R3-NL2-K3 [MSYSTEM]

Remote I/O R3 Series LonWorks INTERFACE MODULE;
R3-NL2-K3
型号: R3-NL2-K3
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series LonWorks INTERFACE MODULE

文件: 总6页 (文件大小:187K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-NL2  
Remote I/O R3 Series  
RELATED PRODUCTS  
• XIF File (Device Interface File)  
XIF file is used to define a LonWorks device when  
programmed on LonMaker.  
LonWorks INTERFACE MODULE  
(I/O 56 points)  
27.5 (1.08)  
GENERAL SPECIFICATIONS  
Connection  
LonWorks: Euro type connector terminal  
130  
(5.12)  
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)  
2
Internal bus: Via the Installation Base  
(model: R3-BSx)  
Internal power: Via the Installation Base (model: R3-BSx)  
Power input, RUN contact output: M3 separable screw  
terminal (torque 0.5 N·m)  
109  
(4.29)  
mm (inch)  
Screw terminal: Nickel-plated steel  
Isolation: LonWorks to internal bus or internal power to  
power input to RUN contact output to FG  
Input error data setting: Input value setting at input module  
error with side DIP SW  
MODEL: R3–NL2–[1][2]  
ORDERING INFORMATION  
• Code number: R3-NL2-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-NL2-R/Q)  
Data allocation setting: Set with the side DIP switch  
RUN indicator: Bi-color (green/red) LED; Green ON in  
communications with another device online or changing the  
output data  
• Specify the specification for option code /Q  
(e.g. /C01)  
(turns off after 25 seconds of no communication)  
ERR indicator: Bi-color (green/red) LED; Green ON in normal  
status; Green blinks when  
[1] POWER INPUT  
N: No power supply  
the APB file is not adequately imported;  
Green/Orange turn ON in turn in an abnormality.  
RUN CONTACT OUTPUT  
AC Power  
K3: 100 – 120 V AC  
RUN contact: Turns on while the green RUN LED is ON  
(LonWorks in normal communication)  
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *  
L3: 200 – 240 V AC  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *  
DC Power  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *  
* Not selectable for use with independent power modules.  
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When  
7
driving an inductive load, external contact protection and  
noise quenching recommended.  
[2] OPTIONS  
blank: none  
LonWorks COMMUNICATION  
Neuron Chip: FT3120 (NeuronID printed in numbers and bar  
code [peel-off code 39 format])  
/Q: With options (specify the specification)  
Transceiver: FT-X1 (equivalent to FTT10A)  
Transmission speed: 78 kbps  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Twisted-pair cable  
Distance, free topology: 500 meters  
Max. 64 nodes/channel  
/C02: Polyurethane coating  
/C03: Rubber coating  
LNS: Ver. 3.0 Service Pack 8 or higher  
ONLINE indicator: Red LED  
ON: Off-line or no network information (decommissioned)  
R3-NL2 SPECIFICATIONS  
ES-8428 Rev.10 Page 1/6  
http://www.m-system.co.jp/  
MODEL: R3-NL2  
Blinking in approx. 0.5 Hz: On-line  
(ready to communicate network variables)  
Blinking in approx. 5 Hz for 12 sec.:  
Wink message received  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (LonWorks or  
internal bus or internal power to power input to RUN contact  
output to FG)  
SERVICE indicator: Green LED  
OFF: Normal operations  
Blinking in approx. 0.5 Hz: No network information  
ON: Internal program error  
SERVICE switch: Used to identify the node in LonWorks  
network configuration  
RESET switch: Resetting the Neuron Chip  
Possible I/O combinations  
Analog I/O  
Input  
56  
Output  
0
Network Variable Type  
SNVT_lev_percent  
0
56  
SNVT_lev_percent  
32  
24  
SNVT_lev_percent (factory default)  
Temperature Input (°C input module use  
)
Input  
56  
Output  
Network Variable Type  
SNVT_temp  
0
0
56  
SNVT_temp_p  
Discrete I/O (Usable with the R3-DA16x and the R3-DC16x)  
Input  
56  
Output  
0
Network Variable Type  
SNVT_switch  
0
56  
SNVT_switch  
32  
24  
SNVT_switch  
Totalized Pulse I/O (Usable as analog I/O  
)
Input  
56  
Output  
0
Network Variable Type  
SNVT_count  
0
56  
SNVT_count  
32  
24  
SNVT_count  
Totalized Pulse Input, Discrete I/O (Totalized pulse usable as  
analog input) (Usable with the R3-DA16x and the R3-DC16x)  
Totalized Pulse  
Input  
Discrete  
Network Variable Type  
Input Output  
SNVT_count  
SNVT_switch  
16  
16  
16  
INSTALLATION  
Power consumption  
AC: Approx. 20 VA  
DC: Approx. 12 W  
Current consumption (no power supply): 100 mA  
Output current (power supply): 250 mA continuous at 20 V  
DC; 400 mA for 10 minutes  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
R3-NL2 SPECIFICATIONS  
ES-8428 Rev.10 Page 2/6  
http://www.m-system.co.jp/  
MODEL: R3-NL2  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
ONLINE LED  
SERVICE LED  
SERVICE SW  
RESET SW  
RUN LED  
ERR LED  
DIP SW  
SW3  
ON  
SW2  
SW1  
1
2
3
4
5
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Configuration Jack  
Euro Type  
Connector Terminal  
1
2
3
4
5
6
ON  
ON  
COMMUNICATION CABLE CONNECTIONS  
HOST PC  
R3-NLx  
R3-NLx  
LONWORKS  
LONWORKS  
LONWORKS  
Terminator  
TRANSMISSION DATA DESCRIPTIONS  
ANALOG INPUT / OUTPUT  
The DIP SW located at the side of the module specifies each I/O module's data allocation (occupied data area).  
[Example 1]  
Seven (7) of 8-point analog input module:  
Position  
Module Type  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-NL2-N  
R3-PS3-R  
Data Area  
Network Variable  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
Module 8  
Module 9  
8
8
8
8
8
8
8
nvoLV01 through nvoLV08  
nvoLV09 through nvoLV16  
nvoLV17 through nvoLV24  
nvoLV25 through nvoLV32  
nvoLV33 through nvoLV40  
nvoLV41 through nvoLV48  
nvoLV49 through nvoLV56  
The same principle is applied to Analog Output (R3NL2-LVO56) or Temperature Input (R3NL2_T56, R3NL2_TP56).  
R3-NL2 SPECIFICATIONS  
ES-8428 Rev.10 Page 3/6  
http://www.m-system.co.jp/  
MODEL: R3-NL2  
DISCRETE INPUT / OUTPUT  
One (1) data area can handle 16 points of discrete signals.  
[Example 2]  
Four (4) of 16-point discrete input module:  
Position  
Module Type  
R3-DA16S  
R3-DA16S  
R3-DA16S  
R3-DA16S  
R3-NL2-N  
R3-PS1-R  
Data Area  
Network Variable  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
1
1
1
1
nvoSW01 through nvoSW16  
nvoSW17 through nvoSW32  
nvoSW33 through nvoSW48  
nvoSW49 through nvoSW56  
Channels 9 through 16 of the Module 4 are not transmitted.  
MIXED I/O  
Network Variables for the input channels are assigned first, and then those for the output channels are assigned to the next  
module position.  
[Example 3]  
Four (4) of 8-point analog input module and three (3) of 8-point analog output:  
Position  
Module Type  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-SV8S  
R3-YV8S  
R3-YV8S  
R3-YV8S  
R3-NL2-N  
R3-PS3-R  
Data Area  
Network Variable  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
Module 8  
Module 9  
8
8
8
8
8
8
8
nvoLV01 through nvoLV08  
nvoLV09 through nvoLV16  
nvoLV17 through nvoLV24  
nvoLV25 through nvoLV32  
nviLV01 through nviLV08  
nviLV09 through nviLV16  
nviLV17 through nviLV24  
TOTALIZED PULSE INPUT / DISCRETE I/O  
Network Variables for the discrete input channels are assigned first, and then those for the totalized pulse input channels are  
assigned to the next module position. Finally those for the discrete output channels are assigned to the following module  
position. The I/O modules must be assigned as in the fllowing example. Adequate operation is not guaranteed in any other  
configuration.  
[Example 4]  
One (1) of 16-point totalized pulse input module, one (1) of 16-point discrete input module, and one (1) of 16-point discrete  
output:  
Position  
Module Type  
R3-DA16S  
R3-PA16S  
R3-DC16S  
R3-NL2-N  
R3-PS1-R  
Data Area  
Network Variable  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
1
16  
1
nvoSW01 through nvoSW16  
nvoC01 through nvoC16  
nviSW01 through nviSW16  
R3-NL2 SPECIFICATIONS  
ES-8428 Rev.10 Page 4/6  
http://www.m-system.co.jp/  
MODEL: R3-NL2  
I/O COMBINATIONS  
A dedicated Device File for each I/O device depending upon I/O combinations is required for the setting up using an integration  
tool such as Lon Maker.  
On-line download is available for Device Image files at M-System's homepage.  
Functional Blocks usable for respective files are not identical to all. Refer to the table below.  
ANALOG INPUT / OUTPUT  
NO. of DATA  
NETWORK VARIABLE  
SNVT_lev_percent  
SNVT_lev_percent  
SNVT_lev_percent  
DEVICE IMAGE  
USABLE FUNCTIONAL BLOCKS  
INPUT OUTPUT  
56  
0
R3NL2_LVI56_103.XIF  
R3NL2_LVI56_103.APB  
R3NL2_LVO56_103.XIF  
R3NL2_LVO56_103.APB  
R3NL2_LVI32O24_104.XIF  
R3NL2_LVI32O24_104.APB  
NodeObject  
NL2LVIn  
0
56  
24  
NodeObject  
NL2LVOut  
NodeObject  
NL2LVIO  
32  
TEMPERATURE INPUT (°C)  
NO. of DATA  
NETWORK VARIABLE  
DEVICE IMAGE  
USABLE FUNCTIONAL BLOCKS  
INPUT OUTPUT  
56  
0
SNVT_temp  
R3NL2_TI56_103.XIF  
R3NL2_TI56_103.APB  
R3NL2_TPI56_103.XIF  
R3NL2_TPI56_103.APB  
NodeObject  
NL2TIn  
56  
0
SNVT_temp_p  
NodeObject  
NL2TPIn  
DISCRETE INPUT / OUTPUT  
NO. of DATA  
NETWORK VARIABLE  
DEVICE IMAGE  
USABLE FUNCTIONAL BLOCKS  
INPUT OUTPUT  
56  
0
SNVT_switch  
SNVT_switch  
SNVT_switch  
R3NL2_SWI56_103.XIF  
R3NL2_SWI56_103.APB  
R3NL2_SWO56_103.XIF  
R3NL2_SWO56_103.APB  
R3NL2_SWI32O24_103.XIF  
R3NL2_SWI32O24_103.APB  
NodeObject  
NL2SWIn  
0
56  
24  
NodeObject  
NL2SWOut  
NodeObject  
NL2SWIO  
32  
TOTALIZED PULSE INPUT / OUTPUT  
NO. of DATA  
NETWORK VARIABLE  
DEVICE IMAGE  
USABLE FUNCTIONAL BLOCKS  
INPUT OUTPUT  
56  
0
SNVT_count  
SNVT_count  
SNVT_count  
R3NL2_CI56_103.XIF  
NodeObject  
NL2CIn  
R3NL2_CI56_103.APB  
R3NL2_CO56_104.XIF  
R3NL2_CO56_104.APB  
R3NL2_CI32CO24_103.XIF  
R3NL2_CI32CO24_103.APB  
0
56  
24  
NodeObject  
NL2COut  
NodeObject  
NL2CInOut  
32  
TOTALIZED PULSE INPUT / DISCRETE INPUT / DISCRETE OUTPUT  
NO. of DATA  
USABLE  
FUNCTIONAL  
BLOCKS  
TOTAL. PULSE  
INPUT  
16  
DISCRETE  
NETWORK VARIABLE  
DEVICE IMAGE  
INPUT OUTPUT  
16  
16  
SNVT_count  
SNVT_switch  
R3NL2_CI16SWI16SWO16_103.XIF  
R3NL2_CI16SWI16SWO16_103.APB  
NodeObject  
NL2CISWIO  
XIF File: Device Interface File (external interface)  
APB File: Downloadable Application Image File (program for NeuronChip)  
R3-NL2 SPECIFICATIONS  
ES-8428 Rev.10 Page 5/6  
http://www.m-system.co.jp/  
MODEL: R3-NL2  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
27.5 (1.08)  
109 (4.29)  
POSITIONING  
GUIDE  
1
2
3
4
5
6–M3  
SCREW  
1
4
2
5
3
6
TERMINAL  
COVER  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Caution: FG terminal is NOT a protective conductor terminal.  
ONLINE/SERVICE LED RUN/ERR LED  
LONWORKS  
Control  
Circuit  
Communication  
Circuit  
1
2
3
4
5
INTERNAL BUS  
Transceiver  
FT-X1  
Neuron  
Chip  
FT3120  
DIP SW  
SERVICE SW  
RESET SW  
INTERNAL POWER  
1
4
2
3
6
RUN +  
RUN CONTACT OUTPUT  
5
RUN –  
*
U (+)  
*
POWER INPUT  
V (–)  
*
FG  
JACK  
*Not provided with ‘No Power Supply’ type module.  
CONFIGURATION JACK  
Specifications are subject to change without notice.  
R3-NL2 SPECIFICATIONS  
ES-8428 Rev.10 Page 6/6  
http://www.m-system.co.jp/  

相关型号:

R3-NL2-K3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-L3

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-L3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-R

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-R/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NM1

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-NM1-K3

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-NM1-K3/CE

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-NM1-K3/Q

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-NM1-L3

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-NM1-L3/CE

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM

R3-NM1-L3/Q

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM