R9MWTU [MSYSTEM]

Remote I/O R9 Series MULTI POWER MONITORING UNIT;
R9MWTU
型号: R9MWTU
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R9 Series MULTI POWER MONITORING UNIT

监视器
文件: 总7页 (文件大小:281K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R9MWTU  
Remote I/O R9 Series  
EXTENSION UNIT  
1: With connection  
(Extension unit does not conform to EU directive)  
MULTI POWER MONITORING UNIT  
(Clamp-on current sensor CLSE, Modbus)  
Functions & Features  
AUXILIARY POWER SUPPLY  
AD4: universal  
• Multi Power Monitoring Unit for Modbus.  
• By using clamp-on current sensors, there is no need of  
current transformers.  
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /  
110 – 240 V DC (Operational range 99 – 264 V,  
ripple 10 %p-p max)  
• Up to 8 circuits can be measured. (Common voltage  
measurement)  
• Current sensors are easy to install in existing systems.  
Wide input range of 5 to 600 A is availabe.  
• All measured values, counter values, display mode,  
setting data are stored in the non-volatile memory when  
power is off.  
[1] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• By using SD card, data logging of current and power etc.  
with calendar is available.  
/C02: Polyurethane coating  
125 (4.92)  
/C03: Rubber coating  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-6221)  
140 (5.51)  
RELATED PRODUCTS  
• Discrete I/O extension unit (model: R9WTU-ED)  
• Multi power monitoring extension unit (model: R9WTU-EP)  
• PC configurator software (model: PMCFG)  
Software downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
80 (3.15)  
mm (inch)  
MODEL: R9MWTU–2001–AD4[1]  
ORDERING INFORMATION  
• Code number: R9MWTU-2001-AD4[1]  
Specify a code from below for [1].  
(e.g. R9MWTU-2001-AD4/Q)  
• Clamp-on current sensor (model: CLSE)  
The clamp-on current sensors, not included in this product  
package, must be ordered separately. Required number  
depends upon the system configuration.  
• SD card  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
A SD card is required to store data in the unit.  
Use the specified model number of memory card.  
Available for purchase from M-System. Consult M-System.  
- Hagiwara Solutions NSD6-004GH(B21SEI  
(NSD6-004GH(A00SDI, NSDA-004GT,  
CONFIGURATION  
2: Single-phase/2-wire, 3-phase/3-wire, single-phase/3-wire; 8 circuits  
CONNECTION  
0: Terminal block  
NSDA-004GL ... discontinued)  
- Apacer Technology AP-ISD04GIS4B-3T  
(AP-ISD04GIS4B-T ... discontinued)  
I/O  
0: Without  
GENERAL SPECIFICATIONS  
Construction: Stand-alone  
Degree of protection: IP20  
Connection  
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 1/7  
https://www.m-system.co.jp/  
MODEL: R9MWTU  
Auxiliary power or voltage input: M3.5 screw terminals  
(torque 0.8 N·m)  
MODBUS COMMUNICATION  
Communication: Half-duplex, asynchronous, no procedure  
Current input: M3 screw terminals (torque 0.5 N·m)  
Modbus: M3 screw terminals (torque 0.5 N·m)  
Solderless terminal: Refer to the drawing at the end of the  
section.  
Standard: Conforms to TIA/EIA-485-A  
Transmission distance: 500 meters max.  
Transmission media: Shielded twisted-pair cable  
(CPEV-S 0.9 dia.)  
Recommended manufacturer: Japan Solderless Terminal  
MFG.Co.Ltd, Nichifu Co.,ltd  
Protocol: Modbus - RTU (default) or Modbus - ASCII  
Max. number of nodes: 31 (excluding master)  
Node address setting: 1 - 99 (with rotary switch) (factory  
default setting: 00)  
Applicable wire size  
M3 screw terminal: 0.25 to 1.65 mm  
2
(AWG 22 to 16)  
(AWG 16 to 14)  
M3.5 screw terminal: 1.04 to 2.63 mm  
2
Baud rate setting: With rotary switch 38.4 kbps (default),  
19.2 kbps, 9600 bps, 4800 bps  
Configuration: Single-phase/2-wire, single-phase/3-wire, 3-  
phase/3-wire  
Status indicator LED: Run, RD, SD, ERR  
Terminating resistor: Built-in (Selected with the DIP SW;  
factory setting: disabled)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
Isolation: Sensor core to sensor output or current input or  
voltage input to Modbus to auxiliary power to FE1  
■ Measured variables  
INPUT SPECIFICATIONS  
Frequency: 50 / 60 Hz (45 – 65 Hz)  
Voltage Input  
Voltage: R – N, S – N, T – N, R – S, S – T, T – R  
Current: R, S, T, N  
Rated voltage  
Active / reactive / apparent power: R, S, T, Σ  
Power factor: R, S, T, Σ  
Between lines: 400 V AC  
Line-neutral (phase voltage): 230 V (single-phase / 2-wire  
and 3-wire)  
Frequency  
Active energy: Incoming  
Input burden: ≤ ULN2 / 300 kΩ / phase  
Overload capacity: 200 % of rating for 10 sec., 120 %  
continuous  
Reactive energy: Incoming lag  
Active / reactive / apparent power intervals (demand)  
Average (demand) current: R, S, T, N  
Harmonic contents: Σ  
Selectable primary voltage range: 50 – 400 000 V  
Current Input  
Voltage: R - N, S - N, T - N, R - S, S - T, T - R  
Current: R, S, T, N  
CLSE-R5: 0 – 5 A AC  
CLSE-05: 0 – 50 A AC  
Max. and min. values  
CLSE-10: 0 – 100 A AC  
Calendar log (inserting SD card): Voltage, Current, power,  
electric energy, power factor  
CLSE-20: 0 – 200 A AC  
CLSE-40: 0 – 400 A AC  
Operating mode setting: Connection, clamp-on sensor  
selection  
CLSE-60: 0 – 600 A AC  
Overload capacity: 120 % continous, 500 % for 10 sec.  
Note: Use for the circuit not exceed 480 V  
Selectable primary current range: 1 – 20 000 A (Using CLSE-  
R5 the unit is configurable only with configurator software.)  
Operational range  
Status indicators: Power, SD Card  
■Recommended solderless terminal size - M3  
3.3 (.13) max  
Current: 0 – 120 % of the rating  
Voltage: 10 – 120 % of the rating  
Apparent power: ≤ 120 % of the rating  
Active/reactive power: ±120 % of the rating  
Frequency: 45 – 65 Hz  
mm (inch)  
■Recommended solderless terminal size - M3.5  
3. (.1 ) max  
Power factor: ±1  
INSTALLATION  
Auxiliary power supply  
mm (inch)  
AC: < 7 VA  
DC: < 1.2 W  
Operating temperature: -10 to +55°C (14 to 131°F)  
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 2/7  
https://www.m-system.co.jp/  
MODEL: R9MWTU  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Surface or DIN rail  
Weight: 500 g (1.1 lb)  
PERFORMANCE  
Accuracy (at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)*1  
Add the accuracy of the current sensor for overall values.  
Voltage: ±0.5 % of the rating*2  
Current: ±0.5 % of the rating*2  
Power: ±0.5 % of the rating*2  
Power factor: ±1.5 %  
Frequency: ±0.1 % of the rating*2  
Energy: ±1 %  
Harmonic contents: ±2 % of the rating*2  
*1. Sensor error margin not included  
*2. The described accuracy levels are ensured at the input  
1% or more for neutral current in a 1-phase/3-wire circuit  
and phase-S current in an unbalanced 3-phase/3-wire  
circuit.  
Data update period:  
Harmonic contents and frequency: ≤ 1 sec.  
Other: ≤ 500 msec.  
Calendar clock: (with battery backup)  
Accuracy: Monthly deviation 3 minutes at 25°C  
Back up period: Approx. 2 years at 25°C without power  
With the power on, no battery drain  
Battery: Primary lithium battery (non-removable)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(current input or voltage input to Modbus to auxiliary power  
or FE1)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1,EN 61010-2-201  
Measurement Category II (input)  
Installation Category II (auxiliary power)  
Pollution Degree 2  
Input to Modbus: Reinforced insulation (400 V)  
Input or Modbus to auxiliary power: Reinforced insulation  
(300 V)  
RoHS Directive  
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 3/7  
https://www.m-system.co.jp/  
MODEL: R9MWTU  
EXTERNAL VIEW  
FRONT VIEW  
9
8ch 8 8ch 7 7ch 6 7ch 5 6ch 4 6ch 3 5ch 2 5ch 1  
3
2
1
Modbus Terminals  
Terminal Block, Current Input 2  
T2 3L 1L 3L 1L 3L 1L 3L 1L  
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10  
FE SLD DB  
5
7
6
4
NC NC DG DA  
T1 3K 1K 3K 1K 3K 1K 3K 1K  
Terminating Resistor SW  
Term on  
SD Card Slot  
Node Address Setting Rotary SW  
Baud Rate Setting Rotary SW  
Operating Mode Setting DIP SW (SW1)  
PC Configurator Connection Jack  
Status Indicator LED  
Terminal Block,  
Voltage Input / Auxiliary Power Supply  
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18  
NC 1K 3K 1K 3K 1K 3K 1K 3K  
4
5
6
7
P1 P2 P3  
1
N
3
Terminal Block, Current Input 1  
2
1
1ch  
2 1ch 3 2ch 4 2ch 5 3ch 6 3ch 7 4ch 8 4ch 9  
(
U +  
)
(-)  
V
FE1  
NC 1L 3L 1L 3L 1L 3L 1L 3L  
TERMINAL CONNECTIONS  
Use the model CLSE clamp sensor for current inputs.  
The figure below shows only one circuit.  
A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8).  
Grounding is not required for low voltage circuits.  
System /  
Application  
System /  
Application  
Terminal  
Terminal  
P1 P2 P3 1K 1L  
P1  
N
1K 1L  
k
l
source  
L1  
load  
k
l
source  
L1  
load  
K
L
K
L
L2  
L3  
Three-phase  
/ 3-wire  
N
Single-phase  
/ 2-wire  
balanced  
load  
P1 P2 P3  
1K 1L  
P1  
N
1K 1L  
u
v
v
u
u
v
k
l
source  
L1  
load  
k
l
U
V
V
U
source  
L1  
U
V
load  
K
L
K
L
L2  
L3  
N
P1  
N P3 1K 1L 3K 3L  
P1 P2 P3 1K 1L 3K 3L  
k
l
source  
L1  
N
load  
k
l
source  
L1  
load  
K
L
k
l
K
L
k
l
L2  
L3  
Three-phase  
/ 3-wire  
L2  
K
L
K
L
Single-phase  
/ 3-wire  
unbalanced  
load  
P1  
N
P3  
1K 1L 3K 3L  
P1 P2 P3  
1K 1L 3K 3L  
u
v
v
u
u
v
v
u
k
l
source  
L1  
load  
U
V
V
U
k
l
source  
L1  
load  
U
V
V
U
K
L
k
l
K
L
k
l
N
L2  
L3  
L2  
K
L
K
L
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 4/7  
https://www.m-system.co.jp/  
MODEL: R9MWTU  
COMMUNICATION CABLE CONNECTIONS  
MASTER CONNECTION  
Host PC  
Remote Unit  
Remote Unit  
TERMINATOR  
TERMINATOR  
Tx+/Rx+  
DA  
DB  
DA  
Tx /Rx  
DB  
DG  
SLD  
FE  
SG  
DG  
SLD  
FE  
Rx+  
Rx  
Be sure to connect the terminating resistor across DA and DB at both ends of communication line.  
When this unit is located at an end, turn the terminating resistor SW ON.  
The Host PC can be located at not only both ends but also any node of the of communication line.  
TERMINAL ASSIGNMENTS  
• Modbus  
• Current Input 2  
9
8ch  
3L  
8
8ch  
1L  
7
7ch  
3L  
6
7ch  
1L  
5
6ch  
3L  
4
6ch  
1L  
3
5ch  
3L  
2
5ch  
1L  
1
3
2
1
T2  
FE SLD DB  
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10  
7
6
5
NC NC DG DA  
4
T1  
3K  
1K  
3K  
1K  
3K  
1K  
3K  
1K  
No.  
ID  
FUNCTION  
No.  
ID  
FUNCTION  
No.  
ID  
FUNCTION  
1
2
3
4
5
6
7
DB DB  
1
2
3
4
5
6
7
8
9
5ch 1L Ch.5, Current input 1L  
5ch 3L Ch.5, Current input 3L  
6ch 1L Ch.6, Current input 1L  
6ch 3L Ch.6, Current input 3L  
7ch 1L Ch.7, Current input 1L  
7ch 3L Ch.7, Current input 3L  
8ch 1L Ch.8, Current input 1L  
8ch 3L Ch.8, Current input 3L  
10  
11  
12  
13  
14  
15  
16  
17  
18  
5ch 1K Ch.5, Current input 1K  
5ch 3K Ch.5, Current input 3K  
6ch 1K Ch.6, Current input 1K  
6ch 3K Ch.6, Current input 3K  
7ch 1K Ch.7, Current input 1K  
7ch 3K Ch.7, Current input 3K  
8ch 1K Ch.8, Current input 1K  
8ch 3K Ch.8, Current input 3K  
SLD Shield  
FE  
DA  
DG  
NC  
NC  
Modbus ground  
DA  
DG  
Unused  
Unused  
T2  
Unused  
T1  
Unused  
• Auxiliary Power Supply, Voltage Input  
• Current Input 1  
4
5
6
7
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18  
P1  
P2  
P3  
N
NC  
1K  
3K  
1K  
3K  
1K  
3K  
1K  
3K  
1
2
3
1
1ch  
2
1ch  
3
2ch  
4
2ch  
5
3ch  
6
3ch  
7
4ch  
8
4ch  
9
U(+) V(−) FE1  
NC  
1L  
3L  
1L  
3L  
1L  
3L  
1L  
3L  
No.  
ID  
FUNCTION  
No.  
ID  
FUNCTION  
Unused  
No.  
ID  
FUNCTION  
Unused  
1
U(+) Auxiliary power (+)  
V(−) Auxiliary power (−)  
FE1 Power ground  
1
2
3
4
5
6
7
8
9
NC  
10  
11  
12  
13  
14  
15  
16  
17  
18  
NC  
2
3
4
5
6
7
1ch 1L Ch.1, Current input 1L  
1ch 3L Ch.1, Current input 3L  
2ch 1L Ch.2, Current input 1L  
2ch 3L Ch.2, Current input 3L  
3ch 1L Ch.3, Current input 1L  
3ch 3L Ch.3, Current input 3L  
4ch 1L Ch.4, Current input 1L  
4ch 3L Ch.4, Current input 3L  
1ch 1K Ch.1, Current input 1K  
1ch 3K Ch.1, Current input 3K  
2ch 1K Ch.2, Current input 1K  
2ch 3K Ch.2, Current input 3K  
3ch 1K Ch.3, Current input 1K  
3ch 3K Ch.3, Current input 3K  
4ch 1K Ch.4, Current input 1K  
4ch 3K Ch.4, Current input 3K  
P1  
P2  
P3  
N
Voltage input P1  
Voltage input P2  
Voltage input P3  
Voltage input N  
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 5/7  
https://www.m-system.co.jp/  
MODEL: R9MWTU  
EXTERNAL DIMENSIONS unit: mm [inch]  
43−M3 SCREW TERMINAL  
6 (.24)  
4 − 4.5 (.18) dia. MTG HOLE  
DIN RAIL  
35 mm wide  
75 (2.95)  
6.5 (.25)  
[4 (.16)]  
125 (4.92)  
80 (3.15)  
7−M3.5 SCREW TERMINALS  
7.3 (.29)  
MOUNTING REQUIREMENTS unit: mm [inch]  
SINGLE MOUNTING  
75 (2.95)  
4M4  
Pitch 130 (5.12) min.  
BASIC + EXTENSION UNIT  
75 (2.95)  
70.5 (2.78)  
6M4  
Pitch 223 (8.78) min.  
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 6/7  
https://www.m-system.co.jp/  
MODEL: R9MWTU  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Note: In order to improve EMC performance, bond the FE1 terminal to ground.  
Caution: FE1 terminal is NOT a protective conductor terminal.  
4
1
5
2
3
6
7
DA  
DB  
DG  
Comm.  
U(+)  
1
To other  
Circuit  
COMMUNICATION  
AUXILIARY  
POWER SUPPLY  
Modbus devices  
V(-)  
SLD  
FE  
2
Isolation  
FE1  
P1  
P2  
P3  
N
3
4
5
6
7
AUX. POWER SUPPLY  
VOLTAGE INPUT  
NC  
NC  
VOLTAGE  
10  
1
1K  
1L  
3K  
3L  
Ch. 5  
CURRENT  
11  
2
1K 11  
1L  
2
Ch. 1  
CURRENT  
12  
3
3K 12  
1K  
1L  
3K  
3L  
3L  
3
Ch. 6  
CURRENT  
13  
4
1K 13  
Control  
Circuit  
1L  
4
Ch. 2  
CURRENT INPUT 1  
CURRENT INPUT 2  
CURRENT  
14  
5
3K 14  
1K  
1L  
3K  
3L  
3L  
5
Ch. 7  
CURRENT  
15  
6
1K 15  
1L  
6
Ch. 3  
CURRENT  
16  
7
3K 16  
1K  
1L  
3K  
3L  
T2  
3L  
7
Ch. 8  
CURRENT  
17  
8
1K 17  
1L  
8
Ch. 4  
CURRENT  
9
3K 18  
18 T1  
9
1
3L  
NC  
NC  
10  
Specifications are subject to change without notice.  
R9MWTU SPECIFICATIONS  
ES-6221 Rev.11 Page 7/7  
https://www.m-system.co.jp/  

相关型号:

R9MWTU-2001-AD4

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9MWTU-2001-AD4/Q

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9S01830XX00

Rectifier Diode, 1 Phase, 1 Element, 3935A, 1800V V(RRM), Silicon, HERMETIC SEALED, CERAMIC PACKAGE-2
POWEREX

R9S01830XXOO

Rectifier Diode, 1 Phase, 1 Element, 3935A, 1800V V(RRM), Silicon,
POWEREX

R9S02030XX

GENERAL PURPOSE RECTIFIER DIODE 3000 Amperes 2600 Volts
POWEREX

R9S02030XX00

Rectifier Diode, 1 Phase, 1 Element, 3935A, 2000V V(RRM), Silicon, HERMETIC SEALED, CERAMIC PACKAGE-2
POWEREX

R9S02030XXOO

Rectifier Diode, 1 Phase, 1 Element, 3935A, 2000V V(RRM), Silicon,
POWEREX

R9S02230XX

GENERAL PURPOSE RECTIFIER DIODE 3000 Amperes 2600 Volts
POWEREX

R9S02230XX00

Rectifier Diode, 1 Phase, 1 Element, 3935A, 2200V V(RRM), Silicon, HERMETIC SEALED, CERAMIC PACKAGE-2
POWEREX

R9S02430XX

GENERAL PURPOSE RECTIFIER DIODE 3000 Amperes 2600 Volts
POWEREX

R9S02430XX00

Rectifier Diode, 1 Phase, 1 Element, 3935A, 2400V V(RRM), Silicon, HERMETIC SEALED, CERAMIC PACKAGE-2
POWEREX

R9S02430XXOO

Rectifier Diode, 1 Phase, 1 Element, 3935A, 2400V V(RRM), Silicon,
POWEREX