DP55D6S [MTU]
DIESEL GENERATOR SET;型号: | DP55D6S |
厂家: | MTU ONSITE ENERGY CORPORATION |
描述: | DIESEL GENERATOR SET |
文件: | 总4页 (文件大小:205K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
DIESEL GENERATOR SET
DP55D6S
/
/
55 kWe 60 Hz Prime
208 - 600V
(Reference DS60D6S for Standby Rating Technical Data)
SYSTEM RATINGS
Prime
DP55D6SGA
DP55D6SDA
DP55D6SPA
DP55D6SJA
DP55D6SVA
DP55D6SRA
DP55D6SNA
Voltage (L-L) 240V**
240V**
1
208V**
3
240V**
3
380V**
3
480V**
3
600V**
3
Phase
1
PF
Hz
kW
kVA
1.0
60
56
56
233
1.0
60
55
55
0.8
60
58
72.5
201
0.8
60
58
72.5
174
0.8
60
55
68.75
104
0.8
60
55
68.75
82
0.8
60
55
68.75
66
Amps
229
skVA@30%
Voltage Dip
Generator
Model*
Temp Rise
Connection
119
132
200
200
265
172
138
362CSL1604
105 °C/40 °C 105 °C/40 °C
361CSL1613
361CSL1602
105 °C/40 °C
361CSL1602
105 °C/40 °C
12 LEAD
HI DELTA
361CSL1602
105 °C/40 °C
12 LEAD
HI WYE
361CSL1601
361PSL1633
105 °C/40 °C 105 °C/40 °C
12 LEAD
12 LEAD
12 LEAD
DOUBLE DELTA 4 LEAD
LOW WYE
HI WYE
4 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
//ꢀ
Emissions – EPA Tier 3 Certified
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//ꢀ
Generator set is designed and manufactured in
facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//ꢀ
Power Rating
- Accepts Rated Load in One Step Per NFPA 110
//ꢀ
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
/ // ꢀ/
2
DP55D6S
STANDARD FEATURES*
//ꢀ
//ꢀ
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
4045HF280 Diesel Engine
- 4.5 Liter Displacement
- Mechanical Injection Pump
- 4-Cycle
Engine-generator resilient mounted
Complete Range of Accessories
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
STANDARD EQUIPMENT*
//ꢀ
Engine
Air Cleaner
Oil Pump
105 °C Maximum Prime Temperature Rise
1 Bearing, Sealed
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Fuel Filter with Water Separator
Jacket Water Pump
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
Thermostat
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Mechanical Droop
Base - Formed Steel
//ꢀ
Digital Control Panel(s)
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Contact Inputs
Programmable Contact Outputs
UL Recognized, CSA Certified, CE Approved
Event Recording
//ꢀ
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self-Ventilated and Drip-Proof
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
Superior Voltage Waveform
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
/ // ꢀ/
3
DP55D6S
APPLICATION DATA
//ꢀ
//ꢀ
Engine
Fuel Consumption
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
John Deere
4045HF280
4-Cycle
PRIME
17.8 (4.7)
13.6 (3.6)
9.5 (2.5)
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
4-Inline
4.5 (275)
10.6 (4.19)
12.7 (5.0)
19.0:1
//ꢀ
Cooling - Radiator System
1,800
PRIME
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
Mechanical Droop
67 (90)
Ambient Capacity of Radiator: °C (°F)
Maximum Allowable Static
50 (122)
±0.50%
Pressure on Rad. Exhaust: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Rejection to Air to Air: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
0.12 (0.5)
144 (38)
33 (1,849)
4 (233)
9.2 (522)
1.16 (1.55)
Dry
//ꢀ
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
13 (3.4)
8.5 (2.3)
16.7 (4.4)
//ꢀ
Air Requirements
PRIME
5.3 (187)
//ꢀ
Electrical
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
12
925
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
91 (3,162)
34 (1,176)
//ꢀ
Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
3/8” NPT
3/8” NPT
1.8 (6)
Diesel #2
113 (29.9)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
//ꢀ
Exhaust System
Total Fuel Flow: L/hr (gal/hr)
PRIME
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
515 (959)
Temp: m3/min (CFM)
13.5 (477)
7.5 (30)
N/A
Maximum Allowable
Back Pressure: kPa (in. H20)
Minimum Allowable
Back Pressure: kPa (in. H20)
/ // ꢀ/
4
DP55D6S
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Dimensions (LxWxH)
Weight (dry/less tank)
Open Power Unit (OPU)
1,873 x 800 x 1,232 mm (73.75 x 31.50 x 48.50 in)
964 kg (2,120 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Prime Full Load
Level 0: Open Power Unit dB(A)
76.1
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
//ꢀ
NOx
3.2
HC
0.17
CO
0.7
PM
0.22
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, overload power in accordance
with ISO 3046-1, BS 5514, AS 2789, and DIN 6271.
Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
All units are in g/hp-hr and are EPA D2 cycle values.
Emission levels of the engine may vary as a function of ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one
engine representing this rating. The data was obtained
under controlled environmental conditions with calibrated
instrumentation traceable to the United States National Bureau
of Standards and in compliance with US EPA regulations found
within 40 CFR Part 89. The weighted cycle value from each
engine is guaranteed to be below the US EPA Standards at the
US EPA defined conditions.
//ꢀ
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
相关型号: