R3S-YS4W/H [MSYSTEM]

Remote I/O R3 Series DC CURRENT OUTPUT MODULE;
R3S-YS4W/H
型号: R3S-YS4W/H
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series DC CURRENT OUTPUT MODULE

输出元件
文件: 总4页 (文件大小:131K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3S-YS4  
Remote I/O R3 Series  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Output: Separable tension clamp terminal (applicable wire  
DC CURRENT OUTPUT MODULE  
(4 points, isolated, tension clamp terminal block)  
size: 0.2 to 1.5 mm , stripped length 10 mm)  
2
27.5 (1.08)  
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Output 1 to output 2 to output 3 to output 4 to  
internal bus or internal power  
Output hold function: Setting for communication error with  
side DIP SW  
130 (5.12)  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with output abnormality;  
120 (4.72)  
mm (inch)  
Green in normal operating conditions.  
MODEL: R3S-YS4[1][2]  
OUTPUT SPECIFICATIONS  
Output range: 4 – 20 mA DC  
ORDERING INFORMATION  
• Code number: R3S-YS4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3S-YS4W/H/Q)  
Load resistance: 300 Ω max. (600 Ω max. with Option /H)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
NO. OF CHANNELS  
4: 4  
[1] COMMUNICATION MODE  
S: Single  
PERFORMANCE  
Conversion accuracy: ±0.05 %  
W: Dual  
Data range: 0 – 10000 of the output range  
Data allocation: 4  
[2] OPTIONS (multiple selections)  
Load Resistance  
Current consumption: 180 mA (260 mA with Option /H)  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.2 sec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (output 1 to  
output 2 to output 3 to output 4 to internal bus or internal  
power)  
blank: ≤ 300 Ω  
/H: ≤ 600Ω  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
FUNCTIONS  
/C02: Polyurethane coating  
OUTPUT HOLD or OUTPUT OFF  
In normal conditions, the module outputs the signal from  
the preferred bus A.  
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8370)  
When an error is detected, the output is switched to the  
data from the bus B.  
Output Hold  
R3S-YS4 SPECIFICATIONS  
ES-8939 Rev.5 Page 1/4  
http://www.m-system.co.jp/  
MODEL: R3S-YS4  
If both are in error, the module holds the signal and stands  
by until one of the communications recovers.  
Output OFF  
If both are in error, the module outputs -15 % and stands by  
until one of the communications recovers.  
At the startup, it outputs -15 % until the communication is  
established and normal data is received.  
EXTERNAL VIEW  
FRONT VIEW  
RUN LED  
SIDE VIEW  
ERR LED  
1
SW3  
4
3
2
1
Output  
Hold  
ON  
20  
EXTERNAL DIMENSIONS unit: mm (inch)  
120 (4.72)  
109 (4.29)  
27.5 (1.08)  
POSITIONING  
GUIDE  
1
20  
R3S-YS4 SPECIFICATIONS  
ES-8939 Rev.5 Page 2/4  
http://www.m-system.co.jp/  
MODEL: R3S-YS4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED  
DIP SW  
Output Circuit  
1
2
INTERNAL BUS A  
+
Comm.  
Circuit  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
INTERNAL BUS B*1  
Output Circuit  
Output Circuit  
Output Circuit  
5
+
INTERNAL POWER  
Control  
Circuit  
6
11  
12  
15  
16  
4
+
3
7
+
9
10  
13  
17  
SLD  
SLD  
SLD  
SLD  
8
14  
18  
19  
20  
SLD  
SLD  
*2  
*1. For dual redundant communication.  
*2. To use shield line, connect it to SLD terminal and ground the terminal 20.  
Note: Do not use void terminals.  
Unused Output Channels  
Close across the unused output terminals as shown below.  
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4  
1
2
5
6
11  
12  
15  
16  
Cross-wire  
Unused channels left open are equal to the wire breakdown,  
which turns the red ERR LED on and sets a  
burnout flag at the PLC or the host device.  
Unused channels can be specified and set so on the PC  
Configurator Software (model: R3CON) without needing to  
short at the field terminals.  
R3S-YS4 SPECIFICATIONS  
ES-8939 Rev.5 Page 3/4  
http://www.m-system.co.jp/  
MODEL: R3S-YS4  
OUTPUT TERMINAL ASSIGNMENT  
PIN No.  
1
FUNCTION  
I1  
2
COM1  
NC  
3
4
SLD  
I2  
5
6
COM2  
NC  
7
8
SLD  
NC  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
NC  
I3  
COM3  
NC  
SLD  
I4  
COM4  
NC  
SLD  
SLD  
SLD  
Specifications are subject to change without notice.  
R3S-YS4 SPECIFICATIONS  
ES-8939 Rev.5 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

R3S-YS4W/Q

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM

R3Y-DA16

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16A

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16S

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16S/CE

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16S/Q

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16W

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16W/CE

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DA16W/Q

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DAC16AS

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DAC16AS/CE

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM

R3Y-DAC16AS/Q

Remote I/O R3 Series DISCRETE INPUT MODULE
MSYSTEM