800-XC6DT2_14 [MTU]
DIESEL GENERATOR SET;型号: | 800-XC6DT2_14 |
厂家: | MTU ONSITE ENERGY CORPORATION |
描述: | DIESEL GENERATOR SET |
文件: | 总4页 (文件大小:229K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
DIESEL GENERATOR SET
800-XC6DT2
/
/
800 kWe 60 Hz Prime
208 - 4160V
(Reference 900-XC6DT2 for Standby Rating Technical Data)
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
208V**
3
240V**
3
380V
3
480V**
3
600V**
3
4160V
3
PF
0.8
0.8
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
60
kW
kVA
Amps
800
1000
2776
800
1000
2406
800
1000
1521
800
1000
1203
800
1000
962
800
1000
139
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
2600
2600
1850
2500
2850
1950
741RSL4045
105 °C/40 °C
12 LEAD LOW WYE
741RSL4045
105 °C/40 °C
12 LEAD HI DELTA
740RSL4046
105 °C/40 °C
4 BAR WYE
574RSL4037
105 °C/40 °C
12 LEAD HI WYE
574RSS4280
105 °C/40 °C
4 LEAD WYE
741FSM4360
105 °C/40 °C
6 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
//ꢀ
Emissions – EPA Tier 2 Certified
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//ꢀ
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//ꢀ
Power Rating
//ꢀ
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.
/ // ꢀ/
2
800-XC6DT2
STANDARD FEATURES*
//ꢀ
//ꢀ
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
16V 2000 Diesel Engine
- 31.8 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- PMG (Permanent Magnet Generator) supply to regulator
- 300% Short Circuit Capability
Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
Complete Range of Accessories
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
STANDARD EQUIPMENT*
//ꢀ
Engine
Air Cleaners
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Closed Crankcase Ventilation
Jacket Water Pump
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
105 °C Maximum Prime Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Inter Cooler Water Pump
Thermostats
Full Amortisseur Windings
125% Rotor Balancing
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electronic Isochronous
Base - Structural Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
3-Phase Voltage Sensing
±0.25% Voltage Regulation
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
//ꢀ
Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
CAN Bus ECU Communications
Windows®-Based Software
Multilingual Capability
//ꢀ
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for
up to 10 seconds
Remote Communications to RDP-110 Remote Annunciator
16 Programmable Contact Inputs
Up to 11 Contact Outputs
UL Recognized, CSA Certified, CE Approved
Event Recording
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
/ // ꢀ/
3
800-XC6DT2
APPLICATION DATA
//ꢀ
//ꢀ
Engine
Fuel Consumption
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
MTU
16V 2000 G45 TB
PRIME
221.4 (58.5)
169.2 (44.7)
15.4 (30.5)
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
4-Cycle
16-V
31.8 (1,943)
13 (5.1)
//ꢀ
Stroke: cm (in)
Compression Ratio
Rated RPM
15 (5.9)
16:1
1,800
Cooling - Radiator System
PRIME
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
Electronic Isochronous (ADEC)
Ambient Capacity of Radiator: °C (°F)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
After Cooler Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Rejection to After Cooler: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
50 (122)
915 (1,227)
±0.25%
Dry
0.12 (0.5)
833 (220)
257 (68)
320 (18,197)
265 (15,070)
92.5 (5,260)
55.6 (74.5)
//ꢀ
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
102 (26.9)
130 (34.3)
20 (5.3)
Engine Jacket Water Capacity: L (gal)
After Cooler Water Capacity: L (gal)
System Coolant Capacity: L (gal)
//ꢀ
415 (110)
Air Requirements
PRIME
81 (2,860)
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
//ꢀ
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
24
2,800
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
1,133 (40,013)
336 (11,863)
//ꢀ
Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
3/4” NPT
1/4” NPT
3 (10)
Diesel #2
480.7 (127)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
//ꢀ
Exhaust System
Total Fuel Flow: L/hr (gal/hr)
PRIME
Gas Temp. (Stack): °C ( °F)
Gas Volume at Stack
520 (968)
Temp: m3/min (CFM)
190 (6,780)
8.5 (34.1)
Maximum Allowable
Back Pressure: kPa (in. H20)
/ // ꢀ/
4
800-XC6DT2
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Dimensions (LxWxH)
Weight (less tank)
OPU
5,010 x 1,940 x 2,600 mm (197.4 x 76.5 x 102.5 in)
7,733 kg (17,047 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Prime Full Load
Level 0: Open Power Unit dB(A)
92.5
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
//ꢀ
NOx + NMHC
4.36
CO
0.35
PM
0.03
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514, AS 2789,
and DIN 6271.
All units are in g/hp-hr and at 100% load.
Emission levels of the engine may vary as a function of ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one
engine representing this rating. The data was obtained
under controlled environmental conditions with calibrated
instrumentation traceable to the United States National Bureau
of Standards and in compliance with US EPA regulations found
within 40 CFR Part 89. The weighted cycle value (not shown)
from each engine is guaranteed to be below the US EPA
Standards at the US EPA defined conditions.
//ꢀ
Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
相关型号: