R3-TS4 [MSYSTEM]

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE;
R3-TS4
型号: R3-TS4
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE

输入元件
文件: 总4页 (文件大小:133K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-TS4  
Remote I/O R3 Series  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: M3 separable screw terminal (torque 0.5 N·m)  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
THERMOCOUPLE INPUT MODULE  
(4 points, isolated)  
27.5 [1.08]  
Isolation: Input 1 to input 2 to input 3 to input 4 to internal  
bus or internal power  
Sensor type: Selectable with the side DIP SW  
Temperature unit: °C, °F or absolute temperature selectable  
with the side DIP SW  
130  
[5.12]  
Conversion rate: Selectable with the side DIP SW  
Burnout detection: Upscale or downscale selectable with the  
side DIP SW  
109  
[4.29]  
mm [inch]  
Linearization: Standard  
Cold junction compensation: CJC sensor attached to the  
input terminals  
MODEL: R3-TS4[1][2]  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with burnout; Green in normal operating conditions.  
ORDERING INFORMATION  
• Code number: R3-TS4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-TS4W/CE/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
NO. OF CHANNELS  
4: 4  
[1] COMMUNICATION MODE  
S: Single  
W: Dual  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
/CE: CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8362)  
R3-TS4 SPECIFICATIONS  
ES-8362 Rev.15 Page 1/4  
https://www.m-system.co.jp/  
MODEL: R3-TS4  
Cold junction compensation error:  
INPUT SPECIFICATIONS  
Input resistance: 30 kΩ min.  
Burnout sensing: 0.1 μA  
±1.0°C max. (at 25°C ±10°C)  
±1.8°F max. (at 77°F ±18°F)  
(±1.5°C or ±2.7°F for R, S, PR)  
Temperature range  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Burnout response time: ≤ 2 sec.  
°C  
T/C  
K (CA)  
E (CRC)  
J (IC)  
USABLE  
RANGE  
CONFORMANCE  
RANGE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to input 3 to input 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
-272 to +1472  
-272 to +1120  
-260 to +1300  
-150 to +1370  
-170 to +1000  
-180 to +1200  
T (CC)  
B (RH)  
R
-272 to +500  
24 to 1920  
-100 to +1860  
-170 to +400  
400 to 1760  
200 to 1760  
S
-100 to +1860  
-52 to +2416  
-272 to +1400  
0 to 1760  
0 to 2315  
-130 to +1300  
STANDARDS & APPROVALS  
EU conformity:  
C (WRe 5-26)  
N
U
L
-252 to +700  
-252 to +1000  
-52 to +1496  
-52 to +1860  
-200 to +600  
-200 to +900  
0 to 1395  
EMC Directive  
EMI EN 61000-6-4  
P (Platinel II)  
(PR)  
EMS EN 61000-6-2  
RoHS Directive  
0 to 1760  
°F  
T/C  
USABLE  
RANGE  
CONFORMANCE  
RANGE  
K (CA)  
E (CRC)  
J (IC)  
-458 to +2682  
-458 to +2048  
-436 to +2372  
-238 to +2498  
-274 to +1832  
-292 to +2192  
T (CC)  
B (RH)  
R
-458 to +932  
75 to 3488  
-148 to +3380  
-274 to +752  
752 to 3200  
392 to 3200  
S
-148 to +3380  
-62 to +4381  
-458 to +2552  
32 to 3200  
32 to 4199  
-202 to +2372  
C (WRe 5-26)  
N
U
L
-422 to +1292  
-422 to +1832  
-62 to +2725  
-62 to +3380  
-328 to +1112  
-328 to +1652  
32 to 2543  
32 to 3200  
P (Platinel II)  
(PR)  
Max. (upscale) or min. (downscale) value of the usable  
range when a burnout is detected.  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Conversion accuracy: ±1.0°C (±1.8°F) except ±2.0°C  
(±3.6°F) for B, R, S, C, PR  
Conversion rate: 250 msec. or 1 sec. selectable  
Data range  
°C, absolute temperature: Engineering unit value × 10  
(integer)  
°F: Engineering unit value (integer)  
Data allocation: 4  
Current consumption: 70 mA  
R3-TS4 SPECIFICATIONS  
ES-8362 Rev.15 Page 2/4  
https://www.m-system.co.jp/  
MODEL: R3-TS4  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
Functions  
1
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SW3  
ON  
SW2  
SW1  
2
3
4
5
6
7
8
9
10  
Conv.  
Rate  
Temp.  
Unit  
Burnout  
T/C  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)  
or  
Input 4 (SW2)  
Input 1 (SW1)  
or  
Input 3 (SW2)  
ON  
ON  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
1
11  
2
20–M3  
SCREW  
12  
3
13  
4
14  
5
15  
6
16  
7
17  
8
18  
9
19  
10  
20  
TERMINAL  
COVER  
R3-TS4 SPECIFICATIONS  
ES-8362 Rev.15 Page 3/4  
https://www.m-system.co.jp/  
MODEL: R3-TS4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Input Circuit  
INTERNAL BUS A  
+
+
+
+
Communication  
Circuit  
+
1
2
T/C  
INTERNAL BUS B*  
comp. wire  
INPUT 1  
Control  
Circuit  
CJC  
SENSOR  
INTERNAL POWER  
12  
11  
3
Input Circuit  
Input Circuit  
Input Circuit  
5
+
T/C  
10  
15  
20  
comp. wire  
INPUT 2  
4
14  
13  
6
CJC  
SENSOR  
+
T/C  
comp. wire  
INPUT 3  
7
17  
16  
8
CJC  
SENSOR  
+
T/C  
comp. wire  
INPUT 4  
9
CJC  
SENSOR  
19  
18  
*For dual redundant communication.  
• Unused Input Channels  
Close across the unused input terminals as shown below.  
(Choose K (CA) thermocouple for unused channels.)  
INPUT 1  
1
INPUT 2  
3
INPUT 3  
6
INPUT 4  
8
Short  
2
4
7
9
CJC  
SENSOR  
12  
14  
17  
19  
Unused channels left open are equal to the burnout, which  
turns the red ERR LED on and sets a burnout !ag at the  
PLC or the host device.  
Unused channels can be speci"ed and set so on the PC  
Con"gurator Software (model: R3CON) without needing to  
short at the "eld terminals.  
Specifications are subject to change without notice.  
R3-TS4 SPECIFICATIONS  
ES-8362 Rev.15 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

R3-TS4S

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS4S/CE

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS4S/Q

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS4W

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS4W/CE

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS4W/Q

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS8

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS8A

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS8AS

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS8AS/CE

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS8AS/Q

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM

R3-TS8AW

Remote I/O R3 Series THERMOCOUPLE INPUT MODULE
MSYSTEM