DIESEL GENERATOR SET  
800-XC6DT2  
/
/
800 kWe 60 Hz Prime  
208 - 4160V  
(Reference 900-XC6DT2 for Standby Rating Technical Data)  
SYSTEM RATINGS  
Prime  
Voltage (L-L)  
Phase  
208V**  
3
240V**  
3
380V  
3
480V**  
3
600V**  
3
4160V  
3
PF  
0.8  
0.8  
0.8  
0.8  
0.8  
0.8  
Hz  
60  
60  
60  
60  
60  
60  
kW  
kVA  
Amps  
800  
1000  
2776  
800  
1000  
2406  
800  
1000  
1521  
800  
1000  
1203  
800  
1000  
962  
800  
1000  
139  
skVA@30%  
Voltage Dip  
Generator Model*  
Temp Rise  
Connection  
2600  
2600  
1850  
2500  
2850  
1950  
741RSL4045  
105 °C/40 °C  
12 LEAD LOW WYE  
741RSL4045  
105 °C/40 °C  
12 LEAD HI DELTA  
740RSL4046  
105 °C/40 °C  
4 BAR WYE  
574RSL4037  
105 °C/40 °C  
12 LEAD HI WYE  
574RSS4280  
105 °C/40 °C  
4 LEAD WYE  
741FSM4360  
105 °C/40 °C  
6 LEAD WYE  
* Consult the factory for alternate conguration.  
** UL 2200 Oered  
CERTIFICATIONS AND STANDARDS  
//  
//ꢀ  
Emissions – EPA Tier 2 Certied  
Performance Assurance Certification (PAC)  
- Generator Set Tested to ISO 8528-5 for Transient Response  
- Veried product design, quality and performance integrity  
- All engine systems are prototype and factory tested  
//ꢀ  
Generator set is designed and manufactured  
in facilities certied to standards ISO 9001:2008 and  
ISO 14001:2004  
//ꢀ  
Power Rating  
//ꢀ  
UL 2200 / CSA – Optional  
– UL 2200 Listed  
– CSA Certied  
- Accepts Rated Load in One Step Per NFPA 110  
- Permissible average power output during 24 hours of  
operation is approved up to 75%.  
/ // /  
2
800-XC6DT2  
STANDARD FEATURES*  
//ꢀ  
//ꢀ  
MTU Onsite Energy is a single source supplier  
Global Product Support  
2 Year Standard Warranty  
16V 2000 Diesel Engine  
- 31.8 Liter Displacement  
- Electronic Unit Pump Injection  
- 4-Cycle  
Generator  
- Brushless, Rotating Field Generator  
- 2/3 Pitch Windings  
- PMG (Permanent Magnet Generator) supply to regulator  
- 300% Short Circuit Capability  
Digital Control Panel(s)  
- UL Recognized, CSA Certied, NFPA 110  
- Complete System Metering  
- LCD Display  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
Complete Range of Accessories  
Cooling System  
- Integral Set-Mounted  
- Engine Driven Fan  
STANDARD EQUIPMENT*  
//ꢀ  
Engine  
Air Cleaners  
Oil Pump  
Oil Drain Extension & S/O Valve  
Full Flow Oil Filter  
Closed Crankcase Ventilation  
Jacket Water Pump  
No Load to Full Load Regulation  
Brushless Alternator with Brushless Pilot Exciter  
4 Pole, Rotating Field  
105 °C Maximum Prime Temperature Rise  
1 Bearing, Sealed  
Flexible Coupling  
Inter Cooler Water Pump  
Thermostats  
Full Amortisseur Windings  
125% Rotor Balancing  
Blower Fan & Fan Drive  
Radiator - Unit Mounted  
Electric Starting Motor - 24V  
Governor – Electronic Isochronous  
Base - Structural Steel  
SAE Flywheel & Bell Housing  
Charging Alternator - 24V  
Battery Box & Cables  
Flexible Fuel Connectors  
Flexible Exhaust Connection  
EPA Certied Engine  
3-Phase Voltage Sensing  
±0.25% Voltage Regulation  
100% of Rated Load - One Step  
5% Maximum Total Harmonic Distortion  
//ꢀ  
Digital Control Panel(s)  
Digital Metering  
Engine Parameters  
Generator Protection Functions  
Engine Protection  
CAN Bus ECU Communications  
Windows®-Based Software  
Multilingual Capability  
//ꢀ  
Generator  
NEMA MG1, IEEE and ANSI standards compliance for temperature rise  
and motor starting  
Sustained short circuit current of up to 300% of the rated current for  
up to 10 seconds  
Remote Communications to RDP-110 Remote Annunciator  
16 Programmable Contact Inputs  
Up to 11 Contact Outputs  
UL Recognized, CSA Certied, CE Approved  
Event Recording  
Self-Ventilated and Drip-Proof  
Superior Voltage Waveform  
Digital, Solid State, Volts-per-Hertz Regulator  
IP 54 Front Panel Rating with Integrated Gasket  
NFPA110 Compatible  
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional congurations.  
/ // /  
3
800-XC6DT2  
APPLICATION DATA  
//ꢀ  
//ꢀ  
Engine  
Fuel Consumption  
Manufacturer  
Model  
Type  
Arrangement  
Displacement: L (in3)  
Bore: cm (in)  
MTU  
16V 2000 G45 TB  
PRIME  
221.4 (58.5)  
169.2 (44.7)  
15.4 (30.5)  
At 100% of Power Rating: L/hr (gal/hr)  
At 75% of Power Rating: L/hr (gal/hr)  
At 50% of Power Rating: L/hr (gal/hr)  
4-Cycle  
16-V  
31.8 (1,943)  
13 (5.1)  
//ꢀ  
Stroke: cm (in)  
Compression Ratio  
Rated RPM  
15 (5.9)  
16:1  
1,800  
Cooling - Radiator System  
PRIME  
Engine Governor  
Maximum Power: kWm (bhp)  
Speed Regulation  
Air Cleaner  
Electronic Isochronous (ADEC)  
Ambient Capacity of Radiator: °C (°F)  
Maximum Restriction of Cooling Air, Intake,  
and Discharge Side of Rad.: kPa (in. H20)  
Water Pump Capacity: L/min (gpm)  
After Cooler Pump Capacity: L/min (gpm)  
Heat Rejection to Coolant: kW (BTUM)  
Heat Rejection to After Cooler: kW (BTUM)  
Heat Radiated to Ambient: kW (BTUM)  
Fan Power: kW (hp)  
50 (122)  
915 (1,227)  
±0.25%  
Dry  
0.12 (0.5)  
833 (220)  
257 (68)  
320 (18,197)  
265 (15,070)  
92.5 (5,260)  
55.6 (74.5)  
//ꢀ  
Liquid Capacity (Lubrication)  
Total Oil System: L (gal)  
102 (26.9)  
130 (34.3)  
20 (5.3)  
Engine Jacket Water Capacity: L (gal)  
After Cooler Water Capacity: L (gal)  
System Coolant Capacity: L (gal)  
//ꢀ  
415 (110)  
Air Requirements  
PRIME  
81 (2,860)  
Aspirating: *m3/min (SCFM)  
Air Flow Required for Rad.  
//ꢀ  
Electrical  
Electric Volts DC  
Cold Cranking Amps Under -17.8 °C (0 °F)  
24  
2,800  
Cooled Unit: *m3/min (SCFM)  
Remote Cooled Applications;  
Air Flow Required for Dissipation  
of Radiated Gen-set Heat for a  
Max of 25 °F Rise: *m3/min (SCFM)  
1,133 (40,013)  
336 (11,863)  
//ꢀ  
Fuel System  
Fuel Supply Connection Size  
Fuel Return Connection Size  
Maximum Fuel Lift: m (ft)  
Recommended Fuel  
3/4” NPT  
1/4” NPT  
3 (10)  
Diesel #2  
480.7 (127)  
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)  
//ꢀ  
Exhaust System  
Total Fuel Flow: L/hr (gal/hr)  
PRIME  
Gas Temp. (Stack): °C ( °F)  
Gas Volume at Stack  
520 (968)  
Temp: m3/min (CFM)  
190 (6,780)  
8.5 (34.1)  
Maximum Allowable  
Back Pressure: kPa (in. H20)  
/ // /  
4
800-XC6DT2  
WEIGHTS AND DIMENSIONS  
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website  
for unit specic template drawings.  
System  
Dimensions (LxWxH)  
Weight (less tank)  
OPU  
5,010 x 1,940 x 2,600 mm (197.4 x 76.5 x 102.5 in)  
7,733 kg (17,047 lb)  
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specic generator set.  
SOUND DATA  
Unit Type  
Prime Full Load  
Level 0: Open Power Unit dB(A)  
92.5  
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with innite exhaust.  
EMISSIONS DATA  
RATING DEFINITIONS AND CONDITIONS  
//ꢀ  
NOx + NMHC  
4.36  
CO  
0.35  
PM  
0.03  
Prime power ratings apply to installations where utility power  
is unavailable or unreliable. At varying load, the number of  
generator set operating hours is unlimited. A 10% overload  
capacity is available for one hour in twelve. Ratings are in  
accordance with ISO 8528-1, ISO 3046-1, BS 5514, AS 2789,  
and DIN 6271.  
All units are in g/hp-hr and at 100% load.  
Emission levels of the engine may vary as a function of ambient  
temperature, barometric pressure, humidity, fuel type and  
quality, installation parameters, measuring instrumentation,  
etc. The data provided are laboratory results from one  
engine representing this rating. The data was obtained  
under controlled environmental conditions with calibrated  
instrumentation traceable to the United States National Bureau  
of Standards and in compliance with US EPA regulations found  
within 40 CFR Part 89. The weighted cycle value (not shown)  
from each engine is guaranteed to be below the US EPA  
Standards at the US EPA dened conditions.  
//ꢀ  
Deration Factor:  
Altitude: Consult your local MTU Onsite Energy Power  
Generation Distributor for altitude derations.  
Temperature: Consult your local MTU Onsite Energy Power  
Generation Distributor for temperature derations.  
Materials and specications subject to change without notice.  
C/F = Consult Factory/MTU Onsite Energy Distributor  
MTU Onsite Energy  
A Rolls-Royce Power Systems Brand  
www.mtuonsiteenergy.com  

相关型号:

800-Z1-016-10-001

PCB connectors 2.54 mm Single row / double row Solder tail
PREDIP

800-Z1-016-10-002

PCB connectors 2.54 mm Single row / double row Solder tail
PREDIP

800-Z1-016-20-001

PCB connectors 2.54 mm Single row / double row Solder tail
PREDIP

800-Z1-016-30-001

PCB connectors 2.54 mm Single row / double row Surface mount
PREDIP

800-Z1-016-40-001

PCB connectors 2.54 mm Single row / double row Surface mount
PREDIP

8000

PRINTED CIRCUIT PINS
MILL-MAX
MILL-MAX
MILL-MAX

8000-0-01-1-3

PCB Terminal
MILL-MAX

8000-0-01-34-3

PCB Terminal
MILL-MAX

8000-12-1

Analog IC
ETC

8000-15

Analog IC
ETC