R9WTU-ED16/Q [MSYSTEM]
Remote I/O R9 Series DISCRETE I/O EXTENSION UNIT;型号: | R9WTU-ED16/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R9 Series DISCRETE I/O EXTENSION UNIT |
文件: | 总5页 (文件大小:191K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R9WTU-ED
Remote I/O R9 Series
GENERAL SPECIFICATIONS
Construction: Stand-alone
Degree of protection: IP20
DISCRETE I/O EXTENSION UNIT
(Di (internal power), Do (photo MOSFET relay), pulse
totalizer)
Connection: M3 screw terminals (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
Functions & Features
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
• Extension unit for Multi Power Monitoring Unit (model:
R9xWTU)
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
• Photo MOSFET relay output
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: R9xWTU (input or network or auxiliary power) to
input to output to between outputs
100 (3.98)
Input status indicator: Red LED; turns on with the inputs ON.
Output status indicator: Red LED; turns on with the outputs
ON.
140 (5.51)
■Recommended solderless terminal size - M3
3.3 (.13) max
80 (3.15)
mm (inch)
mm (inch)
MODEL: R9WTU-ED16[1]
INPUT SPECIFICATIONS
Common: Negative common
ORDERING INFORMATION
• Code number: R9WTU-ED16[1]
Specify a code from below for [1].
(e.g. R9WTU-ED16/Q)
Maximum frequency: 50 Hz
Minimum pulse width: 10 msec.
Max. counter value: 0 - 999 999 999
Count at overflow: Reset and restart at ‘0.’
Detecting voltage/current: 5 V DC / 5 mA approx.
ON/OFF levels: ≤ 5 kΩ / ≤ 2 V for ON;
≥ 100 kΩ / 4 V for OFF
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
Operation mode: Discrete and pulse counter
16: 16 points (Di 8, Do 8)
OUTPUT SPECIFICATIONS
Output: Photo MOSFET relay
Rating: Peack 350 V AC/DC @ 80 mA
ON resistance: ≤ 50 Ω
[1] OPTIONS
blank: none
/Q: With options (specify the specification)
Power dissipation: 320 mW
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Leakage current at OFF: ≤ 10 μA
INSTALLATION
/C02: Polyurethane coating
Power consumption
/C03: Rubber coating
•AC: ≤ 2 VA
•DC: ≤ 1.5 W
RELATED PRODUCTS
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 300 g (0.66 lb)
•Multi Power Monitoring Unit for CC-Link (model: R9CWTU)
•Multi Power Monitoring Unit for LonWorks (model: R9LWTU)
•Multi Power Monitoring Unit for Modbus (model: R9MWTU)
•Multi Power Monitoring Unit for Modbus/TCP (model:
R9EWTU)
R9WTU-ED SPECIFICATIONS
ES-6225 Rev.1 Page 1/5
http://www.m-system.co.jp/
MODEL: R9WTU-ED
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
2000 V AC @ 1 minute (R9xWTU (input or network or
auxiliary power) to input)
1500 V AC @ 1 minute (R9xWTU (input or network or
auxiliary power) to output)
1500 V AC @ 1 minute (input to output)
1500 V AC @ 1 minute (between outputs)
EXTERNAL VIEW
9
8
7
6
5
4
3
2
1
Terminal Block, Discrete Outputs
-
-
-
-
-
-
-
-
NC DO8 DO7 DO6 DO5 DO4 DO3 DO2 DO1
18 17 16 15 14 13 12 11 10
NC DO8 DO7 DO5 DO3 DO1
DO6 DO4 DO2
+
+
+
+
+
+
+
+
Output Status Indicator LED
Input Status Indicator LED
10
11
12
13
14
15
16
17
18
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 NC
Terminal Block, Discrete inputs
1
2
3
4
5
6
7
8
9
COM COM COM COM COM COM COM COM NC
TERMINAL ASSIGNMENTS
■ DISCRETE INPUT
■ DISCRETE OUTPUT
10
11
12
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 NC
13
14
15
16
17
18
9
8
7
6
5
4
3
2
1
NC DO8– DO7– DO6– DO5– DO4– DO3– DO2– DO1–
1
2
3
COM COM COM COM COM COM COM COM NC
4
5
6
7
8
9
18
17
16
15
14
13
12
11
10
NC DO8+ DO7+ DO6+ DO5+ DO4+ DO3+ DO2+ DO1+
No.
ID
No.
ID
No.
ID
No.
ID
FUNCTION
FUNCTION
FUNCTION
FUNCTION
1
2
3
4
5
6
7
8
9
COM Input comon
COM Input comon
COM Input comon
COM Input comon
COM Input comon
COM Input comon
COM Input comon
COM Input comon
10
11
12
13
14
15
16
17
18
DI1 Input 1ch
DI2 Input 2ch
DI3 Input 3ch
DI4 Input 4ch
DI5 Input 5ch
DI6 Input 6ch
DI7 Input 7ch
DI8 Input 8ch
NC Unused
1
2
3
4
5
6
7
8
9
DO1– Output 1ch–
DO2– Output 2ch–
DO3– Output 3ch–
DO4– Output 4ch–
DO5– Output 5ch–
DO6– Output 6ch–
DO7– Output 7ch–
DO8– Output 8ch–
10 DO1+ Output 1ch+
11 DO2+ Output 2ch+
12 DO3+ Output 3ch+
13 DO4+ Output 4ch+
14 DO5+ Output 5ch+
15 DO6+ Output 6ch+
16 DO7+ Output 7ch+
17 DO8+ Output 8ch+
NC
Unused
NC
Unused
18
NC Unused
R9WTU-ED SPECIFICATIONS
ES-6225 Rev.1 Page 2/5
http://www.m-system.co.jp/
MODEL: R9WTU-ED
EXTERNAL DIMENSIONS unit: mm (inch)
36−M3 SCREW TERMINAL
6 (.24)
2 − 4.5 (.18) dia. MTG HOLE
DIN RAIL
35 mm wide
6.5 (.25)
[4 (.16)]
7 (.28)
93 (3.66)
80 (3.15)
R9WTU-ED SPECIFICATIONS
ES-6225 Rev.1 Page 3/5
http://www.m-system.co.jp/
MODEL: R9WTU-ED
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Input Circuit
Output Circuits
10
11
12
13
14
15
16
17
1
10
1
DI1
DI2
DO1+
DO1–
DO2+
DO2–
DO3+
DO3–
DO4+
DO4–
DO5+
DO5–
DO6+
DO6–
DO7+
DO7–
DO8+
DO8–
NC
11
2
DI3
DI4
12
3
DI5
DI6
13
4
DI7
DI8
Control
Circuit
DISCRETE
INPUT
DISCRETE
OUTPUT
14
5
COM
COM
COM
COM
COM
COM
COM
COM
NC
2
3
15
6
4
5
16
7
6
7
17
8
8
9
9
18
18
NC
NC
■ INPUT
■ OUTPUT
10
17
10
DI1
DO1+
DI8
Control
Circuit
1
DO1–
DO8+
Control
Circuit
+
–
17
1
8
COM
COM
Excitation Supply
8
DO8–
■ Refer to the figure below for Photo MOS Relay discrete protection and noise removal.
• DC Powered
• AC Powered
Coil, etc.
Inductive loads
Coil, etc.
Inductive loads
10
10
LOAD
LOAD
1
Varistor/CR Circuit
1
Varistor/CR Circuit
U
R9WTU-ED SPECIFICATIONS
ES-6225 Rev.1 Page 4/5
http://www.m-system.co.jp/
MODEL: R9WTU-ED
Specifications are subject to change without notice.
R9WTU-ED SPECIFICATIONS
ES-6225 Rev.1 Page 5/5
http://www.m-system.co.jp/
相关型号: