R30GCIE1S [MSYSTEM]
Remote I/O R30 Series;型号: | R30GCIE1S |
厂家: | M-SYSTEM |
描述: | Remote I/O R30 Series |
文件: | 总5页 (文件大小:174K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R30GCIE1
Remote I/O R30 Series
CAUTION
Please use this unit with a network module (model:
R30NECT1) of firmware version V1.04.10 or higher, and a
network module (model: R30NCIE1) of firmware version
V1.01.13 or higher.
CC-Link INTERFACE MODULE
(CC-Link IE Field network)
Functions & Features
• Serves as a gateway for allowing CC-Link IE Field Network
data to be handled by network modules that use different
protocols.
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B
type USB cable. (provided by user)
• Recognized as an analog I/O mixed module by the
network modules.
• Works as a slave station on CC-Link IE Field Network in the
same manner as R30NCIE1.
GENERAL SPECIFICATIONS
Connection
Typical Applications
• A gateway for CC-Link IE Filed and EtherCAT.
CC-Link IE Field: RJ-45 connector
25
Internal bus: Via the Installation Base (model: R30BS)
Internal power: Via the Installation Base (model: R30BS)
Isolation: CC-Link IE Field to internal bus or internal power
Internal bus communication cycle: Approx. 1 msec.
Status indicator: RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)
[.98]
110
[4.33]
CC-Link IE Field COMMUNICATION
Protocol: IEEE 802.3
98 [3.86]
Transmission type: 1000BASE-T
mm [inch]
Communication speed: 1 Gbps
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
MODEL: R30GCIE1S[1]
Network topology: Line, star and ring
Max. number of stations: 120 (Total slave stations)
(Number of max. connectable slaves may vary depending
on the master module. Refer to the instruction manual of
the master module)
ORDERING INFORMATION
• Code number: R30GCIE1S[1]
Specify a code from below for [1].
(e.g. R30GCIE1S/Q)
Max. station-to-station distance: 100 m
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points
NetWork No.: 1 to 239 (factory default: 1)
• Specify the specification for option code /Q
(e.g. /C01)
COMMUNICATION MODE
S: Single
INSTALLATION
Current consumption: 140 mA
[1] OPTIONS
blank: none
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 125 g (0.28 lb)
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
R30GCIE1 SPECIFICATIONS
ES-9027 Rev.3 Page 1/5
https://www.m-system.co.jp/
MODEL: R30GCIE1
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (CC-Link IE Field
to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the
power supply module)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
Positioning Guide
Specifications
RUN
RD
Status Indicator LEDs
SD
D
LINK
ERR
CC-Link IE Field Communication
RJ-45 Modular Jack
CN1
CN2
×10
Station No. Rotary SW
Not in use
STATION No.
×1
■ BOTTOM VIEW
Base Fixing Screw
Lock Tab
R30GCIE1 SPECIFICATIONS
ES-9027 Rev.3 Page 2/5
https://www.m-system.co.jp/
MODEL: R30GCIE1
TRANSMISSION DATA DESCRIPTIONS
Number of transmission data: 4 points (4 words) for input; 4 points (4 words) for output
This unit is equivalent to an analog I/O mixed module (AIO4) of R30 series, and is recognized as an I/O module by Interface
module (e.g. model: R30NECT1).
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points
• DATA FLOW
Host PC/PLC
Input
data
Output
data
R30PS1
R30Nx*
R30GCIE1
Output
Input
data
RWr
data
RWw
CC-Link IE Field master
* R30Nx: R30 Interface module
■ OUTPUT DATA
■ INPUT DATA
The figure below shows details of data transmitted to Host
PC/PLC from Interface module.
The figure below shows details of data received by Interface
module from Host PC/PLC.
[CC-Link IE Field master]—>[R30GCIE1]—>[R30 internal bus]
—>[R30 interface module]—>[Host PC/PLC]
[Host PC/PLC]—>[R30 interface module]—>[R30 internal bus]
—>[R30GCIE1]—>[CC-Link IE Field master]
Output data (RWw) from CC-Link IE Field master is transmitted
as Input data to Host PC/PLC.
Output data from Host PC/PLC is transmitted as Input data (RWr)
to CC-Link IE Field master.
15
0
15
0
RWw (n + 0)
RWw (n + 1)
RWw (n + 2)
RWw (n + 3)
RWw (n + 4)
RWr (n + 0)
RWr (n + 1)
RWr (n + 2)
RWr (n + 3)
RWr (n + 4)
Output data
Not in use
Input data
Not in use
RWw (n + 63)
n: initial device
RWr (n + 63)
n: initial device
R30GCIE1 SPECIFICATIONS
ES-9027 Rev.3 Page 3/5
https://www.m-system.co.jp/
MODEL: R30GCIE1
■ STATUS
15
0
F E D C B A 9 8 7 6 5 4 3 2 1 0
RX (n + 0)
Remote READY
Module status
RX (n + 1)
RX (n + 2)
Not in use
RX (n + 7)
n: initial device
• RX(n+0)0 to 7 is reservation area, RX(n+0)B is used as Ready signal, and the bit is“1” when this module is operating normally.
RX(n+0)8 to A and RX(n+0)C to F are not in use.
• Module Status
RX(n + 1)0 indicates communication status of this unit.
1 = Normal communication
0 = Communication error / timeout
RX(n + 1)1 indicates internal communication status.
1 = Normal communication
0 = Communication stop / communication error
RX(n + 1)2 indicates communication status of field bus built in the interface module.
1 = Normal communication
0 = Communication stop / communication error / timeout
RX(n + 1)3 to F are not in use.
Link devices other than the above are not in use.
EXTERNAL DIMENSIONS unit: mm [inch]
98 [3.86]
25 [.98]
R30GCIE1 SPECIFICATIONS
ES-9027 Rev.3 Page 4/5
https://www.m-system.co.jp/
MODEL: R30GCIE1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
IND. LEDs
STATION NO. SETTING
ROTARY SW
Isolation
Comm.
Circuit
CC-Link IE Field CN1 RJ-45 MODULAR JACK
INTERNAL BUS
Control
Circuit
CC-Link IE Field CN2
RJ-45 MODULAR JACK
INTERNAL POWER
Not in use USB CONNECTOR
Isolation
CN1 and CN2 of RJ-45 modular jacks for CC-Link IE Field network can be connected in any order.
SYSTEM CONFIGURATION EXAMPLES
The below figure shows a system configuration example in which CC-Link IE Field data is converted into EtherCAT data by using
this unit as a gateway.
EtherCAT
master module
EtherCAT
R30
R30
R30
PS1 NECT1 GCIE1
CC-Link IE Field
CC-Link IE Field
master module
Specifications are subject to change without notice.
R30GCIE1 SPECIFICATIONS
ES-9027 Rev.3 Page 5/5
https://www.m-system.co.jp/
相关型号: