R5T-YS1W [MSYSTEM]
Remote I/O R5 Series 4 - 20 mA OUTPUT MODULE;型号: | R5T-YS1W |
厂家: | M-SYSTEM |
描述: | Remote I/O R5 Series 4 - 20 mA OUTPUT MODULE 输出元件 |
文件: | 总3页 (文件大小:110K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R5T-YS
TERMINAL SCREW MATERIAL
Remote I/O R5 Series
/S01: Stainless steel
4 - 20 mA OUTPUT MODULE
(screw terminal block)
GENERAL SPECIFICATIONS
Connection
18 (.71)
Internal bus: Via the Installation Base (model: R5-BS)
Output: M3.5 screw terminal block (torque 0.8 N·m)
Internal power: Via the base (model: R5-BS)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
90
(3.54)
Isolation: Output 1 to output 2 to internal bus or internal
power
137
(5.39)
Output hold: Setting of output hold or off for communication
error with side DIP SW
mm (inch)
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
MODEL: R5T-YS[1][2]/A[3]
ORDERING INFORMATION
• Code number: R5T-YS[1][2]/A[3]
Specify a code from below for each [1] through [3].
(e.g. R5T-YS1W/A/H/Q)
OUTPUT SPECIFICATIONS
Output range: 4 – 20 mA DC
Load resistance: 300 Ω max. (600 Ω max. with Option /H)
• Specify the specification for option code /Q
(e.g. /C01/S01)
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 110 g (0.24 lb)
[1] NO. OF CHANNELS
1: 1
2: 2
[2] COMMUNICATION MODE
S: Single
PERFORMANCE
Conversion accuracy: ±0.1 %
W: Dual
Data range: 0 – 10000 of the output range
Data allocation: 1 (2 for 2-channel type)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
With Option /H, ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output 1 to output 2 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
OUTPUT HOLD
/A: With output hold setting switch
[3] OPTIONS (multiple selections)
Load Resistance
blank: ≤ 300 Ω
/H: ≤ 600Ω (available only for 1-channel output type)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
STANDARDS & APPROVALS
EU conformity:
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
/C02: Polyurethane coating
/C03: Rubber coating
EN 50581
R5T-YS SPECIFICATIONS
ES-6121 Rev.8 Page 1/3
http://www.m-system.co.jp/
MODEL: R5T-YS
FUNCTIONS
Output hold function:
In normal conditions, the module outputs the signal from
the preferred internal bus A.
When an error is detected, the output is switched to the
data from the internal bus B.
If both are in error, when the DIP switch on the side panel is
OFF, the module holds and output the last received data.
When the DIP switch 1 is ON, the module holds and output
-15 % of the selected range (approx. 1.6 mA).
Either internal bus A or bus B becomes normal, output
recovers.
EXTERNAL VIEW
■ SIDE VIEW
■ FRONT VIEW
Function
RUN
1 2 3 4 5 6 7 8
RUN LED
Output Hold or
Output OFF
4
5
2
6
3
1
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
LOCKING CLAMP
18 (.71)
38.5 (1.52)
98.5 (3.88)
TERMINAL COVER
8.2 (.32)
6–M3.5
TERMINAL
SCREWS
4
5
2
6
3
7.2 (.28)
POSITIONING GUIDE
1
R5T-YS SPECIFICATIONS
ES-6121 Rev.8 Page 2/3
http://www.m-system.co.jp/
MODEL: R5T-YS
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED
DIP SW
Isolation
Isolation
INTERNAL BUS A
Communication
Circuit
+
–
1
2
*INTERNAL BUS B
OUTPUT 1
OUTPUT 2
Control
Circuit
4
5
3
6
+
–
INTERNAL POWER
* For dual redundant communication.
Note: The section enclosed by broken line is with 2-ch. option.
Specifications are subject to change without notice.
R5T-YS SPECIFICATIONS
ES-6121 Rev.8 Page 3/3
http://www.m-system.co.jp/