40-GC6NLT1_14 [MTU]
GAS GENERATOR SET;型号: | 40-GC6NLT1_14 |
厂家: | MTU ONSITE ENERGY CORPORATION |
描述: | GAS GENERATOR SET |
文件: | 总4页 (文件大小:466K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
GAS GENERATOR SET
40-GC6NLT1
/
/
40 kWe 60 Hz Standby
208 - 600V
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
240V**
1
240V**
1
208V**
3
240V**
3
480V**
3
600V**
3
PF
Hz
1.0
60
1.0
60
0.8
60
0.8
60
0.8
60
0.8
60
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
167
167
139
120
60
48
40/40
167
40/40
167
40/50
139
40/50
120
40/50
60
40/50
48
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
40/40
40/40
40/50
40/50
40/50
40/50
128
116
125
125
167
92
362CSL1604
130 °C/40 °C
12 LEAD ZIG-ZAG
361CSL1612
130 °C/40 °C
4 LEAD
284PSL1742
130 °C/40 °C
12 LEAD LOW WYE
284PSL1742
130 °C/40 °C
12 LEAD HI DELTA
284PSL1742
130 °C/40 °C
12 LEAD HI WYE
361PSL1632
130 °C/40 °C
4 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
//ꢀ
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
Power Rating
- Accepts Rated Load in One Step Per NFPA 110
ISO 14001:2004
//ꢀ
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//ꢀ
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
/ // ꢀ/
2
40-GC6NLT1
STANDARD FEATURES*
//ꢀ
//ꢀ
//ꢀ
//ꢀ
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
4.3 L Engine
- 4.3 Liter Displacement
- 4-Cycle
Engine-generator resilient mounted
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
Complete Range of Accessories
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
STANDARD EQUIPMENT*
//ꢀ
Engine
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Air Cleaner
Oil Pump
Flexible Coupling
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Full Amortisseur Windings
125% Rotor Balancing
Jacket Water Pump
3-Phase Voltage Sensing
Thermostat
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electronic Isochronous
Base - Formed Steel
//ꢀ
Digital Control Panel(s)
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
16 Programmable Contact Inputs
Up to 11 Contact Outputs
//ꢀ
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
UL Recognized, CSA Certified, CE Approved
Event Recording
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
/ // ꢀ/
3
40-GC6NLT1
APPLICATION DATA
Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
//ꢀ
//ꢀ
Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power (NG): kWm (bhp)
Maximum Power (LP): kWm (bhp)
Speed Regulation
Air Cleaner
GM
4.3L
4-Cycle
6-V
4.3 (262)
10.2 (4)
8.8 (3.5)
9.4:1
1,800
Bosch
49.6 (66.5)
53.2 (71.4)
C/F
NG
13.9 (489)
10.4 (368)
7.3 (256)
LPG
6.1 (216)
4.6 (163)
3.2 (113)
At 100% of Power Rating: m3/hr (ft3/hr)
At 75% of Power Rating: m3/hr (ft3/hr)
At 50% of Power Rating: m3/hr (ft3/hr)
//ꢀ
Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
50 (122)
0.12 (0.5)
117.3 (31)
39 (2,220)
16.5 (938)
3.4 (4.5)
Dry
3.4 (4.5)
//ꢀ
Liquid Capacity (Lubrication)
//ꢀ
Air Requirements
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
4.2 (1.1)
7.2 (1.9)
21.6 (5.7)
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
3.9 (136.5)
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
211.4 (7,464)
//ꢀ
Electrical
Air Flow Required for Dissipation
of Radiated Gen-set Heat For a
Max of 25 °F Rise: *m3/min (SCFM)
Electric Volts DC
12
59.9 (2,114)
Cold Cranking Amps Under -17.8 °C (0 °F)
925
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
//ꢀ
Fuel Inlet
//ꢀ
Exhaust System
Fuel Supply Connection Size
3/4” NPT
Fuel Supply Pressure: mm H20 (in. H20)
178–279 (7–11)
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
704.4 (1,300)
Temp: m3/min (CFM)
12.5 (440.8)
10 (40)
Maximum Allowable
Back Pressure: kPa (in. H20)
/ // ꢀ/
4
40-GC6NLT1
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Dimensions (LxWxH)
Weight (dry)
OPU
1,981 x 864 x 1,229 mm (78 x 34 x 48.38 in)
572 kg (1,260 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Standby Full Load
Level 0: Open Power Unit dB(A)
WPE - No Sound Attenuation dB(A)
CQE dB(A)
C/F
C/F
C/F
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
//ꢀ
Fuel Type
Natural Gas
Liquid Propane
THC + NOx
5.24
6.09
CO
16.38
23.88
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, AS 2789, and DIN 6271.
Deration Factor:
All units are in g/hp-hr.
Engine meets EPA 40 CFR Part 60/90 specifications.
//ꢀ
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
相关型号:
40.0000MHZEQXO-2100BMH
CMOS/TTL Output Clock Oscillator, 40MHz Nom, HERMETIC SEALED, METAL, DIP-8/4
EUROQUARTZ
©2020 ICPDF网 联系我们和版权申明