error Status and Data Error Status are assigned to the last three words of the output data respectively.  
Each module can handle either input or output data.  
• Module Status indicates whether individual I/O module are mounted or not. The bit corresponding to the mounted slots  
turns to “1,” and the unmounted slots to “0.”  
• Error Status indicates error status for each module as described below. The bit corresponding to such modules turns to “1.”  
R3-TSx, R3-RSx, R3-US4 (T/C or RTD input): Input burnout  
R3-DA16A: Power input in error or disconnected  
R3-YSx: Output current error (e.g. load unconnected)  
R3-PC16A: External power supply in error or disconnected  
• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each  
module. The bit corresponding to such modules turns to “1.”  
R3-NEIP1 SPECIFICATIONS  
ES-8466 Rev.6 Page 3/6  
https://www.m-system.co.jp/  
MODEL: R3-NEIP1  
MODULE STATUS, ERROR STATUS, DATA ERROR STATUS  
Shows each module's availability and error status.  
15  
0
Module 1  
Module 2  
Module 3  
:
Module 16  
I/O DATA DESCRIPTIONS  
The data allocations for typical I/O modules are shown below.  
Refer to the manual for each module for detailed data allocations.  
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)  
16-bit binary data.  
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  
-15 to 0 % is a negative range represented in 2’s complement.  
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.  
15  
0
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)  
16-bit binary data.  
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.  
With °F temperature unit, the integer section of raw data is directly converted into the data.  
For example, 135.4°F is converted into 135.  
Minus temperature is converted into negative values, represented in 2’s complements.  
15  
0
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)  
16-bit binary data.  
Integer obtained by multiplying unit value (A) by 100.  
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.  
15  
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)  
32-bit binary data is used for accumulated counts and encoder positions.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
15  
0
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
15  
R3-NEIP1 SPECIFICATIONS  
ES-8466 Rev.6 Page 4/6  
https://www.m-system.co.jp/  
MODEL: R3-NEIP1  
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)  
32-bit binary data is used for BCD.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
15  
15  
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
0
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)  
15  
0
Input 1 (Output 1)  
Input 2 (Output 2)  
Input 3 (Output 3)  
:
:
Input 16 (Output 16)  
0 : OFF  
1 : ON  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
6–M3  
SCREW  
1
4
2
5
3
6
TERMINAL  
COVER  
R3-NEIP1 SPECIFICATIONS  
ES-8466 Rev.6 Page 5/6  
https://www.m-system.co.jp/  
MODEL: R3-NEIP1  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
LED  
Isolation  
Control  
Communication  
Circuit  
RJ-45 MODULAR JACK  
EtherNet/IP  
INTERNAL BUS  
Circuit  
RUN +  
1
4
ETHERNET DIP SW  
LED  
RUN CONTACT OUTPUT  
RUN –  
INTERNAL POWER  
JACK  
CONFIGURATION JACK  
2
3
5
6
SYSTEM CONFIGURATION EXAMPLES  
EtherNet/IP  
Master Station  
Ethernet  
Hub  
Ethernet  
Ethernet  
EtherNet/IP Interface Module  
model: R3-NEIP1  
EtherNet/IP Interface Module  
model: R3-NEIP1  
Specifications are subject to change without notice.  
R3-NEIP1 SPECIFICATIONS  
ES-8466 Rev.6 Page 6/6  
https://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY