MODEL: SVA  
Z: Specify current (See INPUT SPECIFICATIONS)  
Plug-in Signal Conditioners M-UNIT  
Voltage  
1: 0 – 10 mV DC (Input resistance 10 kΩ min.)  
15: 0 – 50 mV DC (Input resistance 10 kΩ min.)  
16: 0 – 60 mV DC (Input resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Input resistance 100 kΩ min.)  
3: 0 – 1 V DC (Input resistance 1 MΩ min.)  
4: 0 – 10 V DC (Input resistance 1 MΩ min.)  
5: 0 – 5 V DC (Input resistance 1 MΩ min.)  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)  
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)  
0: Specify voltage (See INPUT SPECIFICATIONS)  
SIGNAL TRANSMITTER  
(isolated; max. 200 mA output)  
Functions & Features  
• Converting a DC process input into a high-power current  
or voltage up to 200 mA  
• Isolation up to 2000 V AC  
• High-density mounting  
Typical Applications  
• Retrofitting 10 – 50 mA DC control system  
• DC excitation for an electromagnetic coil which demands  
a high power  
[2] OUTPUT  
Current  
50  
(1.97)  
H: 10 – 50mA DC (Load resistance 400 Ω max.)  
L: 0 – 50 mA DC (Load resistance 400 Ω max.)  
M: 0 – 100 mA DC (Load resistance 200 Ω max.)  
N: 0 – 200 mA DC (Load resistance 50 Ω max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
80  
(3.15)  
127  
(5)  
4: 0 – 10 V DC (Load resistance 50 Ω min.)  
5: 0 – 5 V DC (Load resistance 25 Ω min.)  
6: 1 – 5 V DC (Load resistance 25 Ω min.)  
8: 0 – 20 V DC (Load resistance 200 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
mm (inch)  
MODEL: SVA–[1][2]–[3][4]  
ORDERING INFORMATION  
• Code number: SVA-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. SVA-AN-K3/Q)  
[3] POWER INPUT  
AC Power  
K3: 100 – 120 V AC  
(Operational voltage range 90 – 132 V, 47 – 66 Hz)  
L3: 200 – 240 V AC  
• Special input and output ranges (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
(Operational voltage range 180 – 264 V, 47 – 66 Hz)  
DC Power  
P: 110 V DC  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
[1] INPUT  
Current  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
A1: 4 – 20 mA DC (Input resistance 50 Ω)  
B: 2 – 10 mA DC (Input resistance 500 Ω)  
C: 1 – 5 mA DC (Input resistance 1000 Ω)  
D: 0 – 20 mA DC (Input resistance 50 Ω)  
E: 0 – 16 mA DC (Input resistance 62.5 Ω)  
F: 0 – 10 mA DC (Input resistance 100 Ω)  
G: 0 – 1 mA DC (Input resistance 1000 Ω)  
H: 10 – 50 mA DC (Input resistance 100 Ω)  
J: 0 – 10 μA DC (Input resistance 1000 Ω)  
K: 0 – 100 μA DC (Input resistance 1000 Ω)  
GW: -1 – +1 mA DC (Input resistance 1000 Ω)  
FW: -10 – +10 mA DC (Input resistance 100 Ω)  
[4] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
SVA SPECIFICATIONS  
ES-1309 Rev.6 Page 1/3  
http://www.m-system.co.jp/  
MODEL: SVA  
Weight: 300 g (0.66 lb)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
PERFORMANCE in percentage of span  
Accuracy: ±0.2 %  
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
Load effect  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Overrange output: 0 mA or 0 V up to 105 % of upper range  
value  
Current output: ±0.2 % over load range  
Voltage output: +0.2 % or -{0.2 + (0.3 [Ω] × max. load  
[A]) / output span [V] × 100} % over load range  
Line voltage effect: ±0.2 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
Zero adjustment: -25 – +25 % no output below 0 mA or 0 V  
(front)  
Span adjustment: 50 to 100 % for the rated input span  
(front)  
INPUT SPECIFICATIONS  
DC Current:  
STANDARDS & APPROVALS  
EU conformity:  
Shunt resistor attached to the input terminals (0.5 W)  
Specify input resistance value for code Z.  
DC Voltage: -30 – +30 V DC  
Span: Min. 3 mV, max. 30 V  
Offset: Max. 1.5 times span  
Input resistance  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Span 3 – 10 mV : ≥ 10 kΩ  
Measurement Category II  
Pollution Degree 2  
Span 10 – 100 mV : ≥ 10 kΩ  
Span 0.1 – 1 V : ≥ 100 kΩ  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
RoHS Directive  
Span ≥ 1 V : ≥ 1 MΩ  
EN 50581  
OUTPUT SPECIFICATIONS  
DC Current: 0 – 200 mA DC  
Minimum span: 20 mA  
Zero suppression: max. 30 % of span  
Load inductance: 1 H max.  
Load resistance  
Max. current ≤ 100 mA: Output drive max. 20 V  
100 mA < max. current ≤ 200 mA: R  
current [A])  
L
[Ω] = 2 [W] / (max.  
2
DC Voltage: 0 – 20 V DC  
Minimum span: 2 V  
Zero suppression: Max. 30 % of span  
Load resistance  
Max. voltage ≤ 10 V: R  
10 V < max. voltage ≤ 20V: R  
[W]  
L
[Ω] = max. voltage [V] / 0.2 [A]  
L
[Ω] = (max. voltage [V]) / 2  
2
INSTALLATION  
Power consumption  
AC: Approx. 10 VA, 5 W max.  
DC: ≤ 5 W  
Operating temperature: -5 to + 50°C (23 to 122°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
SVA SPECIFICATIONS  
ES-1309 Rev.6 Page 2/3  
http://www.m-system.co.jp/  
MODEL: SVA  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
6
5
4
3
2–4.5 (.18) dia.  
MTG HOLE  
15 (.59) deep  
7
8
1
2
8–M3.5  
SCREW  
50 (1.97)  
107 (4.21)  
127 (5)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
INPUT RESISTOR  
(model: REM)  
6
5
4
3
7
8
1
2
Input shunt resistor attached  
for current input.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
Isolation  
Low Drift  
Amplifier  
Output  
Driver  
+
+
3
4
5
6
1
2
7
8
*
INPUT  
R
OUTPUT  
POWER  
U(+)  
V(–)  
Base Socket  
*Input shunt resistor attached for current input.  
Specifications are subject to change without notice.  
SVA SPECIFICATIONS  
ES-1309 Rev.6 Page 3/3  
http://www.m-system.co.jp/  

SVB-JH-L3/Q 相关器件

型号 制造商 描述 价格 文档
SVB-JH-P MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JH-P/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JL-K3 MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JL-K3/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JL-L3 MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JL-L3/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JL-P MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JL-P/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JM-K3 MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
SVB-JM-K3/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格

SVB-JH-L3/Q 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8