SC210-22-M2/1 [MSYSTEM]
Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER;型号: | SC210-22-M2/1 |
厂家: | M-SYSTEM |
描述: | Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER |
文件: | 总14页 (文件大小:579K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: SC210
Single Loop Controller Series
[4] OPTIONS (multiple selections)
Housing Depth (must be specified)
/300: 300 mm (Discontinued, select /3)
/400: 400 mm (Discontinued, select /4)
/3: 300 mm
MULTI-FUNCTION PID CONTROLLER
(color LCD with touch-panel, MV output backup,
Modbus/NestBus communication)
/4: 400 mm
Backup Module Power Supply
blank: Single supply
/M2: 100 – 240 V AC (dual supply)
(Operational voltage range 85 – 264 V AC; 50/60 Hz)
/R: 24 V DC (dual supply)
144
(5.67)
(Operational voltage range 24 V DC ±10 %;
ripple 10 %p-p max.)
Control/Backup modules are powered from common terminals
with 'single' supply type; powered from independent
terminals with 'dual' supply type.
Language
*
mm (inch)
*Selectable with option code
blank: Japanese
/E: English
(Language (Japanese or English) can be chosen by front
panel setting.)
Configurator Interface
blank: Infrared
/1: Stereo jack
(If external noise interference is a concern, stereo jack
type is recommended.)
MODEL: SC210-[1][2]-[3][4]
Terminal block
ORDERING INFORMATION
• Code number: SC210-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. SC210-11-M2/3/M2/E/1/T/Q)
blank: One block terminal
/T: Separable terminal
Other Options
blank: none
• Specify the specification for option code /Q
(e.g. /C01/S01)
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
[1] DISCRETE OUTPUT
1: Relay contact
2: Photo MOSFET relay
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
[2] MODBUS
1: Modbus-RTU
2: Modbus/TCP
FUNCTIONS & FEATURES
Functions & Features
[3] POWER INPUT
• Color LCD with touch panel
AC Power
• Five Operation views (digital display, bargraph, dual-loop
bargraph, short trend and user's parameter table views)
• Enhanced screen functions for engineering (configuration,
programming and tuning views)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Universal input x 2 points, analog input x 4 points,
discrete input x 6 points, pulse input x 5 points, high speed
pulse input x 1 point
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 1/14
http://www.m-system.co.jp/
MODEL: SC210
• Current output (4-20 mA) x 2 points, voltage output (1-5
V) x 2 points, relay or photo-MOSFET relay output x 5 points
• RUN contact output (relay) x 1 point
GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Degree of protection: IP55; ensured for the front panel of
the unit independently mounted to a panel
Connection
• I/O signals can be added with remote I/O modules
connected via NestBus peer-to-peer communication
• Computation cycle selectable between 50 msec. and 3
sec. (control cycle selectable between 1 and 64 times of the
computation cycle)
Terminal screws: M3.5 screw terminals (torque 1.0 N·m)
Terminal fixing screws: M4 screw terminals
(torque 1.2 N·m)
• Two PID function blocks
Backup module power supply terminal (option /M2, /R):
Euro terminal block (applicable wire size: dia. 2.4 max.,
• Advanced computation and sequence control functions
• Auto-tuning function
0.5 – 2.5 mm , stripped length 10 mm)
2
• Parameter input and changing with touch panel
• Function parameter setting, list printing and data
downloading/uploading available with Loop Configuration
Builder Software (model: SFEW3E)
Ethernet: RJ-45 Modular Jack
Screw terminal
Terminal screws: Nickel-plated steel (standard) or stainless
steel
• Short trend export (CSV), display parameter setting,
saving and transfer with PC Configurator Software (model:
SCCFG)
Terminal fixing screws: Chrome-plated steel
Housing material: Flame-resistant resin (gray), steel
Isolation: Pv1 to Pv2 to supply output to Ai1 or Ai2 or Ai3 or
Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or
Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Mv2B to Ao1 or Ao2
to Do1 to Do2 to Do3 to Do4 to Do5 to Do6 to NestBus to
Modbus-RTU to Modbus/TCP to power to backup module
power to FG
• Control and supervision by SCADA software via Modbus
TCP/IP or RTU communication
• Backup module (applicable to Mv2 only) is incorporated
for manual loading: MV output is automatically switched to
manual control in case of control module abnormality
• Independent power supply usable for the manual loader
• Control module can be extracted at the front for
replacement while MV output is maintained
• Selectable housing depth for ease of using existing wires
in replacement: 300 mm and 400 mm
PID control: Single loop, cascade, advanced
Proportional band (P): 1 to 1000 %
Integral time (I): 0.01 to 100 minutes
Derivative time (D): 0.01 to 10 minutes
Auto-tuning: Limit cycle method
• Separable terminal block
Alarm: PV high & low, deviation, rate of change
Computation: 48 functions blocks available for arithmetic
operations, time functions, signal selection, limit, alarm and
other functions
Typical Applications
• Replacement of conventional controllers
• Panel operation for small-scale instrumentation
Sequence operation: Logic sequence and step sequence
(max. 1068 commands)
Computation cycle: 50 msec. to 3 sec. (control cycle
selectable among 1, 2, 4, 8, 16, 32 and 64 times of the
computation cycle)
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• Loop configuration builder software (model: SFEW3E Ver.
1.40 or later)
MV output range: -15 - +115 %
Parameter setting: With touch panel or PC (Loop
Configuration Builder Software model: SFEW3E)
Self diagnostics: CPU monitoring with a watchdog timer
RUN contact: OFF in error detected by diagnostic (including
NestBus)
• Infrared communication adaptor (model: COP-IRDA)
• PC configurator software (model: SCCFG Ver.1.50 or later)
Builder software and configurator software are
downloadable at M-System’s web site.
Infrared communication: Transmission distance max. 0.2
meter (for use with the COP-IRDA)
ACCESSORIES
• Precision resistor module (model: REM4): 2
Short trend
• Cold junction sensor: 2
Storing interval: 1, 2, 5, 10, 20, 30 sec.,
1, 2, 5, 10, 30, 60 min.
• Mounting brackets: 2
• Connector adapter: 1
Capacity: 400 points (display 200 points)
(included in Stereo jack type. The jack on the unit and the
plug of PC Configurator cable (not included in the product)
are different in size.)
■ Display
Display device: 4.3-inch TFT LCD
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 2/14
http://www.m-system.co.jp/
MODEL: SC210
Display colors: 256
■ Modbus-RTU
Resolution: 480 × 272 pixels
Configuration: Half-duplex, asynchronous, no procedure
Standard: Conforms to TIA/EIA-485-A
Max. transmission distance: 500 meters
Transfer rate: 4800, 9600, 19.2 k, 38.4 k bps
Data bit: 8
Pixel pitch: 0.198 × 0.198 mm (128 × 128 DPI)
Backlight: LED
Backlight life: Approx. 50 000 hours (at 50 % brightness)
Note: The backlight can be replaced in M-System factory.
The LCD must be replaced at the same time.
Screen saver standby time: 1 to 99 minutes
Scaling range: -32000 to +32000
Parity bit: Odd, even, none
Max. node number: 15 (except the master)
Transmission media:
Decimal point position: 10-1, 10-2, 10-3, 10-4, 10-5 or none
Scale divisions: 2 to 10
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
Terminating resistor: incorporated
Node address setting: 1 - 247
■ Modbus/TCP (Ethernet)
Engineering unit indication: Max. 8 characters
Auto/Man indicator: Green/Amber LED
Backup mode MV output setting indicator: Blue LED
MV output setting indicator: Blue LED
Physical layer standard: IEEE 802.3u
Data link layer: 10BASE-T / 100BASE-TX
Transfer rate: 10 / 100 Mbps, Auto Negotiation
Protocol: Modbus/TCP
FACTORY DEFAULT
Data: RTU (binary)
■ LOOP 1
Connections: 2
P : 100%
Transmission media:
I : No integral action
D : No derivative action
CAS
10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length: 100 meters
Port number: 502
H
L
PID
G02
SEQ
G81
Reverse Action
Ai 1
Pv 1
Mv 1
(PV /MV
)
IP address: 192.168.0.1 (factory setting)
1
1
*
*
1 – 5 V DC
1 – 5 V DC
4 – 20 mA DC
AL1
AL2
SUPPLY OUTPUT
Output voltage:
■ LOOP 2
24 V DC ±10 % with no load
18 V DC min. at 20 mA
Current rating: ≤ 22 mA DC
∙Shortcircuit protection
Current limited: Approx. 30 mA
P : 100%
: No integral action
D : No derivative action
I
CAS
H
L
PID
G03
SEQ
G81
Reverse Action
Ai 2
Pv 2
Mv 2
(PV /MV
)
1
1
*
*
1 – 5 V DC
1 – 5 V DC
4 – 20 mA DC
INPUT SPECIFICATIONS
■ Pv1, Pv2 (universal input)
∙Current input: 4 – 20 mA DC with input resistance 250 Ω
(REM4)
AL3
AL4
*1. Factory default setting
Use Loop Configuration Builder Software (model: SFEW3E)
to modify setting.
∙Voltage input: -10 – +10 V DC
-1 – +1 V DC
0 – 10 V DC
EXTERNAL INTERFACE
■ NestBus
1 – 5 V DC
0 – 1 V DC
Configuration: Bus type multi-drop
Standard: Conforms to TIA/EIA-485-A
Transfer rate: 19.2 kbps
Input resistance: ≥ 1 MΩ
∙Thermocouple input: K, E, J, T, B, R, S, C, N, U, L, P, PR (See
Table 1)
Protocol: NestBus (M-System’s own protocol)
Max. transmission distance: 1 kilometer
Transmission media:
Input resistance: ≥ 30 kΩ
Burnout sensing: ≤ 0.3 µA
Burnout indication: 115 % of the measuring range (upscale)
∙RTD input: Pt100 (JIS ’97, IEC), Pt100 (JIS ’89), JPt100 (JIS
’89), Pt50Ω (JIS ’81), Ni100 (See Table 2)
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
Terminating resistor: incorporated
Address setting: 0 - F (16 nodes)
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 3/14
http://www.m-system.co.jp/
MODEL: SC210
Maximum lead wire resistance: 100 Ω per wire
Burnout indication: 115 % of the measuring range (upscale)
Sensing current: ≤ 1 mA
[Table 1 (Thermocouple input)]
USABLE
RANGE (°C)
CONFORMANCE
RANGE (°C)
T/C
K (CA)
∙Potentiometer input: Total resistance 100 Ω to 10 kΩ
Minimum span: 50 % of total resistance
Excitation: ≤ 0.6 V DC
-272 to +1472
-272 to +1100
-260 to +1300
-272 to +500
24 to 1920
-150 to +1370
-170 to +1000
-180 to +1200
-170 to +400
1000 to 1760
380 to 1760
400 to 1760
100 to 2315
-130 to +1300
-200 to +600
-200 to +900
0 to 1395
E (CRC)
J (IC)
■ Ai1, Ai2, Ai3, Ai4
T (CC)
B (RH)
∙Voltage input: 1 – 5 V DC
R
-100 to +1860
-100 to +1860
-52 to +2416
-272 to +1400
-252 to +700
-252 to +1000
-52 to +1496
-52 to +1860
Input resistance: ≥ 1 MΩ
S
■ Pi1, Pi2, Pi3, Pi4, Pi5: Dry contact
(Di1 through Di5 are assigned to the same terminals
respectively.)
C (WRe 5-26)
N
U
Maximum frequency: 20 Hz
L
Minimum pulse width: 25 msec.
Common: Negative common per 5 points
Sensing: Approx. 12 V DC, 6 mA
ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ
■ Pi6: Dry contact
P (Platinel II)
(PR)
300 to 1760
Overrange input (out of the usable range) is handled as burnout.
[Table 2 (RTD input)]
USABLE
RANGE (°C)
CONFORMANCE
RANGE (°C)
RTD
(Di6 is assigned to the same terminal.)
Maximum frequency: 10 kHz
Pt 100 (JIS ’97, IEC
Pt 100 (JIS ’89)
JPt 100 (JIS ’89)
Pt 50Ω (JIS ’81)
Ni 100
)
-240 to +900
-240 to +900
-236 to +560
-236 to +700
-100 to +252
-200 to +850
-200 to +660
-200 to +510
-200 to +649
-80 to +250
Minimum pulse width: 0.05 msec.
Common: Negative common
Sensing: Approx. 12 V DC, 12 mA
ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ
Excitation: 12 V DC ±10%, 15 mA
Current limiting circuit: Approx. 30 mA
■ Di1, Di2, Di3, Di4, Di5: Dry contact
(Pi1 through Pi5 are assigned to the same terminals
respectively.)
Overrange input (out of the usable range) is handled as burnout.
OUTPUT SPECIFICATIONS
■ Mv1, Mv2, Mv2B
∙Current output: 4 – 20 mA DC
Load resistance: ≤ 600 Ω
Common: Negative common per 5 points
Sensing: Approx. 12 V DC, 6 mA
ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ
■ Di6: Dry contact
(Mv2B is the output from backup unit.)
■ Ao1, Ao2
∙Voltage output: 1 – 5 V DC
Load resistance: ≥ 10 kΩ
■ Discrete Output
(Pi6 is assigned to the same terminal.)
Common: Negative common
∙Do1, Do2, Do3, Do4, Do5, RUN contact (Do6): Relay
contact
Sensing: Approx. 12 V DC, 12 mA
ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ
Rated load: 250 V AC @1 A (cos ø = 1)
30 V DC @1 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 60 W
Minimum load: 5 V DC @10 mA
Mechanical life: 2 × 10 cycles
7
∙Do1, Do2, Do3, Do4, Do5: Photo MOSFET relay
Rating: 200 V AC/DC @0.5 A (resistive load)
ON resistance: 2.1 Ω
Maximum frequency: 4 Hz @24 V, 10 mA
ON delay time: ≤ 5.0 msec.
OFF delay time: ≤ 3.0 msec.
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 4/14
http://www.m-system.co.jp/
MODEL: SC210
Modbus-RTU to Modbus/TCP to power to backup module
power to FG)
INSTALLATION
Power input
500 V AC @ 1 minute (Pv2 to Ai1 or Ai2 or Ai3 or Ai4)
500 V AC @ 1 minute (Mv2 or Mv2B to Ao1 or Ao2)
500 V AC @ 1 minute (Do2 to Do3 to Do4 to Do5 to Do6)
500 V AC @ 1 minute (Pv1 to supply output)
∙AC:
Control module
≤ 25 VA at 100 V AC
≤ 40 VA at 240 V AC
Backup module
≤ 10 VA at 100 V AC
STANDARDS & APPROVALS
EU conformity:
≤ 15 VA at 240 V AC
•DC
EMC Directive
Control module: ≤ 650 mA
Backup module: ≤ 150 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 90 %RH (non-condensing)
Mounting: Panel flush mounting (high-density mounting in
horizontal direction)
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (contact output)
Installation Category II (power)
Pollution degree 2
Weight:
Approx. 2.0 kg (4.41 lb) for 300 mm depth type
Approx. 2.5 kg (5.51 lb) for 400 mm depth type
Input or output to contact output – Basic insulation (300
V)
Input or output to power - Reinforced insulation (300 V)
RoHS Directive
PERFORMANCE
Accuracy
EN 50581
Protection against access to the terminal blocks:
Finger protection (VDE 0660-514)
DC input: ±0.1 % ±1 digit
Thermocouple input: ±1℃ ±1 digit
±2℃ ±1 digit for B, R, S, C and PR
RTD input: ±1℃ ±1 digit
Potentiometer input: ±0.2 % ±1 digit
DC output: ±0.1 %
Precision resistor module (REM4): ±0.1 %
Cold junction compensation:
±2°C at 25°C ±10°C
±4°C for S, R and PR
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
DC input: ±0.015 %/°C (±0.008 %/°F)
Thermocouple input: ±0.015 %/°C (±0.008 %/°F)
RTD input: ±0.015 %/°C (±0.008 %/°F)
Potentiometer input: ±0.015 %/°C (±0.008 %/°F)
DC output: ±0.015 %/°C (±0.008 %/°F)
Precision resistor module (REM4): ±0.015 %/°C (±0.008
%/°F)
Line voltage effect: ±0.1 % over voltage range
Calendar clock accuracy: Monthly deviation 3 minutes at
25°C
RAM memory duration in power failure for hot start:
10 minutes assured
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to
Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or
Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Mv2B or Ao1 or Ao2 to
Do1 to Do2 or Do3 or Do4 or Do5 or Do6 to NestBus to
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 5/14
http://www.m-system.co.jp/
MODEL: SC210
EXTERNAL VIEW
■ CONTROL MODULE FRONT VIEW
• Infrared communication type
• Stereo jack type
1
1
2
2
8
Auto/Man
Auto/Man
3
4
6
7
5
7
4
5
6
1. TFT Color LCD with touch panel
Provides operation and engineering views to facilitate monitoring and setting
2. MV output setting indicator LEDs for the backup mode
3. Infrared communication port
Used to communicate with PC via IRDA Communication Adaptor (model: COP-IRDA) to program and change parameters
using Loop Configuration Builder Software (model: SFEW3E) or PC Configurator Software (model: SCCFG)
4. MV value (DOWN) button
5. Acceleration button
(Accelerates MV signal’s changing speed by pressing simultaneously with MV value button)
6. MV value (UP) button
7. Auto / Man selector (changes the control mode for MV output)
8. Configurator jack and cap
Connects with a PC where Loop Configuration Builder Software (model: SFEW3E) or PC configurator software (model: SCCFG)
is installed via a PC configurator cable (model: COP-US) and enables programming and parameter setting
■ BACKUP MODULE
9
10
11
12
13
9. MV output setting indicators
10. Configurator jack
11. MV value (UP) button
12. Acceleration button
(Accelerates MV signal’s changing speed by pressing simultaneously with MV value button)
13. MV value (DOWN) button
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 6/14
http://www.m-system.co.jp/
MODEL: SC210
COMMUNICATION CABLE CONNECTIONS
■ NestBus
SML
T1
SML
T1
SC210
T1
T2
T2
T2
*1
*1
T3
T3
T3
T4
T4
T4
*2
FG
■ Modbus-RTU
R2K-1
RS-485
RS-485
SC210
T1
SC210
T1
T1
T2
T3
T4
RS-232-C
T2
T2
*1
*1
T3
T3
T4
T4
*2
FG
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shield cables to all sections and ground them at single point.
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 7/14
http://www.m-system.co.jp/
MODEL: SC210
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ INFRARED COMMUNICATION TYPE
1
*
BACKUP MODULE POWER INPUT TERMINAL
175 (6.89)
210 (8.27) max.
• ONE BLOCK TERMINAL
(without option /T)
2
MOUNTING BRACKETS
TERMINAL COVER
RJ-45 CONNECTOR
52–M3.5 SCREW
*
80 (3.15)
60 61 62 63
14
40
41
42
43
44
45
46
47
48
49
50
51
52
1
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
72 (2.83)
24
*3
67.5 (2.66)
(.94)
• SEPARABLE TERMINAL
(with option /T)
*1. Option /M2, /R only
*2. For Modbus/TCP only
*3. Option /3: 300 mm (11.81”)
Option /4: 400 mm (15.75”)
2
RJ-45 CONNECTOR
52–M3.5 SCREW
*
4–M4 SCREW FOR
FIXING TERMINAL
14
1
40
41
42
43
44
45
46
47
48
49
50
51
52
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
67.5 (2.66)
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 8/14
http://www.m-system.co.jp/
MODEL: SC210
■ STEREO JACK TYPE
1
*
BACKUP MODULE POWER INPUT TERMINAL
175 (6.89)
210 (8.27) max.
• ONE BLOCK TERMINAL
(without option /T)
2
MOUNTING BRACKETS
TERMINAL COVER
RJ-45 CONNECTOR
52–M3.5 SCREW
*
80 (3.15)
60 61 62 63
14
40
41
42
43
44
45
46
47
48
49
50
51
52
1
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
Jack cap
11
25
12
26
13
72 (2.83)
24
*3
1 (.04)
67.5 (2.66)
(.94)
• SEPARABLE TERMINAL
(with option /T)
*1. Option /M2, /R only
*2. For Modbus/TCP only
*3. Option /3: 300 mm (11.81”)
Option /4: 400 mm (15.75”)
2
RJ-45 CONNECTOR
52–M3.5 SCREW
*
4–M4 SCREW FOR
FIXING TERMINAL
14
1
40
41
42
43
44
45
46
47
48
49
50
51
52
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
67.5 (2.66)
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 9/14
http://www.m-system.co.jp/
MODEL: SC210
MOUNTING REQUIREMENTS unit: mm
■ PANEL CUTOUT unit: mm
• Single mounting
• Clustered mounting
[68+72×(n - 1)] +1
68 +0.7
0
0
n = number of units
Panel thickness 2.3 – 20
■ Caution
• IP55 is ensured for the front panel of the unit mounted independently to according to a panel. Test the sealing at the
mounting surface once the device is installed.
• Set the unit on a vertical surface with its operation buttons at the lower side. Mounting in other directions may cause heat
built up inside the unit and shorten its life span or degrade its performance.
• Ensure that there is sufficient space for ventilation inside a panel. Do not install above the devices that generate high heat
such as heaters, transformers or resistors. Leave at least 30 mm (1.2 inch) space above, below and behind the unit for
maintenance purpose (e.g. wiring, removing or installing).
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 10/14
http://www.m-system.co.jp/
MODEL: SC210
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
■ BACKUP MODULE POWER SUPPLY: SINGLE SUPPLY
Backup Module
Control Module
Isolation
Isolation
Shielded Twisted-pair Cable
+
40 T1
27 T2
28 T3
41 T4
To Other
NestBus
Devices
+
+
+
+
34
35
36
37
Discrete
Input
Circuit
Di 1 / Pi 1
Di 2 / Pi 2
Di 3 / Pi 3
Di 4 / Pi 4
Di 5 / Pi 5
–
1
Jumper*
SHLD
Shielded Twisted-pair Cable
Isolation
+
T1
1
To Other
Modbus-RTU
Devices
–
14 T2
15 T3
+
–
38
39
2
Jumper*
SHLD
2
T4
Isolation
Isolation
Sensor
Excitation
SENSOR EXC
RJ-45 CONNECTOR
Modbus/TCP
31
Di 6 / Pi 6
16
Digital
Do 1
Input
Circuit
Computation
INPUT
COM
32
33
17
18
19
20
21
22
23
24
25
10
11
3
Isolation
Isolation
Isolation
Do 2
A1 42
B1 43
C1 44
A2 45
B2 46
C2 47
A/D
Converter
Pv 1
UNIVERSAL INPUT
Do 3
Do 4
Do 5
A/D
Converter
Pv 2
UNIVERSAL INPUT
+
+
+
48
49
50
A/D
Converter
Ai 1
Ai 2
Ai 3
Ai 4
Do 6
RUN CONTACT
Isolation
Isolation
Isolation
Output
Driver
+
–
+
–
+
Mv 1
+
–
51
52
4
Output
Driver
5
3
*
Isolation
Mv 2, Mv 2B
6
Excitation
Supply
+
–
29
30
Output
Driver
2-WIRE TRANSMITTER
7
Ao 1
Ao 2
PC CONFIGURATOR/
BUILDER SOFTWARE
Output
Driver
Infrared Port / Jack
+
–
8
9
Display /
Setting
12 U(+)
13 V(–)
26 FG
POWER
MV SETTING
INDICATORS
Isolation
Digital
Computation
Output
Driver
Output
Switch
OPERATION BUTTONS
Backup Module
Power Circuit
*1. Close across the terminals 27 – 28 when the unit is located at the end of a transmission line (= no cross-wiring).
*2. Close across the terminals 14 – 15 when the unit is located at the end of a transmission line (= no cross-wiring).
*3. Backup is applicable to Mv 2 only. Mv 2B is output of the backup module.
■ DISCRETE INPUT PULSE
■ UNIVERSAL INPUT CONNECTION E.G.
INPUT CONNECTION E.G.:
POTENTIOMETER
max.
RTD
+12V
A
B
B
3
2
1
+
+
–
+
–
A
A
B
A
B
C
A
B
C
29
30
A
Dry contact
2-Wire
XMTR
1 or 2kΩ
T/C
*4
+
–
+
–
+
B
C
VOLT / CURRENT
INPUT
R
–
–
C
min.
CJC SENSOR
B
*5
*6
R
*4. Connect input resistor module (model: REM4) for current input.
*5. Connect CJC sensor for thermocouple input.
C
*6. Connect input resistor module (model: REM4).
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 11/14
http://www.m-system.co.jp/
MODEL: SC210
■ BACKUP MODULE POWER SUPPLY: DUAL SUPPLY
Backup Module
Control Module
Isolation
Isolation
Shielded Twisted-pair Cable
+
40 T1
27 T2
28 T3
41 T4
To Other
NestBus
Devices
+
+
+
+
34
35
36
37
Discrete
Input
Circuit
Di 1 / Pi 1
Di 2 / Pi 2
Di 3 / Pi 3
Di 4 / Pi 4
Di 5 / Pi 5
–
1
Jumper*
SHLD
Shielded Twisted-pair Cable
Isolation
+
T1
1
To Other
Modbus-RTU
Devices
–
14 T2
15 T3
+
–
38
39
2
Jumper*
SHLD
2
T4
Isolation
Sensor
Excitation
SENSOR EXC
RJ-45 CONNECTOR
Modbus/TCP
31
Di 6 / Pi 6
Isolation
16
Digital
Do 1
Input
Circuit
Computation
INPUT
COM
32
33
17
18
19
20
21
22
23
24
25
10
11
3
Isolation
Isolation
Isolation
Do 2
A1 42
B1 43
C1 44
A2 45
B2 46
C2 47
A/D
Converter
Pv 1
UNIVERSAL INPUT
Do 3
Do 4
Do 5
A/D
Converter
Pv 2
UNIVERSAL INPUT
+
+
+
48
49
50
A/D
Converter
Ai 1
Ai 2
Ai 3
Ai 4
Do 6
RUN CONTACT
Isolation
Isolation
Isolation
Output
Driver
+
–
+
–
+
Mv 1
+
–
51
52
4
Output
Driver
5
3
*
Mv 2, Mv 2B
Isolation
6
Excitation
Supply
+
–
29
30
Output
Driver
7
2-WIRE TRANSMITTER
Ao 1
Ao 2
Output
Driver
PC CONFIGURATOR/
BUILDER SOFTWARE
Infrared Port / Jack
+
–
8
9
Display /
Setting
12 U(+)
13 V(–)
26 FG
POWER
MV SETTING
INDICATORS
Isolation
62
Digital
Computation
Output
Driver
Output
Switch
63 FG
60 U(+)
61 V(–)
OPERATION BUTTONS
Backup Module
Power Circuit
BACK UP POWER
*1. Close across the terminals 27 – 28 when the unit is located at the end of a transmission line (= no cross-wiring).
*2. Close across the terminals 14 – 15 when the unit is located at the end of a transmission line (= no cross-wiring).
*3. Backup is applicable to Mv 2 only. Mv 2B is output of the backup module.
■ DISCRETE INPUT PULSE
INPUT CONNECTION E.G.:
+12V
■ UNIVERSAL INPUT CONNECTION E.G.
POTENTIOMETER
max.
RTD
A
B
B
3
2
1
+
+
–
+
–
A
A
B
A
B
C
A
B
C
29
30
A
Dry contact
2-Wire
XMTR
1 or 2kΩ
T/C
*4
+
–
+
–
+
B
C
VOLT / CURRENT
INPUT
R
–
–
C
min.
CJC SENSOR
B
*5
*6
R
*4. Connect input resistor module (model: REM4) for current input.
*5. Connect CJC sensor for thermocouple input.
C
*6. Connect input resistor module (model: REM4).
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 12/14
http://www.m-system.co.jp/
MODEL: SC210
SYSTEM CONFIGURATION EXAMPLES
■ SINGLE LOOP CONTROL
■ CASCADE CONTROL
Multi-Function PID Controller
Model: SC210
Multi-Function PID Controller
Model: SC210
Ai
PV
PV
MV
MV
Flow
Level
■ I/O EXPANDED VIA NESTBUS
NestBus
Multi-Function PID Controller
Model: SC210
Multi-Function PID Controller
Model: SC210
Remote I/O Module
Model: SML
PWR
RUN
PV
PV
MV
MV
■ CONTROL / SUPERVISION VIA MODBUS/TCP
SCADA System
Modbus/TCP
Ethernet Communication Adaptor
Model: 72EM2-M4
Multi-Function PID Controller
Model: SC210
PV
ETHERNET
RS-485
RUN
SEND
FIELD
CNFG
MV
Modbus-RTU
Multi-Function PID Controller
Model: SC210
Multi-Function PID Controller
Model: SC210
PV
PV
MV
MV
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 13/14
http://www.m-system.co.jp/
MODEL: SC210
■ CONTROL / SUPERVISION VIA MODUBS-RTU
SCADA System
RS-485/RS-232-C
Converter
Model: R2K-1
Modbus-RTU
Multi-Function PID Controller
Model: SC210
Multi-Function PID Controller
Model: SC210
PV
PV
MV
MV
Specifications are subject to change without notice.
SC210 SPECIFICATIONS
ES-6340 Rev.18 Page 14/14
http://www.m-system.co.jp/