GAS GENERATOR SET  
GS200-6S  
/
/
200 kWe 60 Hz Standby  
208 - 600V  
(Reference GP175N6S for Prime Rating Technical Data)  
SYSTEM RATINGS  
Standby (NG)  
GS200N6SGA  
GS200N6SDA  
GS200L6SDA  
GS200N6SPA  
GS200L6SPA  
GS200N6SJA  
GS200L6SJA  
GS200N6SRA  
GS200L6SRA  
GS200N6SNA  
GS200L6SNA  
GS200L6SGA  
Standby (LP)  
Voltage (L-L)  
Phase  
240V**  
1
240V**  
1
208V**  
3
240V**  
3
480V**  
3
600V**  
3
PF  
Hz  
1.0  
60  
1.0  
60  
0.8  
60  
0.8  
60  
0.8  
60  
0.8  
60  
Natural Gas  
Ratings: Amps  
Natural Gas  
Ratings: kW/kVA  
LP Gas  
750  
750  
694  
601  
300  
240  
180/180  
541  
180/180  
541  
200/250  
451  
200/250  
390  
200/250  
195  
200/250  
156  
Ratings: Amps  
LP Gas  
Ratings: kW/kVA  
skVA@30%  
Voltage Dip  
Generator Model*  
Temp Rise  
Connection  
130/130  
130/130  
130/162  
130/162  
130/162  
130/162  
425  
370  
608  
608  
809  
720  
433CSL6216  
130 °C/40 °C  
12 LEAD ZIG-ZAG  
432PSL6228  
130 °C/40 °C  
4 LEAD  
432CSL6210  
130 °C/40 °C  
12 LEAD LOW WYE  
432CSL6210  
130 °C/40 °C  
12 LEAD HI DELTA  
432CSL6210  
130 °C/40 °C  
12 LEAD HI WYE  
432PSL6246  
130 °C/40 °C  
4 LEAD WYE  
* Consult the factory for alternate conguration.  
** UL 2200 Oered  
CERTIFICATIONS AND STANDARDS  
//  
//ꢀ  
Generator set is designed and manufactured  
in facilities certied to standards ISO 9001:2008 and  
Power Rating  
- Accepts Rated Load in One Step Per NFPA 110  
ISO 14001:2004  
//ꢀ  
UL 2200 / CSA – Optional  
UL 2200 Listed  
CSA Certied  
//ꢀ  
Performance Assurance Certification (PAC)  
- Generator Set Tested to ISO 8528-5 for  
Transient Response  
- Veried product design, quality and performance integrity  
- All engine systems are prototype and factory tested  
/ // /  
2
GS200-6S  
STANDARD FEATURES*  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
MTU Onsite Energy is a single source supplier  
Global Product Support  
2 Year Standard Warranty  
11.1 L Turbo Engine Charge Air Cooling  
- 11.1 Liter Displacement  
- 4-Cycle  
3-Way Catalyst  
Optional Fuels: LP Liquid and Dual Fuel  
Engine-generator resilient mounted  
Generator  
- Brushless, Rotating Field Generator  
- 2/3 Pitch Windings  
- 300% Short Circuit Capability with Optional PMG  
Digital Control Panel(s)  
- UL Recognized, CSA Certied, NFPA 110  
- Complete System Metering  
- LCD Display  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
Cooling System  
- Integral Set-Mounted  
//ꢀ  
Complete Range of Accessories  
- Engine Driven Fan  
STANDARD EQUIPMENT*  
//ꢀ  
Engine  
Brushless Alternator with Brushless Pilot Exciter  
4 pole, Rotating Field  
Air Cleaner  
Oil Pump  
Oil Drain Extension & S/O Valve  
Full Flow Oil Filter  
130 °C Maximum Standby Temperature Rise  
1 Bearing, Sealed  
Flexible Coupling  
Jacket Water Pump  
Full Amortisseur Windings  
Thermostats  
125% Rotor Balancing  
Blower Fan & Fan Drive  
Radiator - Unit Mounted  
Electric Starting Motor - 24V  
Governor – Electronic Isochronous  
Base - Formed Steel  
3-phase Voltage Sensing  
100% of Rated Load - One Step  
5% Maximum Total Harmonic Distortion  
//ꢀ  
SAE Flywheel & Bell Housing  
Charging Alternator - 24V  
Battery Box & Cables  
Flexible Fuel Connectors  
Flexible Exhaust Connection  
EPA Certied Engine  
Digital Control Panel(s)  
Digital Metering  
Engine Parameters  
Generator Protection Functions  
Engine Protection  
SAE J1939 Engine ECU Communications  
Windows®-Based Software  
Multilingual Capability  
//ꢀ  
Generator  
Remote Communications to RDP-110 Remote Annunciator  
16 Programmable Contact Inputs  
Up to 11 Contact Outputs  
NEMA MG1, IEEE and ANSI standards compliance for temperature rise  
and motor starting  
Self Ventilated and Drip-proof  
Superior Voltage Waveform  
UL Recognized, CSA Certied, CE Approved  
Event Recording  
Solid State, Volts-per-hertz Regulator  
±1% Voltage Regulation No load to full load  
IP 54 Front Panel Rating with Integrated Gasket  
NFPA110 Compatible  
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional congurations.  
/ // /  
3
GS200-6S  
APPLICATION DATA  
//ꢀ  
//ꢀ  
Engine  
Cooling - Radiator System  
Manufacturer  
Model  
Type  
Arrangement  
Displacement: L (in3)  
Bore: cm (in)  
Stroke: cm (in)  
Compression Ratio  
Rated RPM  
Engine Governor  
Maximum Power (NG): kWm (bhp)  
Maximum Power (LP): kWm (bhp)  
Speed Regulation  
Air Cleaner  
Doosan  
11.1L CAC  
4-Cycle  
6-Inline  
11.1 (673)  
12.3 (4.84)  
15.5 (6.1)  
10.5:1  
1,800  
Bosch  
225 (302)  
155 (208)  
±0.5%  
Ambient Capacity of Radiator: °C (°F)  
Maximum Restriction of Cooling Air, Intake,  
and Discharge Side of Rad.: kPa (in. H20)  
Water Pump Capacity: L/min (gpm)  
50 (122)*  
0.12 (0.5)  
310 (82)  
Heat Rejection to Coolant: kW (BTUM) 194.6 (11,071)  
Heat Radiated to Ambient: kW (BTUM)  
Fan Power: kW (hp)  
40.4 (2,295)  
10.4 (13.9)  
10.4 (13.9)  
* Installation of enclosures reduces the ambient capacity  
of the cooling system by 1 °C (1.8 °F). Gravity exhaust  
louvers reduce ambient capacity of the cooling system  
by an additional 3 °C (5.5 °F).  
Dry  
//ꢀ  
Air Requirements  
Liquid Capacity (Lubrication)  
Aspirating: *m3/min (SCFM)  
Air Flow Required for Rad.  
11.7 (400)  
//ꢀ  
Total Oil System: L (gal)  
Engine Jacket Water Capacity: L (gal)  
System Coolant Capacity: L (gal)  
28.5 (8)  
25 (5.5)  
149 (32.8)  
Cooled Unit: **m3/min (SCFM)  
Remote Cooled Applications;  
Air Flow Required for Dissipation  
of Radiated Gen-set Heat for a  
Max of 25 °F Rise: *m3/min (SCFM)  
631 (22,300)  
237 (8,365)  
//ꢀ  
Electrical  
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)  
Electric Volts DC  
Cold Cranking Amps Under -17.8 °C (0 °F)  
24  
1,050  
** At 0.25 kPa (1 in. H20) static pressure and  
52 °C (125 °F) at radiator  
//ꢀ  
Exhaust System  
//ꢀ  
Fuel Inlet  
Gas Temp. (Stack): °C (°F)  
Gas Volume at Stack  
694 (1,281)  
Fuel Supply Connection Size  
Fuel Supply Pressure: mm H20 (in. H20)  
2” NPT  
178–279 (7–11)  
Temp: m3/min (CFM)  
38.8 (1,371)  
2.5 (10.25)  
Maximum Allowable  
Back Pressure: kPa (in. H20)  
Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)  
//ꢀ  
NG  
LPG  
At 100% of Power Rating: m3/hr (ft3/hr) 59.9 (2,115)  
19.9 (704)  
17 (600)  
11.5 (404)  
At 75% of Power Rating: m3/hr (ft3/hr)  
At 50% of Power Rating: m3/hr (ft3/hr)  
46.7 (1,648)  
32.8 (1,157)  
/ // /  
4
GS200-6S  
WEIGHTS AND DIMENSIONS  
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.  
See website for unit specic template drawings.  
System  
Dimensions (LxWxH)  
Weight (dry)  
Open Power Unit (OPU)  
3,607 x 1,591 x 2,026 mm (142 x 62.6 x 79.75 in)  
3,096 kg (6,258 lb)  
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specic generator set.  
SOUND DATA  
Unit Type  
Standby Full Load (NG)  
Standby Full Load (LP)  
Level 0: Open Power Unit dB(A)  
86.3  
86.1  
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with innite exhaust.  
EMISSIONS DATA  
RATING DEFINITIONS AND CONDITIONS  
//ꢀ  
Fuel Type  
Natural Gas  
Liquid Propane  
THC + NOx  
2.24  
0.08  
CO  
0.26  
0.25  
Ambient capability factor at 984 ft (300 m). Consult your  
local MTU Onsite Energy Power Generation Distributor for  
other altitudes.  
Standby ratings apply to installations served by a reliable  
utility source. The standby rating is applicable to varying  
loads for the duration of a power outage. No overload  
capability for this rating. Ratings are in accordance with  
ISO 3046-1, BS 5514, AS 2789, and DIN 6271.  
Deration Factor:  
//ꢀ  
All units are in g/hp-hr and are EPA D2 cycle values.  
//ꢀ  
Production tolerances in engines and installed components  
can account for power variations of ±5%. Altitude, tempera-  
ture and excessive exhaust and intake restrictions should be  
applied to power calculations. Consult your local MTU Onsite  
Energy Power Generation Distributor for derations.  
Materials and specications subject to change without notice.  
C/F = Consult Factory/MTU Onsite Energy Distributor  
MTU Onsite Energy  
A Rolls-Royce Power Systems Brand  
www.mtuonsiteenergy.com  

相关型号:

GS2004HE

SURFACE MOUNT RECTIFIER
PANJIT

GS2005ELD

Rectifier Diode, Schottky, 1 Element, 0.5A, 20V V(RRM), Silicon,
GOOD-ARK

GS2008HE

SURFACE MOUNT RECTIFIER
PANJIT

GS2012

GS2053
ETC

GS2020-1

PHOTOTRANSISTOR | NPN | 825NM PEAK WAVELENGTH | 400U | TUBE
ETC

GS2020-11

PHOTOTRANSISTOR | NPN | 825NM PEAK WAVELENGTH | TUBE
ETC

GS2020-12

PHOTOTRANSISTOR | NPN | 825NM PEAK WAVELENGTH | TUBE
ETC

GS2020-2

PHOTOTRANSISTOR | NPN | 825NM PEAK WAVELENGTH | 400U | TUBE
ETC

GS2020-3

PHOTOTRANSISTOR | NPN | 825NM PEAK WAVELENGTH | TUBE
ETC