4-WIRE RTD INPUT MODULE
18 (.71)
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base
(model: R5-BSx)
90
(3.54)
Input: Euro type connector terminal
Wire size AWG24-12 (0.2 – 2.5 mm )
2
Power supply: Via the base (model: R5-BSx)
Isolation: Input to internal power
96.5
(3.80)
mm (inch)
Temperature unit: °C
Burnout protection: Upscale standard; downscale selectable
using the PC Configurator.
MODEL: R5H-RS1[1][2][3]
Linearization: Standard
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ORDERING INFORMATION
• Code number: R5H-RS1[1][2][3]
Specify a code from below for each [1] through [3]
(e.g. R5H-RS1A1W)
INPUT SPECIFICATIONS
Maximum leadwire resistance: 10 Ω per wire
Sensing current: ≤ 1 mA
NO. OF CHANNELS
1: 1 channel
Temperature range: 0 – 100°C, 0 – 300°C
Value at burnout: -274 – 323°C
[1] INPUT RTD (4-wire)
A: Pt 100
Reference resistance factory setting
B: Pt 200
Pt 100: Rt = Ro (1 + At + Bt
2)
Refer to ‘Reference resistance factory setting’ under‘Input’
specifications for more information.
where
A = 3.9083 × 10–3 [°C–1
]
B = -5.775 × 10–7 [°C–2
]
Ro = 100 [Ω]
[2] TEMPERATURE RANGE
1: 0 – 100°C
IEC 751-1995 (JIS C1604-1997)
Pt 200: Same equation except Ro = 200 [Ω]
3: 0 – 300°C
INSTALLATION
Current consumption: 50 mA (21 V DC from power supply
[3] COMMUNICATION MODE
S: Single
module)
W: Dual
Operating temperature: 20 to 40°C (68 to 104°F)
Operating humidity: 30 to 80 % RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BSx)
Weight: 100 g (3.53 oz)
RELATED PRODUCTS
•Remote I/O R5 Series
Base (model: R5-BS)
Power Supply Module (model: R5-PS)
Network Module (model: R5-Nx)
PERFORMANCE
Blank Filler Module (model: R5-DM)
Temperature range 0 – 100°C
Resolution: ±0.01°C @ 25 ±3°C
Conversion accuracy: ±0.03°C @ 25 ±3°C
Temperature range 0 – 300°C
Resolution: ±0.01°C @ 25 ±3°C
Please refer to the data sheet for the respective models for
detailed information about the software and I/O modules.
•PC configurator software (model: R5HCFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
http://www.m-system.co.jp/
R5H-RS SPECIFICATIONS
ES-6109 Rev.5 Page 1/6
MODEL: R5H-RS
Conversion accuracy: ±0.1°C @ 25 ±3°C
Data range: Engineering unit value × 100 (integer)
Data allocation: 1
Temp. coefficient: ±0.004 %/°C
Response time: ≤ 0.5 sec.
Burnout response: ≤ 10 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
EXTERNAL VIEW
RUN
RUN LED
4
1
5
2
6
3
Euro Type
Conector Terminals
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
LOCKING CLAMP
18 (.71)
6.5
90 (3.54)
(.26)
4
1
5
2
6
3
POSITIONING GUIDE
http://www.m-system.co.jp/
R5H-RS SPECIFICATIONS
ES-6109 Rev.5 Page 2/6
MODEL: R5H-RS
MOUNTING REQUIREMENTS unit: mm (inch)
■ BASE
A
90 (3.54)
16.5
(.65)
[5 (.20)]
DIN RAIL
MOUNTING
(35 mm width)
DIM.
A
MODEL
R5-BS04
R5-BS05
157 (6.18)
R5-BS08
R5-BS09
231 (9.09)
379 (14.92)
R5-BS16
■ 4 OR 5 I/O MODULE TYPE
137 (5.39)
4–M4 SCREW
*Working space required for mounting/unmounting the modules.
■ 8 OR 9 I/O MODULE TYPE
211 (8.31)
4 – M4 SCREW
*Working space required for mounting/unmounting the modules.
■ 16 I/O MODULE TYPE
359 (14.13)
4.5
5–M4 SCREW
(.18)
*Working space required for mounting/unmounting the modules.
http://www.m-system.co.jp/
R5H-RS SPECIFICATIONS
ES-6109 Rev.5 Page 3/6
MODEL: R5H-RS
MOUNTING
■ MOUNTING DIRECTION
The unit must be mounted on a vertical panel. Mounting in any other angle will cause internal temperature to rise, may
shorten the product’s life expentation or deteriorate its performance.
UP
DOWN
■ VENTILATION & MAINTENANCE SPACE
Maintain sufficient ventilation space. Do not mount the unit directly above devices which radiate great heat such as heaters,
transformers or resistors.
Maintenance space is also required above and below the unit.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED
Isolation
RTD
BUS A
Control
Circuit
Communication
Circuit
A
A
B
B
1
2
3
4
5
6
BUS B*
INTERNAL POWER
*For dual redundant communication.
SYSTEM DESCRIPTIONS
■ GENERAL
The R5H Series Remote I/O consists of a power supply module, network interface module(s), I/O module(s) and a backplane
(base). An extender base for an additional power supply module is available.
• Power Supply Module
Converts AC or DC power inputs for use in the network modules, I/O modules and for exciting discrete I/O.
• Communication Module
Converts data between the open network fieldbus (DeviceNet, etc.) and the internal communication bus, functioning as a
http://www.m-system.co.jp/
R5H-RS SPECIFICATIONS
ES-6109 Rev.5 Page 4/6
MODEL: R5H-RS
Gateway between two buses.
• I/O Module
The model R5H-RS is a high accuracy 4-wire RTD input module. Performs A/D conversion of field analog inputs; D/A conversion
of data received through the internal bus into analog/discrete outputs.
Temperature input is converted into signed binary data which equals 100 times its engineering unit value (°C). e.g. 25.53°C
is converted to 2553.
• Base
Backplane with communications and power supply buses.
An extender base is available for an additional power supply module for dual redundancy.
The R5-BS04, -BS08 and -BS16 can mount two network modules for dual redundant communication. Single mode is also usable.
The R5-BS05 and -BS09 can mount only one network module for single communication mode only.
■ SINGLE COMMUNICATION MODE
When the single communication mode is employed, the input modules send out via the internal bus analog inputs to the
network module. The network module outputs the data to the field bus.
■ DUAL COMMUNICATION MODE
A dual redundant communication system can be easily achieved by employing two network modules and using dual
communication type I/O modules (model suffix code "W").
Each I/O module is equipped with two independent communication ports, which are connected to the separate network
modules.
Input modules continuously respond to request-to-send from the both lines. This secures two independent communications.
■ HOT INSERTION/REMOVAL OF I/O MODULES
Each I/O and network module has an independent CPU. Data is renewed by serial communications between modules.
Therefore no momentary lapse or bumping of analog output occurs when switching communication buses in the dual
communication mode.
Furthermore, removing or replacing modules does not affect other modules on the same backplane. It is possible to replace
them without removing the power supply. However, replacing multiple modules at once may greatly change line voltage
levels. We recommend that you replace them one by one.
PROFIBUS Standard requires that all outputs be turned off when turning the power supply on. Therefore remove the power
before replacing the PROFIBUS modules.
■ USABLE R5 MODULES
• Network Interface Module
R5-ND1: DeviceNet
R5-NM1: Modbus
R5-NC1: CC-Link
R5-NP1: PROFIBUS-DP
R5-NE1: Ethernet (Modbus/TCP)
R5-NF1: T-Link
• Base
R5-BS04: 4 I/O modules
R5-BS05: 5 I/O modules (single communication mode)
R5-BS08: 8 I/O modules
R5-BS09: 9 I/O modules (single communication mode)
R5-BS16: 16 I/O modules
R5-EX1: Extender base for Power Supply Module
• Power Supply Module
R5-PSK: 100 – 120 V AC
R5-PSL: 200 – 240 V AC
R5-PSR: 24 V DC
• Blank Filler Module
R5-DM: Blank filler
http://www.m-system.co.jp/
R5H-RS SPECIFICATIONS
ES-6109 Rev.5 Page 5/6
MODEL: R5H-RS
Mount Input Modules at odd number slots, and Blank Filler Modules at even number slots. The R5 series I/O modules cannot
be mixed with the R5H series.
■ R5-BS04, -BS08, -BS16
•Single Communication Mode (one Network Module)
•Dual Communication Mode (two Network Modules)
Internal Communication
Bus
Internal Communication
Network Modules Bus
Power Module
Network Module
Power Module
Input & Blank Filler Modules
Input & Blank Filler Modules
R5–PSx
R5–
ND1
R5H R5–DM R5H R5–DM R5H R5–DM R5H R5–DM
R5–PSx
R5–
ND1
R5–
R5H R5–DM R5H R5–DM R5H R5–DM R5H R5–DM
–RS –RS –RS
–RS
–RS
–RS
–RS
ND1 –RS
A
1
2
3
4
5
n
A
B
1
2
3
4
5
n
A
B
Power Input Network Bus A
I/O Signals
Power Input
Network Buses
I/O Signals
•Dual Redundant Power Supply
An extender base is available for an additional power supply module for dual redundancy.
Dual mode I/O modules can be used in single mode, while the communication bus B does not operate if single mode modules
are used in dual mode.
■ R5-BS05, -BS09
•Single Communication Mode (one Network Module)
Power Module
Network Module
Input & Blank Filler Modules
R5–PSx
R5–
R5H R5–DM R5H R5–DM R5H R5–DM R5H R5–DM R5H
–RS –RS –RS –RS
ND1 –RS
1
2
3
4
5
6
n
Power Input
Network Bus
I/O Signals
Specifications are subject to change without notice.
http://www.m-system.co.jp/
R5H-RS SPECIFICATIONS
ES-6109 Rev.5 Page 6/6