MODEL: R5-DC4  
internal power  
Remote I/O R5 Series  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
Output status indicator: Red LED; turns on with the outputs  
ON.  
DISCRETE OUTPUT MODULE  
(relay contact output, 4 points)  
18 (.71)  
OUTPUT SPECIFICATIONS  
Output: Relay contact, 4 points  
90  
(3.54)  
Common: Every 2 points  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
96.5  
(3.80)  
mm (inch)  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
MODEL: R5–DC4[1][2]  
Mechanical life: 2 × 10 cycles (rate 300/min.)  
7
When driving an inductive load, external contact protection  
and noise quenching recommended.  
ORDERING INFORMATION  
• Code number: R5-DC4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R5-DC4W/Q)  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R5-BS)  
Weight: 100 g (0.22 lb)  
• Specify the specification for option code /Q  
(e.g. /C01)  
NO. OF CHANNELS  
4: 4-point outputs  
PERFORMANCE  
Data allocation: 1  
[1] COMMUNICATION MODE  
S: Single  
Response time: ≤ 0.1 sec.  
W: Dual  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (Do 1 or Do 2 to  
Do 3 or Do 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
STANDARDS & APPROVALS  
EU conformity:  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
EMC Directive  
EMI EN 61000-6-4  
/C02: Polyurethane coating  
EMS EN 61000-6-2  
/C03: Rubber coating  
Low Voltage Directive  
EN 61010-1, EN 61010-2-201  
Measurement Category II (output)  
Pollution Degree 2  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R5-BS)  
Output: Euro type connector terminal  
Output to internal bus or internal power – Basic insulation  
(300 V)  
(Applicable wire size: 0.2 – 2.5 mm  
2
(AWG24 - 12),  
RoHS Directive  
stripped length 7 mm)  
Internal power: Via the base (model: R5-BS)  
Isolation: Do1 or Do2 to Do3 or Do4 to internal bus or  
R5-DC4 SPECIFICATIONS  
ES-6126 Rev.10 Page 1/3  
https://www.m-system.co.jp/  
MODEL: R5-DC4  
FUNCTIONS  
Output hold function:  
In normal conditions, the module outputs the signal from  
the preferred bus A.  
When an error is detected, the output is switched to the  
data from the bus B.  
If both are in error, the module holds the signal and stands  
by until one of the communications recovers.  
At the startup, it outputs OFF until the communication is  
established and normal data is received.  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
RUN  
1
Status Indicator LED  
2
3
4
1 2 3 4 5 6 7 8  
DO NOT USE  
4
1
5
2
6
3
Euro Type  
Connector Terminals  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
LOCKING CLAMP  
18 (.71)  
6.5  
90 (3.54)  
(.26)  
4
1
5
2
6
3
POSITIONING GUIDE  
R5-DC4 SPECIFICATIONS  
ES-6126 Rev.10 Page 2/3  
https://www.m-system.co.jp/  
MODEL: R5-DC4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN OUTPUT STATUS  
LED INDICATOR LED  
• • • •  
Isolation  
Isolation  
INTERNAL BUS A  
1
2
Communication  
Circuit  
1
2
3
4
5
6
Do 1  
*INTERNAL BUS B  
Do 2  
Control  
Circuit  
COM1  
Do 3  
3
4
INTERNAL POWER  
Do 4  
COM2  
*For dual redundant communication.  
Note: Italic typed numbers correspond to the LEDs on the front panel.  
Specifications are subject to change without notice.  
R5-DC4 SPECIFICATIONS  
ES-6126 Rev.10 Page 3/3  
https://www.m-system.co.jp/  

相关型号:

R5-DC4S

Remote I/O R5 Series DISCRETE OUTPUT MODULE
MSYSTEM

R5-DC4S/Q

Remote I/O R5 Series DISCRETE OUTPUT MODULE
MSYSTEM

R5-DC4W

Remote I/O R5 Series DISCRETE OUTPUT MODULE
MSYSTEM

R5-DC4W/Q

Remote I/O R5 Series DISCRETE OUTPUT MODULE
MSYSTEM

R5-DS

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-DSS

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-DSS/Q

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-DSS/S

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-DSW

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-DSW/Q

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-DSW/S

Remote I/O R5 Series 4 – 20 mA INPUT MODULE
MSYSTEM

R5-E-WHT-BLK-C-F-0

Rocker Switch, DPDT, On-(on), Momentary, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH