R7FN-YS2 [MSYSTEM]
Remote I/O R7 Series FLEX NETWORK I/O MODULE;型号: | R7FN-YS2 |
厂家: | M-SYSTEM |
描述: | Remote I/O R7 Series FLEX NETWORK I/O MODULE |
文件: | 总5页 (文件大小:161K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R7FN-YS2
(No. ESU-7808-YS2)
Remote I/O R7 Series
RELATED PRODUCTS
FLEX NETWORK I/O MODULE
(2 points DC current output, isolated)
Functions & Features
• PC configurator software (model: R7CON)
The configurator software is downloadable at M-System’s
web site.
• 2 points DC current output module for FLEX NETWORK
• Easy parameter setting of individual channels with M-
System's configurator software
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
FLEX NETWORK is registered trademark of Digital
Electronics Corporation in Japan.
• Screen editor software (model: GP-Pro EX)
Screen editor software GP-Pro EX (Ver.2.70 or higher) is
available.
115 (4.53)
For versions between 2.60 and 2.70, the driver must be
installed. The driver is downloadable at Digital Electronics
Corporation's web site. http://www.proface.co.jp/
53 (2.09)
GENERAL SPECIFICATIONS
Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
54 (2.13)
mm (inch)
• Communication cable
MODEL: R7FN–YS2-R[1]
Recommended manufacture: Japan Solderless Terminal
MFG.Co.Ltd
ORDERING INFORMATION
• Code number: R7FN-YS2-R[1]
Specify a code from below for [1].
(e.g. R7FN-YS2-R/Q)
Applicable wire size: 0.2 to 0.5 mm
2
(AWG 26 to 22)
• Others
Recommended manufacture: Japan solderless terminal
MFG.Co.Ltd, Nichifu Co.,ltd
• Specify the specification for option code /Q
(e.g. /C01/SET)
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Output 0 to output 1 to FLEX NETWORK to power
to FG
I/O TYPE
YS2: DC current output, 2 points
Zero adjustments: Configurable via R7CON
Span adjustments: Configurable via R7CON
Output at the loss of communication:
Output hold (*), Output clear
POWER INPUT
DC Power
R: 24 V DC
Selectable with the front DIP SW
(*) factory default setting
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Status indicator LED: PWR, RUN
(Refer to the instruction manual)
■Recommended solderless terminal
[1] OPTIONS
blank: none
/Q: Options other than the above (specify the specification)
3.3 (.13) max
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
mm (inch)
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
R7FN-YS2 SPECIFICATIONS
ES-7808-E Rev.0 Page 1/5
http://www.m-system.co.jp/
MODEL: R7FN-YS2
FLEX NETWORK COMMUNICATION
Communication configuration: 1: N
Connection method: Multi-drop Connection
Communication method: Cyclic Time Division, half-duplex
Communication I/F: Differential, pulse transfer isolation
Error Check: Format, bit, CRC-12 verification
Max. Number of Nodes: 63 (1008 I/O points)
Required node: 2
FUNCTIONS
Output hold function:
Output at the loss of communication is selectable from
output clear (fix the output at -15 %) and output hold (last
normally received data) with DIP switch.
At the startup, it outputs -15 % until the communication is
established and normal data is received.
Network cable: Pro-face’s following cable
FN-CABLE2010-31-MS (10 m)
FN-CABLE2050-31-MS (50 m)
FN-CABLE2200-31-MS (200 m)
Transmission distance: 12 Mbps: 100 meters (328 ft)(*)
6 Mbps: 200 meters (656 ft)
(*) Factory default setting
Station address: Rotary switch
(Refer to the instruction manual)
Terminating resistor: Built-in
OUTPUT SPECIFICATIONS
Output range: 4 to 20 mA DC
Load resistance: ≤ 600 Ω
Operational range: -15 to +115 % of output range
INSTALLATION
Current consumption
•DC: Approx. 140 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy: ±0.1 %
Data range: 0 – 10000 of the output range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Output delay time: ≤ 250 msec. (0 - 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (output 0 to
output 1 to FLEX NETWORK to power to FG)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
R7FN-YS2 SPECIFICATIONS
ES-7808-E Rev.0 Page 2/5
http://www.m-system.co.jp/
MODEL: R7FN-YS2
EXTERNAL VIEW
Operating Mode Setting DIP SW (SW1)
PC Configurator Jack
Station Address Setting Rotary SW
Status Indicator LED
ON
2 3 4 5 6 7 8
1
X10
8
X1
8
PWR RUN
CNFG.
STATION ADD.
4
5
6
7
10
6
7
8
9
1
2
3
1
2
3
4
5
FLEX NETWORK,
Power Supply Terminals
Output Terminals
CONNECTION DIAGRAMS
■ MASTER CONNECTION
Master Station
Slave Station
Slave Station
+
–
+
–
+
–
TR
TR
TR
Terminating
Resistor
TR
TR
TR
+
+
SHIELD
JP
JP
JP
JP
Terminating
Short Bar
–
–
FG
FG
Note: Be sure to use the terminator(s) located at both ends of the modules.
TERMINAL ASSIGNMENTS
■OUTPUT TERMINAL ASSIGNMENT
6
7
8
9
10
NC
NC
I0
NC
I1
1
2
3
4
5
NC
COM0
NC
COM1
NC
NO. ID
FUNCTION
NO. ID
FUNCTION
1
2
3
4
5
NC No connection
COM0 Common 0
NC No connection
COM1 Common 1
NC No connection
6
7
NC No connection
I0 Current 0
8
NC No connection
I1 Current 1
9
10
NC No connection
R7FN-YS2 SPECIFICATIONS
ES-7808-E Rev.0 Page 3/5
http://www.m-system.co.jp/
MODEL: R7FN-YS2
■ NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT
4
5
6
7
-
TR+ TR +24V 0V
1
2
3
-
JP+ JP
FG
NO.
1
ID
JP+
JP–
FG
FUNCTION, NOTES
Terminating resistor
Terminating resistor
FG
2
3
4
TR+
TR–
+24V
0V
Network
5
Network
6
Power input (24V DC)
Power input (0V)
7
DATA CONVERSION
■ OUTPUT RANGE AND DATA CONVERSION (FACTORY DEFAULT SETTING)
Digital output data is converted into analog representations of 0 – 100% proportional to each scaled range.
Overrange output is possible from -15 to +115% of the nominal range.
When the signal exceeds the limit, the data is fixed at -15% or +115%.
• Ouputput Range 4 – 20 mA DC
Digital Value, Decimal
Degital Value, HEX
Output Value, Engineering Unit Output value, %
-1500
0
10000
11500
FA24
0
≤ 1.6 mA
4 mA
20 mA
-15%
0%
100%
115%
2710
2CEC
≥ 22.4 mA
(mA)
22.4
20
-1500
(FA24)
4
1.6
10000
(2710)
11500
(2CEC)
I/O DATA DESCRIPTIONS
■ ANALOG OUTPUT
• Di
• Do
15
0
0
15
0
0
ADD.n
Unused
Unused
CH0
CH1
15
15
ADD.n+1
The data is 16-bit binary.
Negative value is represented in 2’s complements.
R7FN-YS2 SPECIFICATIONS
ES-7808-E Rev.0 Page 4/5
http://www.m-system.co.jp/
MODEL: R7FN-YS2
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
115 (4.53)
17 (.66)
54 (2.13)
DIN RAIL
35mm wide
4
5
6
7
6
7
8
9
10
1
2
3
1
2
3
4
5
[5 (.20)]
30 (1.18)
6 (.24)
6 (.24)
10–M3 SCREW
TERMINALS
for OUTPUT
7–M3 SCREW
TERMINALS
for FLEX NETWORK, POWER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
Output Circuit
Isolation
7
2
9
4
I0
4
5
TR+
TR–
Comm.
Circuit
OUTPUT 0
OUTPUT 1
Control
Circuit
COM0
I1
1
2
3
6
7
JP+
JP–
COM1
1
3
FG
24V DC
0V
5
6
8
10
Specifications are subject to change without notice.
R7FN-YS2 SPECIFICATIONS
ES-7808-E Rev.0 Page 5/5
http://www.m-system.co.jp/
相关型号: