R5-PSR/Q [MSYSTEM]
Remote I/O R5 Series;型号: | R5-PSR/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R5 Series |
文件: | 总3页 (文件大小:99K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R5-PS
master device (PLD or PC etc.), RUN contact output of Power
Supply Module turns ON.
Remote I/O R5 Series
• When using with dual redundant communication or two
system.
POWER SUPPLY MODULE
During both Network Module or one of them communicates
normally with a master device (PLD or PC etc.), RUN contact
output of Power Supply Module turns ON.
45 (1.77)
• When using R5-PS with redundant or two system.
RUN contact output works in same function for both cases.
However, when I/O capacity code of installation base is
"05:5 slots (single communication mode)" or "09: 9 slots
(single communication mode)", the RUN contact output of
Power Supply Module installed in a Extender Power Module
Base (model: R5-EX1) is not available.
90
(3.54)
90
(3.54)
mm (inch)
MODEL: R5–PS[1][2]
GENERAL SPECIFICATIONS
Connection
ORDERING INFORMATION
• Code number: R5-PS[1][2]
•Power input or RUN contact output: M3.5 screw terminals
(torque 0.8 N·m)
Specify a code from below for each of [1] and [2].
(e.g. R5-PSR/Q)
•Internal bus or internal power: Via the Installation Base
(model: R5-BS)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
Isolation: Internal bus or internal power to power supply to
RUN contact output to FG
[1] POWER INPUT
Power LED: Bi-color (red/amber) LED;
Red when the power is supplied; Amber at RUN contact
output ON.
AC Power
K: 100 – 120 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 200 – 240 V AC
■ RUN CONTACT OUTPUT
Contact turns ON (closed) while data from the host is
normally received; OFF (open) with loss of communication
for approx. 3 seconds.
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When
7
driving an inductive load, external contact protection and
noise quenching recommended.
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
INSTALLATION
Power consumption
/C02: Polyurethane coating
/C03: Rubber coating
•AC: Approx. 90 VA
TERMINAL SCREW MATERIAL
/S01: Stainless steel
•DC: Approx. 45 W or 1.8 A
Output current: 1.5 A continuous at 21 V DC;
(Total current continuously consumed at the network
modules and I/O modules must be within 1.5 A.)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
NOTICE
■ RUN CONTACT OUTPUT
• Function of RUN contact output
During a Network Module communicates normally with a
R5-PS SPECIFICATIONS
ES-6110 Rev.14 Page 1/3
https://www.m-system.co.jp/
MODEL: R5-PS
Mounting: Installation Base (model: R5-BS) or Extender
Power Supply Module Base (R5-EX1)
Weight: 250 g (0.55 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (Internal bus or
internal power to power input to RUN output to FG)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (RUN contact output)
Installation Category II (power input)
Pollution Degree 2
Internal power or RUN contact output to power input to FG:
Reinforced insulation (300 V)
Internal power to RUN contact output: Basic insulation
(300 V)
RoHS Directive
EXTERNAL VIEW
POWER
Power LED
R5-PS SPECIFICATIONS
ES-6110 Rev.14 Page 2/3
https://www.m-system.co.jp/
MODEL: R5-PS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
LOCKING CLAMP
45 (1.77)
90 (3.54)
POSITIONING GUIDE
5–M3.5 TERMINAL SCREW
1
2
3
4
5
7 (.28)
TERMINAL COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
POWER LED
Isolation
1
2
3
4
5
U (+)
V (–)
INTERNAL POWER
POWER INPUT
Control
Circuit
*FG
RUN +
RUN –
RUN CONTACT OUTPUT
INTERNAL BUS
*In order to improve EMC performance, bond the FG terminal to ground.
Caution: This terminal is NOT a protective conductor terminal.
Specifications are subject to change without notice.
R5-PS SPECIFICATIONS
ES-6110 Rev.14 Page 3/3
https://www.m-system.co.jp/