W2PE-1ZE-R [MSYSTEM]

Space-saving Dual Output Signal Conditioners Mini-MW Series;
W2PE-1ZE-R
型号: W2PE-1ZE-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Dual Output Signal Conditioners Mini-MW Series

文件: 总3页 (文件大小:119K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: W2PE  
Space-saving Dual Output Signal Conditioners  
[2] OUTPUT 1  
Current  
Mini-MW Series  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
PT TRANSMITTER  
(RMS sensing)  
Functions & Features  
• Converts an alternating voltage input from a potential  
(voltage) transformer  
• Minimum ripple  
• RMS sensing  
• Two independent output ranges  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)  
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
Typical Applications  
• Centralized monitoring and control of power line and  
power supply voltage measured at switch boards  
• Monitoring abnormal voltage drops for detecting overload  
29.5 (1.16)  
Model  
[3] OUTPUT 2  
Y: None  
88.5  
(3.49)  
Current  
ZERO  
SPAN  
A: 4 – 20 mA DC (Load resistance 350 Ω max.)  
B: 2 – 10 mA DC (Load resistance 700 Ω max.)  
C: 1 – 5 mA DC (Load resistance 1400 Ω max.)  
D: 0 – 20 mA DC (Load resistance 350 Ω max.)  
E: 0 – 16 mA DC(Load resistance 430 Ω max.)  
F: 0 – 10 mA DC (Load resistance 700 Ω max.)  
G: 0 – 1 mA DC (Load resistance 7000 Ω max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
124  
(4.88)  
ZERO  
SPAN  
mm (inch)  
MODEL: W2PE–[1][2][3]-[4][5]  
ORDERING INFORMATION  
• Code number: W2PE-[1][2][3]-[4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. W2PE-1AA-M2/CE/Q)  
Same range availability as Output 1  
[4] POWER INPUT  
AC Power  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
Note: When the user requires a current and a voltage  
output, specify the current to be the Output 1 which allows  
a greater load.  
(90 – 264 V for UL)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
R2: 11 – 27 V DC  
[1] INPUT  
Voltage  
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)  
(Select ‘/N’ for ‘Standards & Approvals’ code.)  
P: 110 V DC  
1: 0 – 110 V AC  
5: 0 – 150 V AC  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
(110 V ±10 % for UL)  
W2PE SPECIFICATIONS  
ES-5506 Rev.8 Page 1/3  
http://www.m-system.co.jp/  
MODEL: W2PE  
[5] OPTIONS (multiple selections)  
Standards & Approvals (must be specified)  
/N: Without CE or UL  
INSTALLATION  
Power Consumption  
AC:  
/CE: CE marking  
Approx. 4 VA at 100 V  
Approx. 5 VA at 200 V  
Approx. 6 VA at 240 V  
DC: Approx. 3 W  
/UL: UL approval, CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Weight: 200 g (0.44 lb)  
/C02: Polyurethane coating  
PERFORMANCE in percentage of span  
Accuracy: ±0.4 %  
/C03: Rubber coating (UL not available)  
TERMINAL SCREW MATERIAL  
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
/S01: Stainless steel (UL not available)  
Ripple: 0.5 %p-p max. (100/120 Hz)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
1 to output 2 to power to ground)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3 screw terminals (torque 0.8 N·m)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Input waveform  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
RMS sensing: Up to 15 % of 3rd harmonic content  
Overrange output: 0 to 120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Adjustable individually for each output 1 and output 2.  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Measurement Category II (input)  
Installation Category II (power)  
Pollution Degree 2  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
Input or output 1 or output 2 to power input:  
Reinforced insulation (300 V)  
Input to output 1 to output 2: Basic insulation (300 V)  
RoHS Directive  
Input burden: 0.5 VA max.  
Overload capacity: 200 % of rating for 1 minute, 120 %  
continuous  
EN 50581  
Operational range: 0 – 120 % of rating  
Approval:  
UL/C-UL nonincendive Class I, Division 2,  
Groups A, B, C, and D  
OUTPUT SPECIFICATIONS  
DC Current: 0 – 20 mA DC  
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)  
UL/C-UL general safety requirements  
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max. for Output 1;  
7 V max. for Output 2  
DC Voltage: -10 – +12 V DC (up to 10 V for Output 2)  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V  
W2PE SPECIFICATIONS  
ES-5506 Rev.8 Page 2/3  
http://www.m-system.co.jp/  
MODEL: W2PE  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
6 (.23)  
DIN RAIL  
35mm wide  
3
2
5
1
4
6
24.2x5  
(.17x.20)  
MTG HOLE  
6 (.24) deep  
9
8
7
11M3  
SCREW  
11 10  
22 (.87)  
29.5 (1.16)  
21.5 (.87) 10 (.39)  
84 (3.31)  
114 (4.49)  
[4 (.16)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
SOURCE  
FUSE  
Z
S
INPUT  
TRANSFORMER  
VT  
U
V
u
v
RMS  
Operation  
Output  
Driver  
1
2
4
5
9
7
8
+
OUTPUT 1  
Z
S
Isolation  
LOAD  
Output  
Driver  
3
6
+
OUTPUT 2  
POWER  
10  
11  
U(+)  
V(–)  
Base Socket  
Note: The section enclosed by broken line is only with 2nd output option.  
Specifications are subject to change without notice.  
W2PE SPECIFICATIONS  
ES-5506 Rev.8 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

W2PE-1ZE-R/CE

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R/N

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R/Q

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R/UL

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R2

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R2/CE

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R2/N

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R2/Q

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZE-R2/UL

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZF-M2

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZF-M2/CE

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM

W2PE-1ZF-M2/N

Space-saving Dual Output Signal Conditioners Mini-MW Series

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MSYSTEM