R3-SV4S/Q [MSYSTEM]
Remote I/O R3 Series DC VOLTAGE INPUT MODULE;型号: | R3-SV4S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series DC VOLTAGE INPUT MODULE 输入元件 |
文件: | 总3页 (文件大小:124K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-SV4
Remote I/O R3 Series
CAUTION
■ UNUSED INPUT CHANNELS
Set the unused channels to the ranges otherthan 1 – 5 V.
Otherwise, set them as “Unused” with PC Configurator
software: R3CON. Unused channels left open with 1 – 5 V
setting are equal to the input lower than -15 %, which sets a
data abnormality at the PLC or the host device.
DC VOLTAGE INPUT MODULE
(4 points, isolated)
27.5 [1.08]
130
[5.12]
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base
(model: R3-BSx)
109
[4.29]
mm [inch]
Screw terminal: Nickel-plated steel
Isolation: Input 1 to input 2 to input 3 to input 4 to internal
bus or internal power
MODEL: R3-SV4[1][2]
Input range: Selectable with the side DIP SW
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response
failure);
ORDERING INFORMATION
• Code number: R3-SV4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-SV4W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
4: 4
Green in normal operating conditions.
INPUT SPECIFICATIONS
■ Narrow Span: -1 – +1 V, 0 – 1 V DC
Input resistance: 100 kΩ min.
■ Wide Span: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
[1] COMMUNICATION MODE
S: Single
W: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
Input resistance: 1 MΩ min.
INSTALLATION
/CE: CE marking
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8366)
R3-SV4 SPECIFICATIONS
ES-8366 Rev.11 Page 1/3
https://www.m-system.co.jp/
MODEL: R3-SV4
PERFORMANCE
Conversion accuracy: Refer to the table at the end of this
section.
Conversion rate: 80 / 40 / 20 / 10 msec. selectable
Data range: 0 – 10000 of the input range
Data allocation: 4
Current consumption: 60 mA
Temp. coefficient: ±0.015 % /°C (±0.008 %/°F)
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
Conversion accuracy
RATE
80 msec. 40 msec. 20 msec. 10 msec.
RANGE
0ꢀ05ꢁ
0ꢀ05ꢁ
0ꢀ05ꢁ
0ꢀ05ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ1ꢁ
0ꢀ.ꢁ
0ꢀ.ꢁ
0ꢀ1ꢁ
0ꢀ.ꢁ
0ꢀꢂꢁ
-10 – +10 V
-5 – +5 V
0ꢀꢂꢁ
0ꢀꢂꢁ
0ꢀꢂꢁ
0ꢀ.ꢁ
0ꢀ.ꢁ
0ꢀ.ꢁ
-1 – +1 V
0 – 10 V
0 – 5 V
1 – 5 V
0 – 1 V
0ꢀꢂꢁ
0ꢀꢂꢁ
0ꢀ.ꢁ
0ꢀꢃꢁ
0ꢀꢃꢁ
0ꢀꢂꢁ
0ꢀ1ꢁ
0ꢀ05ꢁ
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
RUN LED
ERR LED
Functions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SW3
ON
SW2
SW1
Range
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)
or
Input 4 (SW2)
Conv.
Rate
Input 1 (SW1)
or
Input 3 (SW2)
ON
ON
R3-SV4 SPECIFICATIONS
ES-8366 Rev.11 Page 2/3
https://www.m-system.co.jp/
MODEL: R3-SV4
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED DIP SW
Input Circuit
INTERNAL BUS A
Communication
Circuit
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
1
2
INTERNAL BUS B*
WIDE SPAN
NARROW SPAN
WIDE SPAN
INPUT 1
INPUT 2
INPUT 3
INPUT 4
Control
Circuit
11
12
3
INTERNAL POWER
Input Circuit
Input Circuit
Input Circuit
5
4
10
15
20
13
14
6
NARROW SPAN
WIDE SPAN
7
16
17
8
NARROW SPAN
WIDE SPAN
9
18
19
NARROW SPAN
* For dual redundant communication.
Note: Connect either wide or narrow span terminals for each channel.
Specifications are subject to change without notice.
R3-SV4 SPECIFICATIONS
ES-8366 Rev.11 Page 3/3
https://www.m-system.co.jp/
相关型号: