DS1650D5S [MTU]

DIESEL GENERATOR SET;
DS1650D5S
型号: DS1650D5S
厂家: MTU ONSITE ENERGY CORPORATION    MTU ONSITE ENERGY CORPORATION
描述:

DIESEL GENERATOR SET

文件: 总6页 (文件大小:679K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
DIESEL GENERATOR SET  
DS01650D5S  
380V – 11 kV/50 Hz/Standby/Fuel Consumption Optimized  
MTU 12V4000G23/Water Charge Air Cooling  
Optional equipment and finishing shown. Standard may vary.  
PRODUCT HIGHLIGHTS  
//  
//  
//  
Benefits  
Performance Assurance Certification (PAC)  
- Engine-generator set tested to ISO 8528-5 for transient  
response  
- 85% load factor  
- Verified product design, quality and performance integrity  
- All engine systems are prototype and factory tested  
- Low fuel consumtion  
- Optimized system integration ability  
- High reliability  
- High availability of power  
- Long maintenance intervals  
//  
//  
MTU Onsite Energy is a single-source supplier  
Complete range of accessories available  
- Control panel  
- Circuit breaker/power distribution  
- Fuel system  
Support  
- Global product support offered  
- Fuel connections with shut-off valve mounted to base frame  
- Starting/charging system  
//  
Standards  
- Engine-generator set is designed and manufactured in  
facilities certified to standards ISO 2008:9001 and  
ISO 2004:14001  
- Exhaust system  
- Mechanical and electrical driven radiators  
- Medium voltage alternators  
- Generator set complies to ISO 8528  
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and  
IEC standards  
//  
//  
Emissions  
- Fuel consumption optimized  
- NFPA 110  
Certifications  
//  
Power Rating  
- CE certification option  
- System ratings: 1650 kVA - 1700 kVA  
- Accepts rated load in one step per NFPA 110  
- Generator set complies to G3 according to ISO 8528-5  
- Generator set exceeds load steps according to ISO 8528-5  
/ // /  
2
DS01650D5S / 50 Hz / 380V - 11kV  
APPLICATION DATA  
//  
//  
Engine  
Liquid Capacity (Lubrication)  
Manufacturer  
Model  
Type  
MTU Total oil system capacity: l  
12V4000G23 Engine jacket water capacity: l  
260  
160  
40  
4-cycle System coolant capacity: l  
Arrangement  
Displacement: l  
Bore: mm  
12V  
57.2  
170  
//  
Combustion Air Requirements  
Stroke: mm  
210 Combustion air volume: m3/s  
1.8  
50  
Compression ratio  
Rated speed: rpm  
Engine governor  
Max power: kWm  
Air cleaner  
16.4 Max. air intake restriction: mbar  
1500  
ADEC (ECU 7)  
1575  
//  
Cooling/Radiator System  
Dry Coolant flow rate (HT circuit): m3/h  
Coolant flow rate (LT circuit): m3/h  
Heat rejection to coolant: kW  
56  
30  
580  
260  
75  
//  
Fuel System  
Heat radiated to charge air cooling: kW  
Maximum fuel lift: m  
Total fuel flow: l/min  
5
Heat radiated to ambient: kW  
16 Fan power for mech. radiator (40°C): kWm  
38  
//  
//  
Fuel Consumption  
Exhaust System  
l/hr  
g/kwh  
At 100% of power rating:  
At 75% of power rating:  
At 50% of power rating:  
358.6  
276.1  
189.8  
189 Exhaust gas temp. (after turbocharger): °C  
440  
4.5  
85  
194 Exhaust gas volume: m3/s  
200 Maximum allowable back pressure: mbar  
Minimum allowable back pressure: mbar  
30  
All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).  
Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.  
All fuel consumption values refer to rated engine power.  
/ // /  
3
DS01650D5S / 50 Hz / 380V - 11kV  
STANDARD AND OPTIONAL FEATURES  
//  
System Ratings (kW/kVA)  
Generator model  
Voltage  
Fuel consumption optimized 40°C/400m  
with mechanical radiator with electr. driven radiator  
without radiator  
kWel*  
1360  
1360  
1320  
1360  
1360  
1320  
n.a.  
kVA**  
1700  
1700  
1650  
1700  
1700  
1650  
n.a.  
AMPS  
kWel*  
1320  
1320  
1320  
1320  
1320  
1320  
n.a.  
kVA**  
1650  
1650  
1650  
1650  
1650  
1650  
n.a.  
AMPS  
2507  
2382  
2295  
2507  
2382  
2295  
n.a.  
kWel*  
1320  
1320  
1320  
1320  
1320  
1320  
n.a.  
kVA*  
1650  
1650  
1650  
1650  
1650  
1650  
n.a.  
AMPS  
2507  
2382  
2295  
2507  
2382  
2295  
n.a.  
Marathon 743RSL7090  
(Low voltage  
marathon standard)  
Marathon 744RSL7091  
(Low voltage  
marathon oversized)  
n.a.  
(Low voltage marathon  
De-rating optimized)  
Marathon 1020FDH7095  
(Medium volt. marathon)  
380 V  
400 V  
415 V  
380 V  
400 V  
415 V  
380 V  
400 V  
415 V  
11 kV  
2583  
2454  
2295  
2583  
2454  
2295  
n.a.  
n.a.  
n.a.  
89  
n.a.  
n.a.  
1360  
n.a.  
n.a.  
1700  
n.a.  
n.a.  
1320  
n.a.  
n.a.  
1650  
n.a.  
n.a.  
87  
n.a.  
n.a.  
1360  
n.a.  
n.a.  
1700  
n.a.  
n.a.  
89  
* cos phi = 1,0  
** cos phi = 0,8  
//  
Engine  
4-Cycle  
Standard single stage air filter  
Oil drain extension & shut-off valve  
Closed crankcase ventilation  
Governor-electronic isochronous  
Common rail fuel injection  
Fuel consumption optimized engine  
//  
Generator  
NEMA MG1, BS5000, ISO, DIN EN and  
IEC standards  
Self-ventilated  
Superior voltage waveform  
Solid state, volts-per-Hertz regulator  
No load to full load regulation  
0,25% voltage regulation no load to  
full load  
Brushless alternator with brushless  
pilot exciter  
Marathon low voltage generator  
† Leroy Somer generator  
(please contact your local MTU Onsite  
Energy distribution partner for system  
ratings)  
4 pole, rotating field  
† Oversized generator  
Sustained short circuit current of up  
to 250% of the rated current for up  
to 10 seconds (marathon generator)  
† Sustained short circuit current of up  
to 300% of the rated current for up to  
10 seconds (Leroy Somer generator)  
† Medium voltage generator  
Represents standard features  
† Represents optional features  
/ // /  
4
DS01650D5S / 50 Hz / 380V - 11kV  
STANDARD AND OPTIONAL FEATURES, CONTINUATION  
//  
Cooling System  
Jacket water pump  
Thermostat(s)  
Water charge air cooling  
† Mechanical radiator  
† Electrical driven front-end cooler  
† Jacket water heater  
//  
Control Panel  
Pre-wired control cabinet for easy  
application of customized controller  
(V1+)  
† Island operation (V2)  
† Automatic mains failure operation  
with ATS (V3a)  
† Automatic mains failure operation  
incl. control of generator and mains  
breaker (V3b)  
† Island parallel operation of multiple  
gensets (V4)  
† Automatic mains failure operation  
with short (< 10s) mains parallel  
overlap synchronization (V5)  
† Mains parallel operation of a single  
genset (V6)  
† Basler controller  
† Deif controller  
Complete system metering  
Digital metering  
Engine parameters  
Generator Protection Functions  
Engine protection  
SAE J1939 engine ECU  
communications  
Parametrization software  
Multilingual capability  
Multiple programmable contact inputs  
Multiple contact outputs  
Event recording  
† Different expansion modules  
† Remote annunciator  
† Daytank control  
† Generator winding temperature  
monitoring  
† Generator bearing temperature  
monitoring  
† Differential protection with  
multi-finction protection relay  
† Modbus RTU-TCP gateway  
IP 54 front panel rating with  
integrated gasket  
† Mains parallel operation of multiple  
gensets (V7)  
//  
Circuit Breaker/Power Distribution  
† 3-pole circuit breaker  
† 4-pole circuit breaker  
† Manual-actuated circuit breaker  
† Electrical-actuated circuit breaker  
† Stand-alone solution in seperate  
switch box  
//  
Fuel System  
Flexible fuel connectors mounted to  
base frame  
† Fuel filter with water separator  
† Switchable fuel filter with  
water separator  
† Seperate fuel cooler  
† Fuel cooler integrated into cooling  
equipment  
Represents standard features  
† Represents optional features  
/ // /  
5
DS01650D5S / 50 Hz / 380V - 11kV  
STANDARD AND OPTIONAL FEATURES, CONTINUATION  
//  
Starting/Charging System  
24V starter  
† Starter batteries  
† Battery rack & cables  
† Battery charger  
//  
Mounting System  
Welded base frame  
Resilient engine and generator  
Modular base frame design  
mounting  
//  
Exhaust System  
† Exhaust bellows with connection  
flange  
† Exhaust silencer with 40 dB(A) sound  
attenuation  
† Exhaust silencer with 10 dB(A) sound  
attenuation  
† Y-connection-pipe  
† Exhaust silencer with 30 dB(A) sound  
attenuation  
Represents standard features  
† Represents optional features  
/ // /  
6
DS01650D5S / 50 Hz / 380V - 11kV  
WEIGHTS AND DIMENSIONS  
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.  
See website for unit specific template drawings.  
System  
Dimensions (LxWxH)  
Weight (dry/less tank)  
Open Power Unit (OPU)  
4419 x 1836 x 2330 mm  
10477 kg  
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.  
SOUND DATA  
//  
Consult your local MTU Onsite Energy distributor for sound data.  
EMISSIONS DATA  
//  
Consult your local MTU Onsite Energy distributor for emissions data.  
RATING DEFINITIONS AND CONDITIONS  
//  
Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for  
the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1,  
BS 5514, AS 2789, and DIN 6271. Average Load Factor: < 85%. Operating hours/year: max. 500.  
Deration factor:  
//  
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.  
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.  
Rated power is available up to 40°C and 400m above sea level.  
Materials and specifications subject to change without notice.  
MTU Onsite Energy  
A Rolls-Royce Power Systems Brand  
www.mtuonsiteenergy.com  

相关型号:

DS1650J

Quad Differential Line Receivers
NSC

DS1650J

QUAD LINE RECEIVER, CDIP16, CERAMIC, DIP-16
TI

DS1650J/883B

IC,LINE RECEIVER,QUAD,BIPOLAR,DIFFERENTIAL,DIP,16PIN,CERAMIC
TI

DS1650J/883C

IC,LINE RECEIVER,QUAD,BIPOLAR,DIFFERENTIAL,DIP,16PIN,CERAMIC
TI

DS1650J/A+

IC,LINE RECEIVER,QUAD,BIPOLAR,DIFFERENTIAL,DIP,16PIN,CERAMIC
TI

DS1650Y-100

Non-Volatile SRAM Module, 512KX8, 100ns, CMOS,
DALLAS

DS1650Y-100-IND

Non-Volatile SRAM Module, 512KX8, 100ns, CMOS,
DALLAS

DS1650Y-70

Non-Volatile SRAM Module, 512KX8, 70ns, CMOS,
DALLAS

DS1650Y-70-IND

NVRAM (Battery Based)
ETC

DS1650Y-85

Non-Volatile SRAM Module, 512KX8, 85ns, CMOS,
DALLAS

DS1650Y-85-IND

Non-Volatile SRAM Module, 512KX8, 85ns, CMOS, PDIP32, 0.600 INCH, PLASTIC, DIP-32
MAXIM

DS1650Y-85-IND

Non-Volatile SRAM Module, 512KX8, 85ns, CMOS,
DALLAS