R30GCIE1S [MSYSTEM]

Remote I/O R30 Series;
R30GCIE1S
型号: R30GCIE1S
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R30 Series

文件: 总5页 (文件大小:174K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R30GCIE1  
Remote I/O R30 Series  
CAUTION  
Please use this unit with a network module (model:  
R30NECT1) of firmware version V1.04.10 or higher, and a  
network module (model: R30NCIE1) of firmware version  
V1.01.13 or higher.  
CC-Link INTERFACE MODULE  
(CC-Link IE Field network)  
Functions & Features  
• Serves as a gateway for allowing CC-Link IE Field Network  
data to be handled by network modules that use different  
protocols.  
RELATED PRODUCTS  
• PC configurator software (model: R30CFG)  
Downloadable at M-System’s web site.  
For connecting to PC, use commercially available Mini-B  
type USB cable. (provided by user)  
• Recognized as an analog I/O mixed module by the  
network modules.  
• Works as a slave station on CC-Link IE Field Network in the  
same manner as R30NCIE1.  
GENERAL SPECIFICATIONS  
Connection  
Typical Applications  
• A gateway for CC-Link IE Filed and EtherCAT.  
CC-Link IE Field: RJ-45 connector  
25  
Internal bus: Via the Installation Base (model: R30BS)  
Internal power: Via the Installation Base (model: R30BS)  
Isolation: CC-Link IE Field to internal bus or internal power  
Internal bus communication cycle: Approx. 1 msec.  
Status indicator: RUN, RD, SD, D LINK, ERR, L ER, LINK  
(Refer to the instruction manual.)  
[.98]  
110  
[4.33]  
CC-Link IE Field COMMUNICATION  
Protocol: IEEE 802.3  
98 [3.86]  
Transmission type: 1000BASE-T  
mm [inch]  
Communication speed: 1 Gbps  
Network cable: Cable conformed to CC-Link IE Field  
Double shielded twist pair cable (CAT5e)  
RJ-45 connector  
MODEL: R30GCIE1S[1]  
Network topology: Line, star and ring  
Max. number of stations: 120 (Total slave stations)  
(Number of max. connectable slaves may vary depending  
on the master module. Refer to the instruction manual of  
the master module)  
ORDERING INFORMATION  
• Code number: R30GCIE1S[1]  
Specify a code from below for [1].  
(e.g. R30GCIE1S/Q)  
Max. station-to-station distance: 100 m  
Station type: Remote device station  
Link device: RX/RY 128 points, RWw/RWr 64 points  
NetWork No.: 1 to 239 (factory default: 1)  
• Specify the specification for option code /Q  
(e.g. /C01)  
COMMUNICATION MODE  
S: Single  
INSTALLATION  
Current consumption: 140 mA  
[1] OPTIONS  
blank: none  
Operating temperature: -10 to +55°C (14 to 131°F)  
Storage temperature: -20 to +65°C (-4 to +149°F)  
Operating humidity: 10 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R30BS)  
Weight: 125 g (0.28 lb)  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
R30GCIE1 SPECIFICATIONS  
ES-9027 Rev.3 Page 1/5  
https://www.m-system.co.jp/  
MODEL: R30GCIE1  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (CC-Link IE Field  
to internal bus or internal power)  
1500 V AC @ 1 minute (power input to FE; isolated on the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
Positioning Guide  
Specifications  
RUN  
RD  
Status Indicator LEDs  
SD  
D
LINK  
ERR  
CC-Link IE Field Communication  
RJ-45 Modular Jack  
CN1  
CN2  
×10  
Station No. Rotary SW  
Not in use  
STATION No.  
×1  
BOTTOM VIEW  
Base Fixing Screw  
Lock Tab  
R30GCIE1 SPECIFICATIONS  
ES-9027 Rev.3 Page 2/5  
https://www.m-system.co.jp/  
MODEL: R30GCIE1  
TRANSMISSION DATA DESCRIPTIONS  
Number of transmission data: 4 points (4 words) for input; 4 points (4 words) for output  
This unit is equivalent to an analog I/O mixed module (AIO4) of R30 series, and is recognized as an I/O module by Interface  
module (e.g. model: R30NECT1).  
Station type: Remote device station  
Link device: RX/RY 128 points, RWw/RWr 64 points  
• DATA FLOW  
Host PC/PLC  
Input  
data  
Output  
data  
R30PS1  
R30Nx*  
R30GCIE1  
Output  
Input  
data  
RWr  
data  
RWw  
CC-Link IE Field master  
* R30Nx: R30 Interface module  
OUTPUT DATA  
INPUT DATA  
The figure below shows details of data transmitted to Host  
PC/PLC from Interface module.  
The figure below shows details of data received by Interface  
module from Host PC/PLC.  
[CC-Link IE Field master]—>[R30GCIE1]—>[R30 internal bus]  
—>[R30 interface module]—>[Host PC/PLC]  
[Host PC/PLC]—>[R30 interface module]—>[R30 internal bus]  
—>[R30GCIE1]—>[CC-Link IE Field master]  
Output data (RWw) from CC-Link IE Field master is transmitted  
as Input data to Host PC/PLC.  
Output data from Host PC/PLC is transmitted as Input data (RWr)  
to CC-Link IE Field master.  
15  
0
15  
0
RWw (n + 0)  
RWw (n + 1)  
RWw (n + 2)  
RWw (n + 3)  
RWw (n + 4)  
RWr (n + 0)  
RWr (n + 1)  
RWr (n + 2)  
RWr (n + 3)  
RWr (n + 4)  
Output data  
Not in use  
Input data  
Not in use  
RWw (n + 63)  
n: initial device  
RWr (n + 63)  
n: initial device  
R30GCIE1 SPECIFICATIONS  
ES-9027 Rev.3 Page 3/5  
https://www.m-system.co.jp/  
MODEL: R30GCIE1  
STATUS  
15  
0
F E D C B A 9 8 7 6 5 4 3 2 1 0  
RX (n + 0)  
Remote READY  
Module status  
RX (n + 1)  
RX (n + 2)  
Not in use  
RX (n + 7)  
n: initial device  
• RX(n+0)0 to 7 is reservation area, RX(n+0)B is used as Ready signal, and the bit is“1” when this module is operating normally.  
RX(n+0)8 to A and RX(n+0)C to F are not in use.  
• Module Status  
RX(n + 1)0 indicates communication status of this unit.  
1 = Normal communication  
0 = Communication error / timeout  
RX(n + 1)1 indicates internal communication status.  
1 = Normal communication  
0 = Communication stop / communication error  
RX(n + 1)2 indicates communication status of field bus built in the interface module.  
1 = Normal communication  
0 = Communication stop / communication error / timeout  
RX(n + 1)3 to F are not in use.  
Link devices other than the above are not in use.  
EXTERNAL DIMENSIONS unit: mm [inch]  
98 [3.86]  
25 [.98]  
R30GCIE1 SPECIFICATIONS  
ES-9027 Rev.3 Page 4/5  
https://www.m-system.co.jp/  
MODEL: R30GCIE1  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
STATUS  
IND. LEDs  
STATION NO. SETTING  
ROTARY SW  
Isolation  
Comm.  
Circuit  
CC-Link IE Field CN1 RJ-45 MODULAR JACK  
INTERNAL BUS  
Control  
Circuit  
CC-Link IE Field CN2  
RJ-45 MODULAR JACK  
INTERNAL POWER  
Not in use USB CONNECTOR  
Isolation  
CN1 and CN2 of RJ-45 modular jacks for CC-Link IE Field network can be connected in any order.  
SYSTEM CONFIGURATION EXAMPLES  
The below figure shows a system configuration example in which CC-Link IE Field data is converted into EtherCAT data by using  
this unit as a gateway.  
EtherCAT  
master module  
EtherCAT  
R30  
R30  
R30  
PS1 NECT1 GCIE1  
CC-Link IE Field  
CC-Link IE Field  
master module  
Specifications are subject to change without notice.  
R30GCIE1 SPECIFICATIONS  
ES-9027 Rev.3 Page 5/5  
https://www.m-system.co.jp/  

相关型号:

R30GCIE1S/Q

Remote I/O R30 Series
MSYSTEM

R30J

FAST SILICON RECTIFIERS
SEMTECH

R30K

FAST SILICON RECTIFIERS
SEMTECH

R30KP100A-PBF

Trans Voltage Suppressor Diode
DIGITRON

R30KP100AHR

Trans Voltage Suppressor Diode
DIGITRON

R30KP100C-PBF

Trans Voltage Suppressor Diode
DIGITRON

R30KP100CA-PBF

Trans Voltage Suppressor Diode
DIGITRON

R30KP110C-PBF

Trans Voltage Suppressor Diode
DIGITRON

R30KP120CA-PBF

Trans Voltage Suppressor Diode
DIGITRON

R30KP130-PBF

Trans Voltage Suppressor Diode
DIGITRON

R30KP130CA

Trans Voltage Suppressor Diode
DIGITRON

R30KP160CA-PBF

Trans Voltage Suppressor Diode
DIGITRON