SC200W-11-M2/1 [MSYSTEM]
Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER;型号: | SC200W-11-M2/1 |
厂家: | M-SYSTEM |
描述: | Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER |
文件: | 总10页 (文件大小:436K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: SC200W
/E: English
Single Loop Controller Series
(Language (Japanese or English) can be chosen by front
panel setting.)
MULTI-FUNCTION PID CONTROLLER
(color LCD with touch-panel, Modbus/NestBus
communication, expansion module function)
Configurator Interface (must be specified)
/1: Stereo jack
Terminal block (must be specified)
/T: Separable terminal
Other Options
blank: none
/Q: Option other than the above (specify the specification)
144
(5.67)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
*
mm (inch)
/C02: Polyurethane coating
/C03: Rubber coating
*Selectable with option code
TERMINAL SCREW MATERIAL
/S01: Stainless steel
MODEL: SC200W–[1][2]–[3][4]
FUNCTIONS & FEATURES
ORDERING INFORMATION
• Code number: SC200W-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. SC200W-11-M2/3/E/1/T/Q)
Functions & Features
• Color LCD with touch panel
• Five Operation views (digital display, bargraph, dual-loop
bargraph, short trend and user's parameter table views)
• Enhanced screen functions for engineering (configuration,
programming and tuning views)
• Specify the specification for option code /Q
(e.g. /C01/S01)
• Universal input x 2 points, analog input x 4 points,
discrete input x 6 points, pulse input x 5 points, high speed
pulse input x 1 point
[1] DISCRETE OUTPUT
1: Relay contact
• Current output (4-20 mA) x 2 points, voltage output (1-5
V) x 2 points, relay or photo-MOSFET relay output x 5 points
• RUN contact output (relay) x 1 point
2: Photo MOSFET relay
[2] MODBUS
1: Modbus-RTU
2: Modbus/TCP
• I/O signals can be added with remote I/O modules
connected via NestBus peer-to-peer communication
• Computation cycle selectable between 100 msec. and 3
sec. (control cycle selectable between 1 and 64 times of the
computation cycle)
[3] POWER INPUT
AC Power
• Two PID function blocks
• Advanced computation and sequence control functions
• Auto-tuning function
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)
DC Power
• Parameter input and changing with touch panel
• Function parameter setting, list printing and data
downloading/uploading available with Loop Configuration
Builder Software (model: SFEW3E)
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[4] OPTIONS (multiple selections)
• Short trend export (CSV), display parameter setting,
saving and transfer with PC Configurator Software (model:
SCCFG)
Housing Depth
blank: 250 mm
/3: 300 mm
• Control and supervision by SCADA software via Modbus
TCP/IP or RTU communication
/4: 400 mm
Language
• Selectable housing depth for ease of using existing wires
in replacement: 250 mm, 300 mm and 400 mm
blank: Japanese
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 1/10
http://www.m-system.co.jp/
MODEL: SC200W
• Separable terminal block
Sequence operation: Logic sequence and step sequence
(max. 1068 commands)
• Expansion of operations blocks due to Expansion module
Computation cycle: 100 msec. to 3 sec. (control cycle
selectable among 1, 2, 4, 8, 16, 32 and 64 times of the
computation cycle)
Typical Applications
• Replacement of conventional controllers
• Panel operation for small-scale instrumentation
MV output range: -15 - +115 %
Parameter setting: With touch panel or PC (Loop
Configuration Builder Software model: SFEW3E)
Self diagnostics: CPU monitoring with a watchdog timer
RUN contact: OFF in error detected by diagnostic (including
NestBus)
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• Loop configuration builder software (model: SFEW3E Ver.
1.101 or later)
Short trend
• PC configurator software (model: SCCFG Ver.1.84 or later)
Builder software and configurator software are
downloadable at M-System’s web site.
Storing interval: 1, 2, 5, 10, 20, 30 sec.,
1, 2, 5, 10, 30, 60 min.
Capacity: 400 points (display 200 points)
ACCESSORIES
■ Display
• Precision resistor module (model: REM4): 2 units
• Cold junction compensation sensor: 2 pcs
• Mounting brackets: 2 pcs
Display device: 4.3-inch TFT LCD
Display colors: 256
Resolution: 480 × 272 pixels
• Connector adapter: 1 pce
Pixel pitch: 0.198 × 0.198 mm (128 × 128 DPI)
Backlight: LED
(The jack on the unit and the plug of PC Configurator cable
(not included in the product) are different in size.)
Backlight life: Approx. 50 000 hours (at 50 % brightness)
Note: The backlight can be replaced in M-System factory.
The LCD must be replaced at the same time.
Screen saver standby time: 1 to 99 minutes
Scaling range: -32000 to +32000
GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Degree of protection: IP55; ensured for the front panel of
the unit independently mounted to a panel
Connection
Decimal point position: 10-1, 10-2, 10-3, 10-4, 10-5 or none
Scale divisions: 2 to 10
Engineering unit indication: Max. 8 characters
Auto/Man indicator: Green/Amber LED
Terminal screws: M3.5 screw terminals (torque 1.0 N·m)
Terminal fixing screws: M4 screw terminals
(torque 1.2 N·m)
Ethernet: RJ-45 Modular Jack
Screw terminal
Terminal screws: Nickel-plated steel (standard) or stainless
steel
Terminal fixing screws: Chrome-plated steel
Housing material: Flame-resistant resin (gray), steel
Isolation: Pv1 to Pv2 to supply output to Ai1 or Ai2 or Ai3 or
Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or
Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 to Ao1 or Ao2 to Do1
to Do2 to Do3 to Do4 to Do5 to Do6 to NestBus to Modbus-
RTU to Modbus/TCP to power to FG
PID control: Single loop, cascade, advanced
Proportional band (P): 1 to 1000 %
Integral time (I): 0.01 to 100 minutes
Derivative time (D): 0.01 to 10 minutes
Auto-tuning: Limit cycle method
Alarm: PV high & low, deviation, rate of change
Computation: 48 functions blocks available for arithmetic
operations, time functions, signal selection, limit, alarm and
other functions
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 2/10
http://www.m-system.co.jp/
MODEL: SC200W
Protocol: Modbus/TCP
Data: RTU (binary)
Connections: 2
FACTORY DEFAULT
■ LOOP 1
P : 100%
I : No integral action
D : No derivative action
Transmission media:
CAS
10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length: 100 meters
Port number: 502
H
L
PID
G02
SEQ
G81
Reverse Action
Ai 1
Pv 1
Mv 1
(PV /MV
)
1
1
*
*
1 – 5 V DC
IP address: 192.168.0.1 (factory setting)
1 – 5 V DC
4 – 20 mA DC
AL1
AL2
SUPPLY OUTPUT
Output voltage:
■ LOOP 2
P : 100%
: No integral action
D : No derivative action
24 V DC ±10 % with no load
18 V DC min. at 20 mA
Current rating: ≤ 22 mA DC
∙Shortcircuit protection
Current limited: Approx. 30 mA
I
CAS
H
L
PID
G03
SEQ
G81
Reverse Action
Ai 2
Pv 2
Mv 2
(PV /MV
)
1
1
*
*
1 – 5 V DC
1 – 5 V DC
4 – 20 mA DC
INPUT SPECIFICATIONS
■ Pv1, Pv2 (universal input)
AL3
AL4
∙Current input: 4 – 20 mA DC with input resistance 250 Ω
(REM4)
*1. Factory default setting
Use Loop Configuration Builder Software (model: SFEW3E)
to modify setting.
∙Voltage input: -10 – +10 V DC
-1 – +1 V DC
0 – 10 V DC
EXTERNAL INTERFACE
■ NestBus
1 – 5 V DC
0 – 1 V DC
Configuration: Bus type multi-drop
Standard: Conforms to TIA/EIA-485-A
Transfer rate: 19.2 kbps
Input resistance: ≥ 1 MΩ
∙Thermocouple input: K, E, J, T, B, R, S, C, N, U, L, P, PR (See
Table 1)
Protocol: NestBus (M-System’s own protocol)
Max. transmission distance: 1 kilometer
Transmission media:
Input resistance: ≥ 30 kΩ
Burnout sensing: ≤ 0.3 µA
Burnout indication: 115 % of the measuring range (upscale)
∙RTD input: Pt100 (JIS ’97, IEC), Pt100 (JIS ’89), JPt100 (JIS
’89), Pt50Ω (JIS ’81), Ni100 (See Table 2)
Maximum lead wire resistance: 100 Ω per wire
Burnout indication: 115 % of the measuring range (upscale)
Sensing current: ≤ 1 mA
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
Terminating resistor: incorporated
Card No. setting: 0 - F (16 cards; 2 assigned for one unit)
■ Modbus-RTU
Configuration: Half-duplex, asynchronous, no procedure
Standard: Conforms to TIA/EIA-485-A
Max. transmission distance: 500 meters
Transfer rate: 4800, 9600, 19.2 k, 38.4 k bps
Data bit: 8
∙Potentiometer input: Total resistance 100 Ω to 10 kΩ
Minimum span: 50 % of total resistance
Excitation: ≤ 0.6 V DC
■ Ai1, Ai2, Ai3, Ai4
Parity bit: Odd, even, none
∙Voltage input: 1 – 5 V DC
Max. node number: 15 (except the master)
Transmission media:
Input resistance: ≥ 1 MΩ
■ Pi1, Pi2, Pi3, Pi4, Pi5: Dry contact
(Di1 through Di5 are assigned to the same terminals
respectively.)
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
Terminating resistor: incorporated
Node address setting: 1 - 247
Maximum frequency: 20 Hz
■ Modbus/TCP (Ethernet)
Minimum pulse width: 25 msec.
Common: Negative common per 5 points
Sensing: Approx. 12 V DC, 6 mA
Physical layer standard: IEEE 802.3u
Data link layer: 10BASE-T / 100BASE-TX
Transfer rate: 10 / 100 Mbps, Auto Negotiation
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 3/10
http://www.m-system.co.jp/
MODEL: SC200W
ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ
■ Pi6: Dry contact
OUTPUT SPECIFICATIONS
■ Mv1, Mv2
∙Current output: 4 – 20 mA DC
Load resistance: ≤ 600 Ω
(Di6 is assigned to the same terminal.)
Maximum frequency: 10 kHz
■ Ao1, Ao2
Minimum pulse width: 0.05 msec.
Common: Negative common
∙Voltage output: 1 – 5 V DC
Load resistance: ≥ 10 kΩ
Sensing: Approx. 12 V DC, 12 mA
ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ
Excitation: 12 V DC ±10%, 15 mA
Current limiting circuit: Approx. 30 mA
■ Di1, Di2, Di3, Di4, Di5: Dry contact
(Pi1 through Pi5 are assigned to the same terminals
respectively.)
■ Discrete Output
∙Do1, Do2, Do3, Do4, Do5, RUN contact (Do6): Relay
contact
Rated load: 250 V AC @1 A (cos ø = 1)
30 V DC @1 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 60 W
Minimum load: 5 V DC @10 mA
Common: Negative common per 5 points
Sensing: Approx. 12 V DC, 6 mA
ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ
■ Di6: Dry contact
Mechanical life: 2 × 10 cycles
7
∙Do1, Do2, Do3, Do4, Do5: Photo MOSFET relay
Rating: 200 V AC/DC @0.5 A (resistive load)
ON resistance: 2.1 Ω
Maximum frequency: 4 Hz @24 V, 10 mA
ON delay time: ≤ 5.0 msec.
(Pi6 is assigned to the same terminal.)
Common: Negative common
OFF delay time: ≤ 3.0 msec.
Sensing: Approx. 12 V DC, 12 mA
ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ
[Table 1 (Thermocouple input)]
INSTALLATION
Power input
∙AC:
USABLE
RANGE (°C)
CONFORMANCE
RANGE (°C)
≤ 25 VA at 100 V AC
T/C
K (CA)
≤ 40 VA at 240 V AC
-272 to +1472
-272 to +1100
-260 to +1300
-272 to +500
24 to 1920
-150 to +1370
-170 to +1000
-180 to +1200
-170 to +400
1000 to 1760
380 to 1760
400 to 1760
100 to 2315
-130 to +1300
-200 to +600
-200 to +900
0 to 1395
•DC: ≤ 650 mA
E (CRC)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 90 %RH (non-condensing)
Mounting: Panel flush mounting (high-density mounting in
horizontal direction)
J (IC)
T (CC)
B (RH)
R
-100 to +1860
-100 to +1860
-52 to +2416
-272 to +1400
-252 to +700
-252 to +1000
-52 to +1496
-52 to +1860
Weight:
S
Approx. 1.8 kg (3.97 lb) for 250 mm depth type
Approx. 2.0 kg (4.41 lb) for 300 mm depth type
Approx. 2.5 kg (5.51 lb) for 400 mm depth type
C (WRe 5-26)
N
U
L
P (Platinel II)
PERFORMANCE
(PR)
300 to 1760
Accuracy
Overrange input (out of the usable range) is handled as burnout.
DC input: ±0.1 % ±1 digit
Thermocouple input: ±1℃ ±1 digit
±2℃ ±1 digit for B, R, S, C and PR
RTD input: ±1℃ ±1 digit
[Table 2 (RTD input)]
USABLE
RANGE (°C)
CONFORMANCE
RANGE (°C)
RTD
Pt 100 (JIS ’97, IEC
Pt 100 (JIS ’89)
JPt 100 (JIS ’89)
Pt 50Ω (JIS ’81)
Ni 100
)
-240 to +900
-240 to +900
-236 to +560
-236 to +700
-100 to +252
-200 to +850
-200 to +660
-200 to +510
-200 to +649
-80 to +250
Potentiometer input: ±0.2 % ±1 digit
DC output: ±0.1 %
Precision resistor module (REM4): ±0.1 %
Cold junction compensation:
±2°C at 25°C ±10°C
Overrange input (out of the usable range) is handled as burnout.
±4°C for S, R and PR
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 4/10
http://www.m-system.co.jp/
MODEL: SC200W
DC input: ±0.015 %/°C (±0.008 %/°F)
Thermocouple input: ±0.015 %/°C (±0.008 %/°F)
RTD input: ±0.015 %/°C (±0.008 %/°F)
Potentiometer input: ±0.015 %/°C (±0.008 %/°F)
DC output: ±0.015 %/°C (±0.008 %/°F)
Precision resistor module (REM4): ±0.015 %/°C (±0.008
%/°F)
Line voltage effect: ±0.1 % over voltage range
Calendar clock accuracy: Monthly deviation 3 minutes at
25°C
RAM memory duration in power failure for hot start:
10 minutes assured
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to
Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or
Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Ao1 or Ao2 to Do1 to Do2
or Do3 or Do4 or Do5 or Do6 to NestBus to Modbus-RTU to
Modbus/TCP to power to FG)
500 V AC @ 1 minute (Pv2 to Ai1 or Ai2 or Ai3 or Ai4)
500 V AC @ 1 minute (Mv2 to Ao1 or Ao2)
500 V AC @ 1 minute (Do2 to Do3 to Do4 to Do5 to Do6)
500 V AC @ 1 minute (Pv1 to supply output)
EXTERNAL VIEW
1
Auto/Man
2
3
4
5
6
1. TFT Color LCD with touch panel
Provides operation and engineering views to facilitate monitoring and setting
2. Configurator jack and cap
Connects with a PC where Loop Configuration Builder Software (model: SFEW3E) or PC configurator software (model: SCCFG)
is installed via a PC configurator cable (model: COP-US) and enables programming and parameter setting
3. MV value (DOWN) button
4. Acceleration button
(Accelerates MV signal’s changing speed by pressing simultaneously with MV value button)
5. MV value (UP) button
6. Auto / Man selector (changes the control mode for MV output)
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 5/10
http://www.m-system.co.jp/
MODEL: SC200W
COMMUNICATION CABLE CONNECTIONS
■ NestBus
SML
T1
SML
T1
SC200W
T1
T2
T2
T2
*1
*1
T3
T3
T3
FG
T4
T4
*2
FG
■ Modbus-RTU
R2K-1
RS-485
RS-485
SC200W
T1
SC200W
T1
T2
T3
T4
T1
RS-232-C
T2
T2
*1
*1
T3
T3
FG
FG
*2
FG
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. For noise protection, connect all shielded cables with each other and ground them at a single dedicated ground point within
the system with grounding resistance of 100 Ω or less. Note that the most suitable ground point differs depending on the system.
Also note that there may be cases where less noise is caused when the shields are left ungrounded.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
175 (6.89)
210 (8.27) max.
1
*
RJ-45 CONNECTOR
52–M3.5 SCREW
MOUNTING BRACKETS
TERMINAL COVER
4–M4 SCREW FOR
FIXING TERMINAL
14
1
40
41
42
43
44
45
46
47
48
49
50
51
52
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
Jack cap
72 (2.83)
1 (.04)
24
*2
67.5 (2.66)
(.94)
*1. For Modbus/TCP only
*2. Standard model: 250 mm (9.84”)
300 mm (11.81”)
400 mm (15.75”)
Option /3:
Option /4:
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 6/10
http://www.m-system.co.jp/
MODEL: SC200W
MOUNTING REQUIREMENTS unit: mm
■ PANEL CUTOUT unit: mm
• Single mounting
• Clustered mounting
68 +0.7
0
[68+72×(n - 1)] +1
0
n = number of units
Panel thickness 2.3 – 20
■ Caution
• IP55 is ensured for the front panel of the unit mounted independently according to a panel. Test the sealing at the mounting
surface once the device is installed.
• Set the unit on a vertical surface with its operation buttons at the lower side. Mounting in other directions may cause heat
built up inside the unit and shorten its life span or degrade its performance.
• Ensure that there is sufficient space for ventilation inside a panel. Do not install above the devices that generate high heat
such as heaters, transformers or resistors. Leave at least 30 mm (1.2 inch) space above, below and behind the unit for
maintenance purpose (e.g. wiring, removing or installing).
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 7/10
http://www.m-system.co.jp/
MODEL: SC200W
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Isolation
Isolation
Shielded Twisted-pair Cable
+
+
34
40 T1
27 T2
28 T3
41 T4
26 FG
To Other
NestBus
Devices
Discrete
Input
Circuit
Di 1 / Pi 1
–
+
+
+
35
36
37
1
Jumper*
Di 2 / Pi 2
Di 3 / Pi 3
Di 4 / Pi 4
Di 5 / Pi 5
SHLD
SHLD
Isolation
+
1
T1
To Other
Modbus-RTU
Devices
+
–
38
39
–
14 T2
15 T3
Shielded Twisted-pair Cable
2
Jumper*
Isolation
Sensor
Excitation
SENSOR EXC
31
2
T4
Di 6 / Pi 6
RJ-45 CONNECTOR Modbus/TCP
Digital
Input
Circuit
Computation
INPUT
COM
32
33
Isolation
16
Do 1
17
Isolation
Isolation
Isolation
A1 42
B1 43
C1 44
A2 45
B2 46
C2 47
18
A/D
Converter
Do 2
Pv 1
UNIVERSAL INPUT
19
20
Do 3
21
A/D
Converter
Pv 2
UNIVERSAL INPUT
22
Do 4
23
+
+
+
48
49
50
24
A/D
Converter
Ai 1
Ai 2
Ai 3
Ai 4
Do 5
25
10
Do 6
RUN CONTACT
11
Isolation
Isolation
Isolation
Output
Driver
+
–
51
52
+
–
+
–
+
3
4
5
6
7
Mv 1
Mv 2
Isolation
Output
Driver
Excitation
Supply
+
–
29
30
2-WIRE TRANSMITTER
Output
Driver
PC CONFIGURATOR/
BUILDER SOFTWARE
Ao 1
Ao 2
Jack
Output
Driver
+
–
8
9
Display /
Setting
12 U(+)
13 V(–)
POWER
*1. Close across the terminals 27 – 28 when the unit is located at the end of a transmission line (= no cross-wiring).
*2. Close across the terminals 14 – 15 when the unit is located at the end of a transmission line (= no cross-wiring).
■ UNIVERSAL INPUT CONNECTION E.G.
■ DISCRETE INPUT PULSE
INPUT CONNECTION E.G.:
+12V
POTENTIOMETER
max.
RTD
A
B
B
3
2
1
+
+
–
+
–
A
A
B
A
B
C
A
B
C
29
30
A
Dry contact
2-Wire
XMTR
T/C
1 or 2kΩ
*3
+
–
+
B
C
+
–
VOLT / CURRENT
INPUT
R
–
–
C
min.
CJC SENSOR
B
*4
*5
R
*3. Connect input resistor module (model: REM4) for current input.
*4. Connect CJC sensor for thermocouple input.
C
*5. Connect input resistor module (model: REM4).
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 8/10
http://www.m-system.co.jp/
MODEL: SC200W
SYSTEM CONFIGURATION EXAMPLES
■ SINGLE LOOP CONTROL
■ CASCADE CONTROL
Multi-Function PID Controller
Model: SC200W
Multi-Function PID Controller
Model: SC200W
Ai
PV
PV
MV
MV
Flow
Level
■ I/O EXPANDED VIA NESTBUS
NestBus
Multi-Function PID Controller
Model: SC200W
Multi-Function PID Controller
Model: SC200
Remote I/O Module
Model: SML
PWR
RUN
PV
PV
MV
MV
■ CONTROL / SUPERVISION VIA MODBUS/TCP
SCADA System
Modbus/TCP
Ethernet Communication Adaptor
Model: GR8-EM
Multi-Function PID Controller
Model: SC200W
PV
MV
Modbus-RTU
Multi-Function PID Controller
Model: SC200W
Multi-Function PID Controller
Model: SC200
PV
PV
MV
MV
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 9/10
http://www.m-system.co.jp/
MODEL: SC200W
■ CONTROL / SUPERVISION VIA MODBUS-RTU
SCADA System
RS-485/RS-232-C
Converter
Model: R2K-1
Modbus-RTU
Multi-Function PID Controller
Model: SC200W
Multi-Function PID Controller
Model: SC200
PV
PV
MV
MV
Specifications are subject to change without notice.
SC200W SPECIFICATIONS
ES-6346 Rev.0 Page 10/10
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明