R3-NP1L3 [MSYSTEM]
Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE;型号: | R3-NP1L3 |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE |
文件: | 总5页 (文件大小:164K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-NP1
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
PROFIBUS-DP INTERFACE MODULE
/C02: Polyurethane coating
27.5 [1.08]
/C03: Rubber coating
CAUTION
■ Mounting on 2-slot base
130
[5.12]
Use a dedicated base (R3-BS02P) for R3-NP1.
115.1
[4.53]
GENERAL SPECIFICATIONS
Connection
mm [inch]
PROFIBUS: 9-pin D-sub connector, female
Internal bus: Via the Installation Base (model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
MODEL: R3-NP1-[1][2]
ORDERING INFORMATION
• Code number: R3-NP1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NP1-R/CE/Q)
Screw terminal: Nickel-plated steel
Isolation: PROFIBUS to internal bus or internal power to
power supply to RUN contact output to FG
Input error data setting: Input value setting at input module
error with side DIP SW
• Specify the specification for option code /Q
(e.g. /C01)
Dual communication setting: Set with the side DIP switch
RUN indicator: Bi-color (green/Amber) LED
(Function selected with DIP SW)
[1] POWER INPUT
N: No power supply
ERR indicator: Bi-color (green/red) LED
(Function selected with DIP SW)
AC Power
■ RUN CONTACT OUTPUT
K3: 100 – 120 V AC
RUN contact: Turns ON while the green RUN LED is ON.
(PROFIBUS in normal communication)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
(CE not available)
L3: 200 – 240 V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
(CE not available)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
Mechanical life: 2 × 10 cycles (300 cycles/min.)
7
When driving an inductive load, external contact protection
and noise quenching recommended.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
PROFIBUS COMMUNICATION
Interface: PROFIBUS-DP, slave (RS-485 isolation)
Max. baud rate: 12 Mbps
/CE: CE marking
Protocol: DPV1
Other Options
Station No. setting: Rotary switch; 00 - 7D
(Address is 7D even setting greater value)
GSD file: Msys093F.GSD
blank: none
/Q: Option other than the above (specify the specification)
GSD files are downloadable at M-System’s web site or at
PROFIBUS International site (www.profibus.com).
Input data: Max. 240 bytes
Output data: Max. 240 bytes
R3-NP1 SPECIFICATIONS
ES-8418 Rev.15 Page 1/5
https://www.m-system.co.jp/
MODEL: R3-NP1
Total I/O data: Max. 480 bytes
Diagnostics: Module-related, Status (devicerelated),
Channel-related (max. 32 channels, maskable)
Acyclic communication (MSAC2): 2 channels
INSTALLATION
Power consumption
•AC: Approx. 20 VA
•DC: Approx. 12 W
Current consumption (no power supply): 130 mA
Output current (power supply): 220 mA continuous at 20 V
DC; 370 mA for 10 minutes
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (PROFIBUS to
internal bus or internal power to power input to RUN output
to FG)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
R3-NP1 SPECIFICATIONS
ES-8418 Rev.15 Page 2/5
https://www.m-system.co.jp/
MODEL: R3-NP1
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
C
Station Address Setting
Rotary SW, upper digit
SA1
SA2
4
C
4
RUN LED
ERR LED
Station Address Setting
Rotary SW, lower digit
DIP SW
SW3
Configuration Jack
Network Connector
4
3
2
1
ON
1
2
3
4
5
6
■ PROFIBUS INTERFACE
PIN No.
SIGNAL
SIGNIFICANCE
5
1
NC
NC
Not used
Not used
Network, B-line
RTS signal
0V
9
2
6
1
3
4
5
6
7
8
9
B_line
RTS
GND
P5V
NC
5V
Not used
Network, A-line
Not used
A_line
NC
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
-15 to 0 % is a negative range represented in 2’s complement.
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.
15
0
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.
For example, 135.4°F is converted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.
15
0
R3-NP1 SPECIFICATIONS
ES-8418 Rev.15 Page 3/5
https://www.m-system.co.jp/
MODEL: R3-NP1
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
16-bit binary data.
Integer obtained by multiplying unit value (A) by 100.
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.
15
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
0
0
+0
+1
Lower 16 bits
Higher 16 bits
15
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
15
0
+0
+1
Lower 16 bits
Higher 16 bits
0
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)
15
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
:
Input 16 (Output 16)
0 : OFF
1 : ON
R3-NP1 SPECIFICATIONS
ES-8418 Rev.15 Page 4/5
https://www.m-system.co.jp/
MODEL: R3-NP1
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
6.1
109 [4.29]
POSITIONING
GUIDE
[.24]
6–M3
SCREW
1
4
2
5
3
TERMINAL
COVER
6
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
LED ROTARY SW
Isolation
PROFIBUS
Control
Circuit
Communication
Circuit
INTERNAL BUS
DIP SW
RUN +
1
4
INTERNAL POWER
RUN CONTACT OUTPUT
RUN –
*
U (+) 2
5
*
POWER INPUT
V (–) 3
*
FG
6
JACK
CONFIGURATION JACK
*Not provided with ‘No Power Supply’ type module.
Specifications are subject to change without notice.
R3-NP1 SPECIFICATIONS
ES-8418 Rev.15 Page 5/5
https://www.m-system.co.jp/