MODEL: R3-SS4  
Remote I/O R3 Series  
CAUTION  
UNUSED INPUT CHANNELS  
Set the unused channels to -20 – +20 mA or 0 – 20 mA  
range. Otherwise, set them as “Unused” with PC  
Configurator software: R3CON. Unused channels left open  
with 4 – 20 mA setting are equal to the input lower than -15  
%, which sets a data abnormality at the PLC or the host  
device.  
DC CURRENT INPUT MODULE  
(4 points, isolated)  
27.5 [1.08]  
130  
[5.12]  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: M3 separable screw terminal (torque 0.5 N·m)  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
109  
[4.29]  
mm [inch]  
Isolation: Input 1 to input 2 to input 3 to input 4 to internal  
bus or internal power  
MODEL: R3-SS4[1][2]  
Input range: Selectable with the side DIP SW  
Conversion rate: Selectable with the side DIP SW  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with input circuit abnormality (AD converter response  
failure);  
ORDERING INFORMATION  
• Code number: R3-SS4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-SS4W/CE/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
NO. OF CHANNELS  
4: 4  
Green in normal operating conditions.  
INPUT SPECIFICATIONS  
DC Current: -20 – +20 mA, 0 – 20 mA, 4 – 20 mA DC  
[1] COMMUNICATION MODE  
S: Single  
Input resistance: 20 Ω resistor incorporated  
W: Dual  
INSTALLATION  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
/CE: CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8393)  
R3-SS4 SPECIFICATIONS  
ES-8393 Rev.11 Page 1/3  
https://www.m-system.co.jp/  
MODEL: R3-SS4  
PERFORMANCE  
Conversion accuracy: Refer to the table at the end of this  
section.  
Conversion rate: 80 / 40 / 20 / 10 msec. selectable  
Data range: 0 – 10000 of the input range  
Data allocation: 4  
Current consumption: 60 mA  
Temp. coefficient: ±0.03 %/°C (±0.02 %/°F)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to input 3 to input 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
RATE  
80 msec. 40 msec. 20 msec. 10 msec.  
RANGE  
0.05%  
0.1%  
0.1%  
0.1%  
0.2%  
0.2%  
0.2%  
0.4%  
0.4%  
0.4%  
0.8%  
0.8%  
-20 – +20 mA  
0 – 20 mA  
4 – 20 mA  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
Functions  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SW3  
ON  
SW2  
SW1  
Range  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)  
or  
Input 4 (SW2)  
Conv.  
Rate  
Input 1 (SW1)  
or  
Input 3 (SW2)  
ON  
ON  
R3-SS4 SPECIFICATIONS  
ES-8393 Rev.11 Page 2/3  
https://www.m-system.co.jp/  
MODEL: R3-SS4  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
1
11  
2
20–M3  
SCREW  
12  
3
13  
4
14  
5
15  
6
16  
7
17  
8
18  
9
19  
10  
20  
TERMINAL  
COVER  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Input Circuit  
INTERNAL BUS A  
Communication  
Circuit  
+
+
+
+
1
2
INTERNAL BUS B*  
INPUT 1  
INPUT 2  
INPUT 3  
INPUT 4  
Input Circuit  
Input Circuit  
Input Circuit  
Control  
Circuit  
3
INTERNAL POWER  
4
6
5
7
10  
15  
20  
8
9
11  
12  
13  
14  
16  
17  
18  
19  
*For dual redundant communication.  
Specifications are subject to change without notice.  
R3-SS4 SPECIFICATIONS  
ES-8393 Rev.11 Page 3/3  
https://www.m-system.co.jp/  

相关型号:

R3-SS4W/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8N

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8NS

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8NS/CE

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8NS/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8NW

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8NW/CE

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8NW/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8S

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8S/CE

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3-SS8S/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM