R9EWTU-2001-AD4/Q [MSYSTEM]
Remote I/O R9 Series MULTI POWER MONITORING UNIT;型号: | R9EWTU-2001-AD4/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R9 Series MULTI POWER MONITORING UNIT 监视器 |
文件: | 总7页 (文件大小:253K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R9EWTU
Remote I/O R9 Series
EXTENSION UNIT
1: With connection
MULTI POWER MONITORING UNIT
(Clamp-on current sensor CLSE, Modbus/TCP)
Functions & Features
AUXILIARY POWER SUPPLY
AD4: universal
• Multi Power Monitoring Unit for Modbus/TCP (Ethernet)
• By using clamp-on current sensors, there is no need of
current transformers.
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
ripple 10 %p-p max)
• Up to 8 circuits can be measured. (Common voltage
measurement)
[1] OPTIONS
blank: none
• Current sensors are easy to install in existing systems.
Wide input range of 5 to 600 A is availabe.
• All measured values, counter values, display mode,
setting data are stored in the non-volatile memory when
power is off.
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• By using SD card, data logging of current and power etc.
with calendar is available.
/C02: Polyurethane coating
/C03: Rubber coating
125 (4.92)
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-6224)
140 (5.51)
RELATED PRODUCTS
• Discrete I/O extension unit (model: R9WTU-ED)
• Multi power monitoring extension unit (model: R9WTU-EP)
• PC configurator software (model: PMCFG)
Downloadable at M-System’s web site.
80 (3.15)
mm (inch)
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
MODEL: R9EWTU-2001-AD4[1]
ORDERING INFORMATION
• Code number: R9EWTU-2001-AD4[1]
Specify a code from below for [1].
(e.g. R9EWTU-2001-AD4/Q)
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product
package, must be ordered separately. Required number
depends upon the system configuration.
• SD card
• Specify the specification for option code /Q
(e.g. /C01/SET)
A SD card is required to store data in the unit.
Use the specified model number of memory card.
Available for purchase from M-System. Consult M-System.
- Hagiwara Solutions NSD6-004GH(B21SEI
(NSD6-004GH(A00SDI, NSDA-004GT,
CONFIGURATION
2: Single-phase/2-wire, 3-phase/3-wire, single-phase/3-wire; 8 circuits
NSDA-004GL ... discontinued)
CONNECTION
0: Terminal block
- Apacer Technology AP-ISD04GIS4B-3T
(AP-ISD04GIS4B-T ... discontinued)
I/O
0: Without
GENERAL SPECIFICATIONS
Construction: Stand-alone
Degree of protection: IP20
Connection
Auxiliary power or voltage input: M3.5 screw terminals
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 1/7
http://www.m-system.co.jp/
MODEL: R9EWTU
(torque 0.8 N·m)
ETHERNET COMMUNICATION
Current input: M3 screw terminals (torque 0.5 N·m)
Ethernet: RJ-45 modular jack
Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Protocol: Modbus/TCP
Solderless terminal: Refer to the drawing at the end of the
section.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Data: RTU (Binary)
Max. number of socket connections: 2
Transmission media: 10BASE-T (STP, Category 5) 100BASE-
TX (STP, Category 5e)
Applicable wire size
M3 screw terminal: 0.25 to 1.65 mm
2
(AWG 22 to 16)
(AWG 16 to 14)
M3.5 screw terminal: 1.04 to 2.63 mm
2
Max. length of fieldbus segment: 100 meters
IP address: 192.168.0.1 (factory setting);
Selectable with PC Configurator Software (model: PMCFG)
Port No.: 502
Configuration: Single-phase/2-wire, single-phase/3-wire, 3-
phase/3-wire
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Sensor core to sensor output or current input or
voltage input to Ethernet to auxiliary power to FE1
■ Measured variables
Ethernet indicator LED: Link, Link100, COL
INPUT SPECIFICATIONS
Frequency: 50 / 60 Hz (45 – 65 Hz)
• Voltage Input
Voltage: R – N, S – N, T – N, R – S, S – T, T – R
Current: R, S, T, N
Rated voltage
Active / reactive / apparent power: R, S, T, Σ
Power factor: R, S, T, Σ
•Between lines: 400 V AC
•Line-neutral (phase voltage): 230 V (single-phase / 2-wire
and 3-wire)
Frequency
Active energy: Incoming
Input burden: ≤ ULN2 / 300 kΩ / phase
Overload capacity: 200 % of rating for 10 sec., 120 %
continuous
Reactive energy: Incoming lag
Active / reactive / apparent power intervals (demand)
Average (demand) current: R, S, T, N
Harmonic contents: Σ
Selectable primary voltage range: 50 – 400 000 V
• Current Input
Voltage: R - N, S - N, T - N, R - S, S - T, T - R
Current: R, S, T, N
CLSE-R5: 0 – 5 A AC
CLSE-05: 0 – 50 A AC
Max. and min. values
CLSE-10: 0 – 100 A AC
Calendar log (inserting SD card): Voltage, Current, power,
electric energy, power factor
CLSE-20: 0 – 200 A AC
CLSE-40: 0 – 400 A AC
Operating mode setting: Connection, clamp-on sensor
selection
CLSE-60: 0 – 600 A AC
Overload capacity: 120 % continous, 500 % for 10 sec.
Note: Use for the circuit not exceed 480 V
Selectable primary current range: 1 – 20 000 A (Using CLSE-
R5 the unit is configurable only with configurator software.)
Operational range
Status indicators: Power, SD Card, RUN
■Recommended solderless terminal size - M3
3.3 (.13) max
Current: 0 – 120 % of the rating
Voltage: 10 – 120 % of the rating
Apparent power: ≤ 120 % of the rating
Active/reactive power: ±120 % of the rating
Frequency: 45 – 65 Hz
mm (inch)
■Recommended solderless terminal size - M3.5
3. (.1 ) max
Power factor: ±1
INSTALLATION
Auxiliary power supply
mm (inch)
•AC: < 9 VA
•DC: < 3 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 2/7
http://www.m-system.co.jp/
MODEL: R9EWTU
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 500 g (1.1 lb)
PERFORMANCE
Accuracy (at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)*1
Add the accuracy of the current sensor for overall values.
Voltage: ±0.5 % of the rating*2
Current: ±0.5 % of the rating*2
Power: ±0.5 % of the rating*2
Power factor: ±1.5 %
Frequency: ±0.1 % of the rating*2
Energy: ±1 %
Harmonic contents: ±2 % of the rating*2
*1. Sensor error margin not included
*2. The described accuracy levels are ensured at the input
1% or more for neutral current in a 1-phase/3-wire circuit
and phase-S current in an unbalanced 3-phase/3-wire
circuit.
Data update period:
Harmonic contents and frequency: ≤ 1 sec.
Other: ≤ 500 msec.
Calendar clock: (with battery backup)
Accuracy: Monthly deviation 3 minutes at 25°C
Back up period: Approx. 2 years at 25°C without power
With the power on, no battery drain
Battery: Primary lithium battery (non-removable)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (current input or
voltage input to Ethernet to auxiliary power to FE1)
EXTERNAL VIEW
TOP VIEW
RJ-45 Connector for
Modbus/TCP (Ethernet)
FRONT VIEW
9
8ch 8 8ch 7 7ch 6 7ch 5 6ch 4 6ch 3 5ch 2 5ch 1
Terminal Block, Current Input 2
T2 3L 1L 3L 1L 3L 1L 3L 1L
18 8ch17 8ch16 7ch15 7ch14 6ch13 6ch12 5ch11 5ch10
T1 3K 1K 3K 1K 3K 1K 3K 1K
SD Card Slot
Unused
RUN
LINK
LK100
COL
Operating Mode Setting DIP SW (SW1)
PC Configurator Connection Jack
Status Indicator LED
Terminal Block,
Voltage Input / Auxiliary Power Supply
10 1ch11 1ch12 2ch13 2ch14 3ch15 3ch16 4ch17 4ch18
NC 1K 3K 1K 3K 1K 3K 1K 3K
4
5
6
7
P1 P2 P3
1
N
3
Terminal Block, Current Input 1
2
1
1ch
2 1ch 3 2ch 4 2ch 5 3ch 6 3ch 7 4ch 8 4ch 9
U(+) V(−) FE1
NC 1L 3L 1L 3L 1L 3L 1L 3L
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 3/7
http://www.m-system.co.jp/
MODEL: R9EWTU
TERMINAL CONNECTIONS
Use the model CLSE clamp sensor for current inputs.
The figure below shows only one circuit.
A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8).
Grounding is not required for low voltage circuits.
System /
Application
System /
Application
Terminal
Terminal
P1 P2 P3 1K 1L
P1
N
1K 1L
k
l
source
L1
load
k
l
source
L1
load
K
L
K
L
L2
L3
Three-phase
/ 3-wire
N
Single-phase
/ 2-wire
balanced
load
P1 P2 P3
1K 1L
P1
N
1K 1L
u
v
v
u
u
v
k
l
source
L1
load
k
l
U
V
V
U
source
L1
U
V
load
K
L
K
L
L2
L3
N
P1
N P3 1K 1L 3K 3L
P1 P2 P3 1K 1L 3K 3L
k
l
source
L1
N
load
k
l
source
L1
load
K
L
k
l
K
L
k
l
L2
L3
Three-phase
/ 3-wire
L2
K
L
K
L
Single-phase
/ 3-wire
unbalanced
load
P1
N
P3
1K 1L 3K 3L
P1 P2 P3
1K 1L 3K 3L
u
v
v
u
u
v
v
u
k
l
source
L1
load
U
V
V
U
k
l
source
L1
load
U
V
V
U
K
L
k
l
K
L
k
l
N
L2
L3
L2
K
L
K
L
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 4/7
http://www.m-system.co.jp/
MODEL: R9EWTU
TERMINAL ASSIGNMENTS
• Auxiliary Power Supply, Voltage Input
• Current Input 2
4
5
6
7
9
8ch
8
8ch
7
7ch
6
7ch
5
6ch
4
6ch
3
5ch
2
5ch
1
P1
P2
P3
N
T2
3L
1L
3L
1L
3L
1L
3L
1L
1
2
3
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10
U(+) V(−) FE1
T1
3K
1K
3K
1K
3K
1K
3K
1K
No.
ID
FUNCTION
No.
ID
FUNCTION
No.
ID
FUNCTION
1
2
3
4
5
6
7
U(+) Auxiliary power (+)
V(−) Auxiliary power (−)
FE1 Power ground
1
2
3
4
5
6
7
8
9
5ch 1L Ch.5, Current input 1L
5ch 3L Ch.5, Current input 3L
6ch 1L Ch.6, Current input 1L
6ch 3L Ch.6, Current input 3L
7ch 1L Ch.7, Current input 1L
7ch 3L Ch.7, Current input 3L
8ch 1L Ch.8, Current input 1L
8ch 3L Ch.8, Current input 3L
10
11
12
13
14
15
16
17
18
5ch 1K Ch.5, Current input 1K
5ch 3K Ch.5, Current input 3K
6ch 1K Ch.6, Current input 1K
6ch 3K Ch.6, Current input 3K
7ch 1K Ch.7, Current input 1K
7ch 3K Ch.7, Current input 3K
8ch 1K Ch.8, Current input 1K
8ch 3K Ch.8, Current input 3K
P1
P2
P3
N
Voltage input P1
Voltage input P2
Voltage input P3
Voltage input N
T2
Unused
T1
Unused
• Current Input 1
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18
NC
1K
3K
1K
3K
1K
3K
1K
3K
1
1ch
2
1ch
3
2ch
4
2ch
5
3ch
6
3ch
7
4ch
8
4ch
9
NC
1L
3L
1L
3L
1L
3L
1L
3L
No.
ID
FUNCTION
Unused
No.
ID
FUNCTION
Unused
1
2
3
4
5
6
7
8
9
NC
10
11
12
13
14
15
16
17
18
NC
1ch 1L Ch.1, Current input 1L
1ch 3L Ch.1, Current input 3L
2ch 1L Ch.2, Current input 1L
2ch 3L Ch.2, Current input 3L
3ch 1L Ch.3, Current input 1L
3ch 3L Ch.3, Current input 3L
4ch 1L Ch.4, Current input 1L
4ch 3L Ch.4, Current input 3L
1ch 1K Ch.1, Current input 1K
1ch 3K Ch.1, Current input 3K
2ch 1K Ch.2, Current input 1K
2ch 3K Ch.2, Current input 3K
3ch 1K Ch.3, Current input 1K
3ch 3K Ch.3, Current input 3K
4ch 1K Ch.4, Current input 1K
4ch 3K Ch.4, Current input 3K
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 5/7
http://www.m-system.co.jp/
MODEL: R9EWTU
EXTERNAL DIMENSIONS unit: mm (inch)
36−M3 SCREW TERMINAL
6 (.24)
4 − 4.5 (.18) dia. MTG HOLE
DIN RAIL
35 mm wide
75 (2.95)
6.5 (.25)
[4 (.16)]
125 (4.92)
80 (3.15)
7−M3.5 SCREW TERMINALS
7.3 (.29)
MOUNTING REQUIREMENTS unit: mm (inch)
■ SINGLE MOUNTING
75 (2.95)
4–M4
Pitch 130 (5.12) min.
■ BASIC + EXTENSION UNIT
75 (2.95)
70.5 (2.78)
6–M4
Pitch 223 (8.78) min.
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 6/7
http://www.m-system.co.jp/
MODEL: R9EWTU
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
U(+)
V(−)
FE1
P1
1
2
3
4
5
6
7
AUXILIARY
POWER SUPPLY
Isolation
AUX. POWER SUPPLY
VOLTAGE INPUT
RJ-45 CONNECTOR
Modbus/TCP (Ethernet)
P2
VOLTAGE
P3
N
10
1
1K
11
2
1K
1L
3K
3L
1L
Ch. 5
CURRENT
3K
Ch. 1
CURRENT
11
2
12
3
3L
1K
12
3
13
4
1K
1L
3K
3L
Control
Circuit
1L
Ch. 6
CURRENT
3K
Ch. 2
CURRENT
13
4
14
5
3L
1K
14
5
15
6
1K
1L
3K
3L
CURRENT INPUT 2
CURRENT INPUT 1
1L
Ch. 7
CURRENT
3K
Ch. 3
CURRENT
15
6
16
7
3L
1K
16
7
17
8
1K
1L
1L
Ch. 8
CURRENT
3K
Ch. 4
CURRENT
17
8
18
9
3K
3L
3L
T2
9
1
NC
NC
18 T1
10
Specifications are subject to change without notice.
R9EWTU SPECIFICATIONS
ES-6224 Rev.8 Page 7/7
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明