TM-R-H [MSYSTEM]

CONTACT TELEMETERING MODULE;
TM-R-H
型号: TM-R-H
厂家: M-SYSTEM    M-SYSTEM
描述:

CONTACT TELEMETERING MODULE

文件: 总4页 (文件大小:62K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Telemetering System  
MODEL  
CONTACT TELEMETERING MODULE  
TMR/TMT  
MODEL & SUFFIX CODE SELECTION  
50  
(1.97)  
TM❑  
MODEL  
80  
(3.15)  
INPUT  
Dry contact  
OUTPUT  
M
•U  
N
l
IT  
M
o
d
e
TM  
R
OUTPUT  
ON  
OFF  
R : Relay contact  
T : Open collector  
POWER INPUT  
123  
(4.84)  
mm (inch)  
AC Power  
DC Power  
Functions & Features  
B : 100V AC  
C : 110V AC  
D : 115V AC  
F : 120V AC  
G : 200V AC  
H : 220V AC  
J : 240V AC  
S : 12V DC*  
R : 24V DC*  
• Transmitting 1-point contact signal through NTT  
(Nippon Telephone & Telegraph) personal telecom-  
munication line of 50 b/s • Approved of Technical  
Requirements Compliance Approval by Japan Ap-  
proval Institute for Telecommunications Equipment  
• Approval No. M90-N227-0 • Applicable to vari-  
ous cables types • No interference by induction noise  
• Lightning protection applicable • No field adjust-  
ment required • Compact plug-in construction easy  
to install and maintain  
*24V DC (Code R) and 12V DC (Code S) are not ap-  
proved by Japan Approvals Institute for Telecommu-  
nications Equipment.  
Therefore an individual application will be necessary  
for using the TMA on NTT telecom. line.  
ORDERING INFORMATION  
INPUT & OUTPUT  
Specify code number. (e.g. TMR-B)  
INPUT: dry contact  
Sensing: approx. 18V DC @5mA  
ON/OFF level: 3kfor ON; 30kfor OFF  
Maximum leadwire resistance: 3kincluding  
return  
GENERAL SPECIFICATIONS  
Construction: plug-in  
Connection: M3.5 screw terminals  
Housing material: flame-resistant resin (black)  
Isolation: input to output to power  
OUTPUT  
Relay Contact: 100V AC @5A (cosø=1)  
24V DC @5A (resistive load)  
electrical life 10 × 104 cycles (rate 30/min.)  
Maximum switching voltage: 380V AC or 125V DC  
Maximum switching power: 500VA or 120W  
Minimum load: 5V DC @10mA (18V DC @5mA)  
Mechanical life: 5 × 107 cycles  
Maximum frequency: 1 Hz  
Open Collector: 24V DC @100mA  
Maximum frequency: 20 Hz  
Saturation voltage: 1.8V DC  
Remark: The output pulse width is adjusted to 25  
millisec. even when the input pulse width is narrower  
than 25 millisec.  
P. 1 / 4  
ES-5221 Rev.9  
TMR / TMT  
INSTALLATION  
EXPLANATIONS  
Power input  
AVAILABLE NTT LINE  
AC:  
DC:  
rating ±10%, 50/60 ±2 Hz, approx. 2VA  
rating ±10% (ripple 10% p-p max.)  
approx. 80mA at 24V  
Among the several circuit lines opened by NTT (Nip-  
pon Telephone & Telegraph), the TMR/TMT utilizes  
the “special DC line” of 50 b/s.  
approx. 160mA at 12V  
The following shows the conditions to use this line.  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90% RH (non-condensing)  
Mounting: surface or DIN rail  
ITEM  
DATA  
Transmission speed  
Technical configuration  
50 b/s max.  
2-wire (metalic return)  
4-wire (metalic return  
Dimensions: W50×H80×D123 mm (1.97"×3.15"×4.84")  
Weight:  
350 g (0.77 lbs)  
Communication  
Intersection  
Uni-directional, full-duplex  
Not allowed  
PERFORMANCE  
Response time: 10 millisec.  
Line voltage effect: ±0.1% over voltage range  
Insulation resistance: 100Mwith 500V DC  
Dielectric strength: 1000V AC @1 minute  
(input to output or power)  
Circuit protection  
Required  
Electrical characteristics Current 45mA max.  
Voltage between lines 100V max.  
Voltage to ground 50V max.  
2000V AC @1 minute (output to ground)  
Specifications subject to change without notice.  
P. 2 / 4  
ES-5221 Rev.9  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
TMR (relay)  
OPEN  
COLLECTOR  
RELAY  
5mA  
Current  
Detector  
Frequency  
Limiter  
+
1
2
7
8
3
4
5
6
OUTPUT 1  
OUTPUT 2  
Constant  
Current  
Relay  
U(+)  
POWER  
V(–)  
Base Socket  
TMT (open collector)  
OPEN  
COLLECTOR  
RELAY  
5mA  
Current  
Detector  
Frequency  
Limiter  
+
+
+
1
2
7
8
3
4
5
6
OUTPUT 1  
OUTPUT 2  
Constant  
Current  
Open  
Collector  
U(+)  
POWER  
V(–)  
Base Socket  
Output Connection Examples  
Open Collector  
Relay  
•AC Powered  
+
+
+
+
3
4
5
6
3
4
LOAD  
Relay or  
Counter Coil  
5
6
Varistor or Spark  
Quenching Circuit  
LOAD  
•DC Powered  
3
4
LOAD  
LOAD  
Relay or  
Counter Coil  
5
6
Spark Quenching Diode  
P. 3 / 4  
ES-5221 Rev.9  
TMR / TMT  
TERMINAL CONNECTIONS  
TMR/TMT  
MDP-24-1  
MDP-24-1  
TMR/TMT  
LEASED CIRCUIT  
50 bps  
1
2
7
8
3
4
P+  
P–  
S+  
S–  
S+  
S–  
P+  
P–  
1
2
3
4
7
8
OUTPUT  
G
G
+
POWER  
1
8
5
4
5
4
1
8
POWER  
7
7
MAX-100/200  
MAX-100/200  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENT mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
6
5
4
3
2–4.5 (.18) dia.  
MTG HOLE  
15 (.59) deep  
7
8
1
2
8–M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
123 (4.84)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
•When mounting, no extra space is needed between units.  
Specifications subject to change without notice.  
P. 4 / 4  
ES-5221 Rev.9  

相关型号:

TM-R-J

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-R-R

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-R-S

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-B

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-C

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-D

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-F

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-G

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-H

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-J

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-R

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

TM-T-S

CONTACT TELEMETERING MODULE

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM