R3Y-RS8S/Q [MSYSTEM]

Remote I/O R3 Series RTD INPUT MODULE;
R3Y-RS8S/Q
型号: R3Y-RS8S/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series RTD INPUT MODULE

输入元件
文件: 总5页 (文件大小:134K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3Y-RS8  
Remote I/O R3 Series  
RELATED PRODUCTS  
• Connector terminal block (model: CNT)  
• Special cable with 40-pin connector (model: FCN)  
RTD INPUT MODULE  
(8 points, isolated, connector type)  
GENERAL SPECIFICATIONS  
Connection  
27.5 [1.08]  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: 40-pin connector (Fujitsu FCN-365P040-AU)  
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Input 1 to input 2 to input 3 to input 4 to input 5 to  
input 6 to input 7 to input 8 to internal bus or internal power  
Sensor type: Selectable with the side DIP SW  
(Independent types selectable per group of 4 channels.)  
Temperature unit: °C, °F or absolute temperature selectable  
with the side DIP SW  
130  
[5.12]  
110  
[4.33]  
mm [inch]  
Conversion rate: Selectable with the side DIP SW  
Burnout detection: Upscale or downscale selectable with the  
side DIP SW  
MODEL: R3Y–RS8[1][2]  
Linearization: Standard  
ORDERING INFORMATION  
• Code number: R3Y-RS8[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3Y-RS8W/CE/Q)  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Red with burnout; Green in normal operating conditions.  
NO. OF CHANNELS  
8: 8  
INPUT SPECIFICATIONS  
Maximum leadwire resistance: 100 Ω per wire  
Sensing current: ≤ 1 mA  
Temperature range  
[1] COMMUNICATION MODE  
°C  
S: Single  
RTD  
USABLE RANGE CONFORMANCE RANGE  
W: Dual  
Pt 100 (JIS ’97, IEC)  
Pt 100 (JIS ’89)  
-240 to +900  
-240 to +900  
-236 to +560  
-200 to +850  
-200 to +660  
-200 to +510  
JPt 100 (JIS ’89)  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Pt 50Ω (JIS ’81)  
Ni 100  
-236 to +700  
-100 to +252  
-212 to +312  
-100 to +200  
-200 to +649  
-80 to +250  
-50 to +250  
-50 to +150  
Cu 10 @25°C  
Cu 50  
/CE: CE marking  
Other Options  
°F  
USABLE RANGE CONFORMANCE RANGE  
RTD  
blank: none  
/Q: Option other than the above (specify the specification)  
Pt 100 (JIS ’97, IEC)  
Pt 100 (JIS ’89)  
-400 to +1652  
-400 to +1652  
-393 to +1040  
-328 to +1562  
-328 to +1220  
-328 to +950  
JPt 100 (JIS ’89)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Pt 50Ω (JIS ’81)  
Ni 100  
-393 to +1292  
-148 to +486  
-350 to +594  
-148 to +392  
-328 to +1200  
-112 to +482  
-58 to +482  
-58 to +302  
Cu 10 @25°C  
Cu 50  
/C02: Polyurethane coating  
Max. (upscale) or min. (downscale) value of the usable range when  
a burnout is detected.  
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8365)  
R3Y-RS8 SPECIFICATIONS  
ES-8959 Rev.9 Page 1/5  
https://www.m-system.co.jp/  
MODEL: R3Y-RS8  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Conversion accuracy: ±1.0°C (±1.8°F) except ±3.0°C  
(±5.4°F) for Cu 10 @ 25°C  
Conversion rate: 250 msec. or 1 sec. selectable  
Data range  
°C, absolute temperature: Engineering unit value × 10  
(integer)  
°F: Engineering unit value (integer)  
Data allocation: 8  
Current consumption: 100 mA  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Burnout response time: ≤ 2 sec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 500 V AC @ 1 minute (input 1 to input 2  
to input 3 to input 4 to input 5 to input 6 to input 7 to input  
8 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
RUN LED  
ERR LED  
Pin Assignment  
Functions  
B A  
20 20  
SW1  
SW2  
SW3  
RTD  
Input Connector  
Burnout  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
Input 1-4 (SW1)  
or  
Input 5-8 (SW2)  
Temp.  
Unit  
Conv.  
Rate  
ON  
ON  
ON  
B
A
1
1
R3Y-RS8 SPECIFICATIONS  
ES-8959 Rev.9 Page 2/5  
https://www.m-system.co.jp/  
MODEL: R3Y-RS8  
EXTERNAL DIMENSIONS unit: mm [inch]  
27.5 [1.08]  
110 [4.33]  
POSITIONING  
GUIDE  
R3Y-RS8 SPECIFICATIONS  
ES-8959 Rev.9 Page 3/5  
https://www.m-system.co.jp/  
MODEL: R3Y-RS8  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Input Circuit  
RTD  
INTERNAL BUS A  
Communication  
Circuit  
A
19B  
INTERNAL BUS B*  
INPUT 1  
B
18B  
Control  
Circuit  
B
17B  
Input Circuit  
RTD  
INTERNAL POWER  
A
15B  
INPUT 2  
B
14B  
B
13B  
Input Circuit  
RTD  
A
11B  
INPUT 3  
B
10B  
B
9B  
Input Circuit  
RTD  
A
7B  
INPUT 4  
B
6B  
B
5B  
Input Circuit  
RTD  
A
19A  
INPUT 5  
B
18A  
B
17A  
Input Circuit  
RTD  
A
15A  
INPUT 6  
B
14A  
B
13A  
Input Circuit  
RTD  
A
11A  
INPUT 7  
B
10A  
B
9A  
Input Circuit  
RTD  
A
7A  
INPUT 8  
B
6A  
B
5A  
*For dual redundant communication.  
• Unused Input Channels  
Close across the unused input terminals with a resistor as shown below and set the DIP switch for an  
RTD. The resistance value must match the RTD type (100Ω for Pt 100, 50Ω For Pt 50Ω)  
INPUT 1  
19B  
INPUT 2  
15B  
INPUT 3  
11B  
INPUT 4  
7B  
18B  
17B  
14B  
13B  
10B  
9B  
6B  
5B  
INPUT 5  
19A  
INPUT 6  
15A  
INPUT 7  
11A  
INPUT 8  
7A  
18A  
17A  
14A  
13A  
10A  
9A  
6A  
5A  
Unused channels left open are equal to the burnout, which turns the red ERR LED on and sets a burnout  
flag at the PLC or the host device.  
Unused channels can be specified and set so on the PC Configurator Software (model: R3CON) without  
needing to connect resistors at the field terminals.  
R3Y-RS8 SPECIFICATIONS  
ES-8959 Rev.9 Page 4/5  
https://www.m-system.co.jp/  
MODEL: R3Y-RS8  
INPUT CONNECTOR (40-pin)  
PIN NO.  
ASSIGNMENT  
PIN NO.  
ASSIGNMENT  
1A  
2A  
3A  
NC  
NC  
NC  
1B  
2B  
3B  
NC  
NC  
NC  
4A  
5A  
6A  
NC  
4B  
5B  
6B  
NC  
IN8B  
IN8B  
IN4B  
IN4B  
7A  
8A  
9A  
IN8A  
NC  
7B  
8B  
9B  
IN4A  
NC  
IN7B  
IN3B  
10A  
11A  
12A  
IN7B  
IN7A  
NC  
10B  
11B  
12B  
IN3B  
IN3A  
NC  
13A  
14A  
15A  
IN6B  
IN6B  
IN6A  
13B  
14B  
15B  
IN2B  
IN2B  
IN2A  
16A  
17A  
18A  
NC  
16B  
17B  
18B  
NC  
IN5B  
IN5B  
IN1B  
IN1B  
19A  
20A  
IN5A  
NC  
19B  
20B  
IN1A  
NC  
Specifications are subject to change without notice.  
R3Y-RS8 SPECIFICATIONS  
ES-8959 Rev.9 Page 5/5  
https://www.m-system.co.jp/  

相关型号:

R3Y-RS8W

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3Y-RS8W/CE

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3Y-RS8W/Q

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3Y-SS16N

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8N

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8NS

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8NS/CE

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8NS/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8NW

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8NW/CE

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3Y-SS8NW/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM