TCS-NZ-V/E [MSYSTEM]

Plug-in Signal Conditioners M-UNIT;
TCS-NZ-V/E
型号: TCS-NZ-V/E
厂家: M-SYSTEM    M-SYSTEM
描述:

Plug-in Signal Conditioners M-UNIT

文件: 总4页 (文件大小:124K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: TCS  
4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)  
5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)  
6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)  
7: R (Usable range -50 to +1760°C, -58 to +3200°F)  
8: S (Usable range -50 to +1760°C, -58 to +3200°F)  
N: N (Usable range -270 to +1300°C, -454 to +2372°F)  
0: Specify  
Plug-in Signal Conditioners M-UNIT  
THERMOCOUPLE TRANSMITTER  
Functions & Features  
• Accepting direct input from a thermocouple and providing  
a standard process signal  
• 7-segment linearization  
• Burnout protection  
[2] OUTPUT  
Current  
• High-accuracy cold junction compensation  
• Isolation up to 2000 V AC  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
• Fast response type available  
• LCD meter (engineering unit display selectable)  
• Simple loop test output (0 % and 100 %)  
• High-density mounting  
Typical Applications  
• High-accuracy cold junction compensation benefits narrow  
span measurements  
• 0.1 μA burnout sensing enables long distance  
transmission with minimum offset drifts  
• Electric furnace (isolation)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 100 Ω min.)  
4: 0 – 10 V DC (Load resistance 1000 Ω min.)  
5: 0 – 5 V DC (Load resistance 500 Ω min.)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
• No burnout type can connect to a single T/C in parallel  
with a recorder  
• Power plant (2000 V AC isolation, 110 V DC power supply)  
50  
(1.97)  
[3] POWER INPUT  
AC Power  
80  
(3.15)  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
127  
(5)  
F: 120 V AC  
mm (inch)  
G: 200 V AC (Not selectable with Option /UL)  
H: 220 V AC (Not selectable with Option /UL)  
J: 240 V AC (Not selectable with Option /UL)  
DC Power  
MODEL: TCS–[1][2]–[3][4]  
S: 12 V DC (Not selectable with Option /UL)  
R: 24 V DC (Not selectable with Option /UL)  
V: 48 V DC (Not selectable with Option /UL)  
P: 110 V DC (Not selectable with Option /E2 or /UL)  
ORDERING INFORMATION  
• Code number: TCS-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. TCS-2A-B/E2/BL/Q)  
• Temperature range (e.g. 0 – 800°C)  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
[4] OPTIONS (multiple selections)  
Input Signal Indicator  
blank: Without  
/E: With (0.0 - 100.0 % display)  
/E2: With (in engineering unit with backlight and the  
simple loop test output)  
[1] INPUT THERMOCOUPLE  
1: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)  
2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)  
3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)  
Response Time (0 – 90 %)  
blank: Standard (≤ 0.5 sec.)  
/K: Fast response (Approx. 25 msec.)  
TCS SPECIFICATIONS  
ES-1331-E Rev.16 Page 1/4  
http://www.m-system.co.jp/  
MODEL: TCS  
(Not selectable with Option /E2)  
Burnout  
INPUT SPECIFICATIONS  
Minimum span: 3 mV  
blank: Upscale burnout  
Offset: Max. 1.5 times span  
Input resistance: 30 kΩ min.  
Burnout sensing: 0.1 μA  
/BL: Downscale burnout  
/BN: No burnout  
Standards & Approvals  
blank: Without UL  
Minimum span (in °C)  
(PR): min. span 370°C  
K (CA): min. span 75°C  
E (CRC): min. span 50°C  
J (IC): min. span 60°C  
T (CC): min. span 75°C  
B (RH): min. span 780°C  
R: min. span 360°C  
/UL: UL approval (Not selectable with /E or /E2)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
S: min. span 380°C  
N: min. span 110°C  
/C02: Polyurethane coating  
/C03: Rubber coating (UL not available)  
TERMINAL SCREW MATERIAL  
Minimum span (in °F)  
(PR): min. span 670°F  
K (CA): min. span 140°F  
E (CRC): min. span 90°F  
J (IC): min. span 110°F  
T (CC): min. span 140°F  
B (RH): min. span 1410°F  
R: min. span 650°F  
/S01: Stainless steel (UL not available)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
S: min. span 690°F  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
N: min. span 200°F  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
At burnout: Downscale ≤ -10 %, Upscale ≥ 110 %  
Linearization: Standard  
Note: The described accuracy may be partially not satisfied  
when the temperature ranges below 0°C. Consult factory.  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Cold junction compensation: CJC sensor attached to the  
input terminals (B thermocouple is without CJC as standard)  
Simple loop test output: 0 % and 100 % signal simulated by  
selecting the front switch positions. (Only for option code  
/E2)  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
■ DISPLAY (Input indicator)  
Offset: Max. 1.5 times span  
• Option code: /E  
Load resistance: Output drive 10 mA max.; 5 mA for  
negative voltage output; at ≥ 0.5 V  
LCD digital display: 0.0 - 100.0 % (min. digit 0.1 %)  
(No scaling)  
• Option code: /E2  
LCD digital display: Engineering unit  
Display scaling: -10000 – +10000  
INSTALLATION  
Power input  
Decimal position: 10-1 - 10-4 or no decimal point  
Engineering unit: %, μV, mV, V, mA, A, °C, °F, Ω, DEG K,  
mHz, Hz, kHz, VAC, AAC, mg, g, kg, t, rpm or rps selectable  
Back light: Green at normal, red at loop test output enable  
Factory setting: scaling 0.00 - 100.00, unit: %  
AC: Operational voltage range: rating ±10 %, 50/60 ±2 Hz,  
approx. 2 VA  
(approx. 3 VA with Option /E2)  
DC: Operational voltage range: rating ±10 %, or 85 – 150 V  
for 110 V rating (ripple 10 % p-p max.) approx. 2.6 W (110  
mA at 24 V; approx. 3.6 W with Option /E2)  
Operating temperature: -5 to +60°C (23 to 140°F)  
TCS SPECIFICATIONS  
ES-1331-E Rev.16 Page 2/4  
http://www.m-system.co.jp/  
MODEL: TCS  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 350 g (0.77 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.3 % (at over 400°C or 750°F for R, S  
and PR; over 770°C or 1420°F for B)  
Display accuracy: ± (0.3 % of FS + 1 digit) (at over 400°C or  
750°F for R, S and PR; over 770°C or 1420°F for B)  
Simple loop test output setting accuracy: ±0.5 %  
Cold junction compensation error  
(at 20°C ±10°C or 68°F ±18°F)  
K, E, J, T & N: ±0.5°C or ±0.9°F  
S, R & PR: ±1°C or ±1.8°F  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
(at over 400°C or 750°F for R, S and PR; over 770°C or  
1420°F for B)  
Burnout response: ≤ 10 sec.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
STANDARDS & APPROVALS  
Approval:  
UL/C-UL general safety requirements  
(UL 3111-1, CAN/CSA-C22.2 No.1010-1)  
EXTERNAL VIEW  
OPTION /E  
OPTION /E2  
LCD Meter  
Zero Adj.  
Span Adj.  
LCD Meter  
Zero Adj.  
Span Adj.  
NEXT Key  
Loop Test Selector  
ENTER Key  
Top  
: 0% fixed  
Middle : 100% fixed  
Bottom : Cancel  
(normal operating mode)  
TCS SPECIFICATIONS  
ES-1331-E Rev.16 Page 3/4  
http://www.m-system.co.jp/  
MODEL: TCS  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
6
5
4
3
2–4.5 (.18) dia.  
MTG HOLE  
15 (.59) deep  
7
8
1
2
8–M3.5  
SCREW  
50 (1.97)  
107 (4.21)  
127 (5)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
CJC SENSOR  
(model: CJM)  
6
3
5
8
4
1
7
2
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
*
comp. leadwire  
T / C  
Z
S
Isolation  
+
Low Drift  
Amplifier  
Output  
Driver  
+
+
3
Linearizer  
1
2
OUTPUT  
POWER  
***  
metal leg  
LOOP TEST  
SELECTOR  
4
5
6
CJC  
SENSOR  
**  
U(+)  
V(–)  
7
8
CJC Sensing  
Volt. Generator  
model: CJM  
Base Socket  
*
Option /E, E2  
** Deleted with B thermocouple  
***Option /E2  
Specifications are subject to change without notice.  
TCS SPECIFICATIONS  
ES-1331-E Rev.16 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

TCS-NZ-V/K

Plug-in Signal Conditioners M-UNIT
MSYSTEM

TCS-NZ-V/Q

Plug-in Signal Conditioners M-UNIT
MSYSTEM

TCS01FPDQR010

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDQR010N

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDQR100

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDQR100N

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDSR010

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDSR010N

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDSR100

TCS Current Sense Chip Resistors
TOKEN

TCS01FPDSR100N

TCS Current Sense Chip Resistors
TOKEN

TCS01FPFQR010

TCS Current Sense Chip Resistors
TOKEN

TCS01FPFQR010N

TCS Current Sense Chip Resistors
TOKEN