R30YV4S/Q [MSYSTEM]

Remote I/O R30 Series DC VOLTAGE OUTPUT MODULE;
R30YV4S/Q
型号: R30YV4S/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R30 Series DC VOLTAGE OUTPUT MODULE

输出元件
文件: 总5页 (文件大小:183K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R30YV4  
Remote I/O R30 Series  
RELATED PRODUCTS  
• PC configurator software (model: R30CFG)  
Downloadable at M-System’s web site.  
DC VOLTAGE OUTPUT MODULE  
(4 points, isolated)  
For connecting to PC, use commercially available Mini-B  
type USB cable. (provided by user)  
Functions & Features  
• 4 channels for DC voltage output remote I/O module  
• Isolation between output channels  
• Output range of each channel is individually adjustable  
with PC configurator  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R30BS)  
Output: M3 separable screw terminal (torque 0.5 N·m)  
Internal power: Via the Installation Base (model: R30BS)  
Solderless terminal: Refer to the drawing at the end of the  
section.  
25 [.98]  
Recommended manufacturer: Japan Solderless Terminal  
MFG. Co., Ltd., Nichifu Co., Ltd.  
110  
[4.33]  
(Solderless terminals with insulation sleeve do not fit.)  
Applicable wire size: 0.25 to 0.75 mm  
2
Screw terminal: Nickel-plated steel  
Isolation: Output 1 to output 2 to output 3 to output 4 to  
internal bus or internal power  
98  
[3.86]  
mm [inch]  
Output range: Selectable with PC configurator software  
(model: R30CFG)  
Output at the loss of communication: Selectable with PC  
configurator software (Model: R30CFG, factory default:  
output hold)  
MODEL: R30YV4S[1]  
Status indicator LED: RUN, ERR  
ORDERING INFORMATION  
• Code number: R30YV4S[1]  
Specify a code from below for [1].  
(e.g. R30YV4S/Q)  
(refer to the instruction manual)  
■Recommended solderless terminal size - M3 (unit: mm)  
3 max.  
3.2 dia.  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
NO. OF CHANNELS  
4: 4  
12 max.  
COMMUNICATION MODE  
S: Single  
OUTPUT SPECIFICATIONS  
Module type: Analog output, 4 points  
Output range: -10 - +10V DC (*), -5 - +5V DC, 0 - 10V DC,  
0 - 5V DC, 1 - 5V DC  
[1] OPTIONS  
blank: none  
(*) Factory default  
Load resistance: ≥ 100 kΩ  
/Q: With options (specify the specification)  
Operational range:  
Except -10 to +10 V DC: -15 to +115 % of output range  
-10 to +10 V DC: Approx. -11.5 to +11.5 V DC  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
INSTALLATION  
/C02: Polyurethane coating  
Current consumption: 60 mA  
/C03: Rubber coating  
Operating temperature: -10 to +55°C (14 to 131°F)  
Storage temperature: -20 to +65°C (-4 to +149°F)  
Operating humidity: 10 to 90 %RH (non-condensing)  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-9005)  
R30YV4 SPECIFICATIONS  
ES-9005 Rev.3 Page 1/5  
https://www.m-system.co.jp/  
MODEL: R30YV4  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R30BS)  
Weight: 160 g (0.35 lb)  
PERFORMANCE  
Conversion accuracy: ±0.1 %  
Conversion rate: 10 msec.  
Data range: 0 – 10000 of the output range  
Data allocation: 4  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Output delay time: ≤ 250 msec. (0 - 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (output 1 to  
output 2 to output 3 to output 4 to internal bus or internal  
power)  
1500 V AC @ 1 minute (power input to FE; isolated by the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
FUNCTIONS  
Output at the loss of communication  
• Output Hold  
If the network module is in error, the module holds the  
signal at error and stands by until the communication  
recovers.  
• Output set value  
If the network module is in error, the module holds the  
signal at error or power up and stands by until the  
communication recovers. The signal at error or power up is  
selectable with PC configurator software (Model: R30 CFG)  
Not depending on output at the loss of communication  
setting, when power up the module holds the signal at error  
or power up and stands by until the normal data is received.  
R30YV4 SPECIFICATIONS  
ES-9005 Rev.3 Page 2/5  
https://www.m-system.co.jp/  
MODEL: R30YV4  
CONFIGURATOR SOFTWARE SETTING  
The following parameters can be set with using PC Configurator Software (model: R30CFG)  
Refer to the users manual for the R30CFG for detailed operation of the software program.  
CHANNEL INDIVIDUAL SETTING  
PARAMETER  
Unused setting  
SETTING RANGE  
CH enabled  
CH disabled  
-10 – +10V DC  
-5 – +5V DC  
0 – 10V DC  
DEFAULT SETTING  
CH enabled  
Output range  
-10 – +10V DC  
0 – 5V DC  
1 – 5V DC  
Fine zero adjustment -320.00 – +320.00 (%) 0.00 (%)  
Fine gain adjustment -3.2000 – +3.2000  
1.0000  
0
Scaled range zero  
Scaled range span  
Output range at  
-32 000 – +32 000  
-32 000 – +32 000  
10 000  
-15.00 – +115.00 (%) -15.00 (%)  
communication  
failure or power up  
CHANNEL BATCH SETTING  
PARAMETER  
SETTING RANGE  
DEFAULT SETTING  
Simulate output  
Normal output  
Simulation data  
Normal output  
Output at the loss of  
communication  
Hold the output data  
User set data output  
Hold the output  
data  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
Positioning Guide  
Specifications  
RUN LED  
ERR LED  
RUN  
ERR  
Output Terminal Block  
Terminal Fixing Screw  
Terminal Cover  
BOTTOM VIEW  
Base Fixing Screw  
Lock Tab  
R30YV4 SPECIFICATIONS  
ES-9005 Rev.3 Page 3/5  
https://www.m-system.co.jp/  
MODEL: R30YV4  
TERMINAL ASSIGNMENTS  
NO. ID  
FUNCTION  
NO. ID  
FUNCTION  
1
V1  
11  
1
2
3
4
5
6
7
8
9
V1 Voltage Output 1  
V2 Voltage Output 2  
V3 Voltage Output 3  
V4 Voltage Output 4  
NC No connection  
NC No connection  
NC No connection  
NC No connection  
NC No connection  
11 COM1 Common 1  
COM1  
2
3
4
5
12 COM2 Common 2  
V2  
V3  
V4  
12  
13 COM3 Common 3  
COM2  
14 COM4 Common 4  
13  
COM3  
15 NC No connection  
16 NC No connection  
17 NC No connection  
18 NC No connection  
19 NC No connection  
20 NC No connection  
14  
COM4  
NC  
15  
NC  
6
NC  
16  
NC  
7
10 NC No connection  
NC  
17  
NC  
8
NC  
18  
NC  
9
NC  
10  
NC  
19  
NC  
20  
NC  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
25 [.98]  
98 [3.86]  
20–M3  
SCREW  
R30YV4 SPECIFICATIONS  
ES-9005 Rev.3 Page 4/5  
https://www.m-system.co.jp/  
MODEL: R30YV4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN ERR  
indicator indicator  
Output circuit  
1
11  
2
V1  
OUTPUT1  
Comm.  
Circuit  
INTERNAL BUS  
COM1  
V2  
Output circuit  
Output circuit  
OUTPUT2  
OUTPUT3  
OUTPUT4  
12  
3
COM2  
V3  
INTERNAL POWER  
Control  
Circuit  
5
6
13  
4
COM3  
V4  
Output circuit  
7
14  
COM4  
8
9
10  
15  
16  
17  
18  
19  
20  
Specifications are subject to change without notice.  
R30YV4 SPECIFICATIONS  
ES-9005 Rev.3 Page 5/5  
https://www.m-system.co.jp/  

相关型号:

R310

Optoelectronic
ETC

R3100016

Rectifier Diode, 1 Element, 16A, 50V V(RRM),
POWEREX

R31001

SAW Resonator
ITF

R3100216

Rectifier Diode, 1 Element, 16A, 200V V(RRM),
POWEREX

R3100712

Rectifier Diode, 1 Element, 12A, 700V V(RRM),
POWEREX

R3100912

Rectifier Diode, 1 Element, 12A, 900V V(RRM),
POWEREX

R3101012

Rectifier Diode, 1 Element, 12A, 1000V V(RRM),
POWEREX

R3101016

Rectifier Diode, 1 Element, 16A, 1000V V(RRM),
POWEREX

R3107003K00

CAPACITOR, TANTALUM, SOLID, POLARIZED, 3V, 100uF, THROUGH HOLE MOUNT, RADIAL LEADED
VISHAY

R311

Optoelectronic
ETC

R3110

Optoelectronic
ETC

R3110-CBAA-E1T

用于助听器的预装 DSP 方案
ONSEMI