CFP-DI-300 [NI]

Digital Input Modules for Compact FieldPoint; 数字量输入模块的Compact FieldPoint的
CFP-DI-300
型号: CFP-DI-300
厂家: National Instruments    National Instruments
描述:

Digital Input Modules for Compact FieldPoint
数字量输入模块的Compact FieldPoint的

文件: 总5页 (文件大小:337K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Digital Input Modules for Compact FieldPoint  
NI cFP-DI-300, NI cFP-DI-301,  
NI cFP-DI-304, NI cFP-DI-330  
• 8-,16-, or 32-channel inputs  
• 24 VDC inputs  
• 4 to 250 VDC inputs  
• 15 to 250 VAC inputs (50/60 Hz AC)  
• 3 to 250 VAC inputs (1 kHz AC)  
• 2,300 Vrms bank isolation for transient  
overvoltage protection  
• Hot-swappable with autoconfiguration  
• -40 to 70 °C operating range  
Separate Ground  
Plane per Channel  
All Channel  
Update Rate1  
Additional  
Features  
Module  
Input Channels  
Input Ranges  
Input Type  
Compatibility Examples  
cFP-DI-300  
cFP-DI-301  
cFP-DI-304  
cFP-DI-330  
8
16  
32  
8
18 to 30 VDC  
18 to 30 VDC  
10 to 30 VDC  
5 to 48 VDC  
5 to 250 VAC  
Sinking  
Sinking  
Sinking  
24 VDC sourcing devices  
24 VDC sourcing devices  
24 VDC sourcing devices  
TTL, CMOS, 12 VDC, 24 VDC,  
48 VDC, 120/240 VAC/VDC  
1 kHz  
1 kHz  
1 kHz  
1 kHz  
Hysteresis  
Input current limiting  
(1.5 mA)  
Sinking or sourcing  
1The all-channel update rate refers to the time the module takes to sample all channels. The overall system update rate is affected by other factors, such as the aggregate module update rate and  
software loop rate. To calculate the system update rate, visit ni.com/info and enter “systemrate.”  
Each channel on the cFP-DI-330 includes circuitry that limits the total  
Overview  
current to 1.5 mA to prevent damaging the module. All channels on the  
National Instruments cFP-DI-3xx devices are versatile digital input  
cFP-DI-3xx modules feature LEDs that indicate the input state of each  
modules available for Compact FieldPoint systems. You can use these  
channel. The modules include an all-channel update rate of 1 kHz. Overall  
modules to monitor digital signals ranging from low-voltage levels up to  
data throughput depends on software loop speeds and network speeds.  
250 V. They are commonly used to monitor proximity and limit switches,  
pushbutton switches, thermostat outputs, relay closures, power circuits, Isolation  
and TTL devices. All the modules include onboard diagnostics to ensure  
The cFP-DI-3xx modules feature bank isolation with 2,300 Vrms of  
trouble-free installation and maintenance.  
breakdown isolation. In addition, the cFP-DI-330 provides double insulation  
for up to 250 Vrms of operational isolation. You can safely use Compact  
Digital Input Modules  
The cFP-DI-3xx modules provide built-in module-to-module isolation to  
FieldPoint with the cFP-CB-1 connector block in applications where  
hazardous voltages are present. These Compact FieldPoint modules do  
protect your Compact FieldPoint system and controller or communication  
not have channel-to-channel isolation.  
interface from high voltage levels. The cFP-DI-300, cFP-DI-301, and  
cFP-DI-304 modules use a common ground plane for all the input  
Field I/O Connections  
channels. Each channel on the cFP-DI-300, cFP-DI-301, and cFP-DI-304  
Compact FieldPoint modules include a built-in power distribution bus  
modules includes current-limiting circuitry to prevent module damage  
that provides multiple power connections on the module. A field-wired  
when connected directly to a 24 VDC source. The cFP-DI-330 uses eight  
power supply connected to the voltage (V) and common (C) terminals is  
optically isolated input channels so that each digital input has a separate  
internally connected to a power distribution bus that delivers additional  
ground plane, and you can use each channel with a different voltage  
breakout terminals for voltage supply (VSUP) and common (COM). These  
potential. Thus, you can connect one channel to a 5 VDC TTL signal and  
terminals offer a convenient way to distribute power to field devices  
another signal on the same cFP-DI-330 module to a 250 VAC line voltage.  
that require external power.  
Digital Input Modules for Compact FieldPoint  
+
5 to 250 V External  
Power Supply  
V
C
V
(Ch 0)  
SUP  
+
IN (Ch 0)  
A
Sinking-  
Output  
Device with  
External  
Power  
15 to 30 VDC  
External Power  
Supply  
Input  
Circuitry  
IN (Ch 0)  
B
V
C
COM (Ch 0)  
V
(Ch 0)  
SUP  
V
(Ch 1)  
SUP  
Sourcing  
Output  
Device with  
External  
Power  
Sourcing-  
Output  
Device with  
External  
Power  
IN (Ch 1)  
A
+
V
(Ch 0)  
IN  
Input  
Circuitry  
Input  
Circuitry  
IN (Ch 1)  
B
COM (Ch 0)  
COM (Ch 1)  
V
(Ch 2)  
SUP  
V
V
(Ch 1)  
SUP  
Sourcing  
Output  
Device  
Powered by  
cFP-DI-30x  
Sinking-  
Output  
IN (Ch 2)  
A
Input  
Circuitry  
Device  
Powered by  
cFP-DI-330  
(Ch 1)  
IN  
IN (Ch 2)  
B
Input  
Circuitry  
COM (Ch 2)  
COM (Ch 1)  
V
(Ch 3)  
SUP  
IN (Ch 3)  
A
V
(Ch n)  
SUP  
Sourcing-  
Output  
Device  
Input  
Circuitry  
IN (Ch 3)  
B
Powered by  
cFP-DI-330  
V
(Ch n)  
IN  
Input  
Circuitry  
COM (Ch 3)  
Switch  
COM (Ch n)  
V
(Ch n)  
SUP  
IN (Ch n)  
A
To next channel  
Input  
Circuitry  
Switch  
IN (Ch n)  
cFP-DI-300/301/304  
B
COM (Ch n)  
To next channel  
cFP-DI-330  
Ordering Information  
Wiring Schematics for the cFP-DI-3xx Modules  
NI cFP-DI-300 ......................................................................777318-300  
NI cFP-DI-301 ......................................................................777318-301  
NI cFP-DI-304 ......................................................................777318-304  
NI cFP-DI-330 ......................................................................777318-330  
Recommended Compact FieldPoint System Products  
NI cFP-2120 ......................................................................777317-2120  
NI cFP-BP-4............................................................................778617-04  
NI cFP-BP-8............................................................................778617-08  
NI cFP-CB-1............................................................................779618-01  
NI PS-5 power supply............................................................778805-90  
NI Developer Suite Professional Control Edition..................777906-03  
BUY NOW!  
For complete product specifications, pricing, and  
accessory information, call 800 813 3693 (U.S.) or go  
to ni.com/compactfieldpoint.  
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)  
2
Digital Input Modules for Compact FieldPoint  
Specifications  
Typical for -40 to 70 °C unless otherwise noted.  
Digital Input Channels  
cFP-DI-300, cFP-DI-330 ..........................................................  
8
cFP-DI-301.............................................................................. 16  
cFP-DI-304.............................................................................. 32  
Input Characteristics  
Input impedance  
cFP-DI-300, cFP-DI-301...................................................... 5 k  
cFP-DI-304.......................................................................... 30 kΩ  
Input current limiting cFP-DI-330........................................... 1.5 mA  
Input Voltages  
cFP-DI-300, cFP-DI-301, cFP-DI-304....................................... 0 to 30 VDC  
cFP-DI-330.............................................................................. 0 to 250 VDC or 0 to 250 VAC (50/60 Hz AC) or 0 to 250 VAC (1 kHz AC)  
Digital Logic Levels  
cFP-DI-300  
cFP-DI-301  
cFP-DI-304  
cFP-DI-330  
ON State  
1 VDC, 1 4 VDC, 15 VAC (50/60 Hz AC),  
VAC 3 VAC (1 kHz AC)  
OFF State ON State OFF State ON State OFF State ON State OFF State  
Input Voltage (V)  
Input Current (µA)  
<5  
>15  
<5  
>15  
5  
10  
1000  
3000  
1000  
3000  
150  
330  
Hysteresis (cFP-DI-304)  
Input voltage.......................................................................... 2 V min  
Input current........................................................................... 60 µA min  
Isolation Voltage  
cFP-DI-30x  
Channel-to-ground  
Continuous .................................................................... 250 Vrms  
Withstand...................................................................... 2,300 Vrms, 5 s max  
Channel-to-backplane  
Continuous .................................................................... 250 Vrms  
Withstand...................................................................... 2,300 Vrms, 5 s max  
Channel-to-channel ........................................................... None  
cFP-DI-330  
Maximum isolation voltage............................................... 250 Vrms, Installation Category II  
Transient overvoltage ............................................................ 2,300 Vrms  
Physical Characteristics  
LED indicators  
Power (green) .................................................................... Power on and self-test passed  
Ready (green)..................................................................... Module configured and ready  
<0..31>, <0..15>, or <0..7> (green) ....................................... Input state of each channel  
Dimensions ........................................................................... 127.0 by 65.9 by 23.9 mm (5.00 by 2.60 by 0.94 in.)  
Weight  
cFP-DI-300/301.................................................................. 100 g (3.6 oz)  
cFP-DI-330.......................................................................... 103 g (3.7 oz)  
cFP-DI-304.......................................................................... 193 g (6.81 oz)  
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)  
3
Digital Input Modules for Compact FieldPoint  
Power Requirements (from Network Module)  
cFP-DI-300.............................................................................. 185 mW  
cFP-DI-301.............................................................................. 325 mW  
cFP-DI-304.............................................................................. 1 W  
cFP-DI-330.............................................................................. 200 mW  
Environment  
Operating temperature .......................................................... -40 to 70 °C  
Storage temperature.............................................................. -55 to 85 °C  
Relative humidity................................................................... 10 to 90%, noncondensing  
Shock and Vibration  
Operating vibration, random (IEC 60068-2-64)...................... 10 to 500 Hz, 5 grms  
Operating vibration, sinusoidal (IEC 60068-2-6).................... 10 to 500 Hz, 5 g  
Operating shock (IEC 60068-2-27) ......................................... 50 g, 3 ms half sine, 18 shocks at 6 orientations;  
30 g, 11 ms half sine, 18 shocks at 6 orientations  
Safety and Compliance  
Safety  
This product is designed to meet the requirements of the following standards  
of safety for electrical equipment for measurement, control, and laboratory use:  
• IEC 61010-1, EN 61010-1  
• UL 61010-1, CSA 61010-1  
Note: For UL and other safety certifications, refer to the product label or visit ni.com/certification,  
search by model number or product line, and click the appropriate link in the Certification column.  
Electromagnetic Compatibility  
This product is designed to meet the requirements of the following standards  
of EMC for electrical equipment for measurement, control, and laboratory use:  
• EN 61326 EMC requirements; Minimum Immunity  
• EN 55011 Emissions; Group 1, Class A  
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A  
Note: For EMC compliance, operate this device according to  
product documentation.  
CE Compliance  
This product meets the essential requirements of applicable European Directives,  
as amended for CE marking, as follows:  
• 2006/95/EC; Low-Voltage Directive (safety)  
• 2004/108/EC; Electromagnetic Compatibility Directive (EMC)  
Note: Refer to the Declaration of Conformity (DoC) for this product for any  
additional regulatory compliance information. To obtain the DoC for this product,  
visit ni.com/certification, search by model number or product line, and click  
the appropriate link in the Certification column.  
Waste Electrical and Electronic Equipment (WEEE)  
EU Customers: At the end of their life cycle, all products must be  
sent to a WEEE recycling center. For more information about WEEE  
recycling centers and National Instruments WEEE initiatives,  
visit ni.com/environment/weee.htm.  
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)  
4
NI Services and Support  
NI has the services and support to meet  
Local Sales and Technical Support  
your needs around the globe and through  
the application life cycle – from planning  
and development through deployment  
and ongoing maintenance. We offer  
services and service levels to meet  
customer requirements in research,  
design, validation, and manufacturing.  
Visit ni.com/services.  
In offices worldwide, our staff is local to the country, giving you access  
to engineers who speak your language. NI delivers industry-leading  
technical support through online knowledge bases, our applications  
engineers, and access to 14,000 measurement and automation  
professionals within NI Developer Exchange forums. Find immediate  
answers to your questions at ni.com/support.  
SERVICE  
NEEDS  
We also offer service programs that provide automatic upgrades to  
your application development environment and higher levels of technical  
support. Visit ni.com/ssp.  
Training and Certification  
NI training is the fastest, most certain route to productivity with our  
products. NI training can shorten your learning curve, save development  
time, and reduce maintenance costs over the application life cycle. We  
schedule instructor-led courses in cities worldwide, or we can hold a  
course at your facility. We also offer a professional certification program  
Hardware Services  
NI Factory Installation Services  
NI Factory Installation Services (FIS) is the fastest and easiest way to  
use your PXI or PXI/SCXI combination systems right out of the box.  
that identifies individuals who have high levels of skill and knowledge on Trained NI technicians install the software and hardware and configure  
using NI products. Visit ni.com/training.  
the system to your specifications. NI extends the standard warranty by  
one year on hardware components (controllers, chassis, modules)  
purchased with FIS. To use FIS, simply configure your system online  
with ni.com/pxiadvisor.  
Professional Services  
Our NI Professional Services team is composed of NI applications  
and systems engineers and a worldwide National Instruments Alliance  
Partner program of more than 600 independent consultants and  
integrators. Services range  
Calibration Services  
NI recognizes the need to maintain properly calibrated devices for  
high-accuracy measurements. We provide manual calibration  
procedures, services to recalibrate your products, and automated  
calibration software specifically designed for use by metrology  
laboratories. Visit ni.com/calibration.  
from start-up assistance to  
turnkey system integration.  
Visit ni.com/alliance.  
OEM Support  
We offer design-in consulting and product integration assistance if you  
want to use our products for OEM applications. For information about  
special pricing and services for OEM customers, visit ni.com/oem.  
Repair and Extended Warranty  
NI provides complete repair services for our products. Express repair  
and advance replacement services are also available. We offer  
extended warranties to help you meet project life-cycle requirements.  
Visit ni.com/services.  
ni.com • 800 813 3693  
*351572A-01*  
351572A-01  
2007-9294-161-101-D  
National Instruments • info@ni.com  
©2008 National Instruments Corporation. All rights reserved. FieldPoint, National Instruments, National Instruments Alliance Partner, NI, ni.com, NI Developer Suite, and SCXI are  
trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner  
is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.  

相关型号:

CFP-DI-301

Digital Input Modules for Compact FieldPoint
NI

CFP-DI-304

Digital Input Modules for Compact FieldPoint
NI

CFP-DI-330

Digital Input Modules for Compact FieldPoint
NI

CFP-DO-400

8 or 16 digital outputs/Fused outputs for short circuit protection cFP-DO-410
NI

CFP-RLY-421

Relay Modules for Compact FieldPoint
NI

CFP-RLY-423

Relay Modules for Compact FieldPoint
NI

CFP-RTD-122

Thermocouple and RTD Modules for Compact FieldPoint
NI

CFP-RTD-124

Thermocouple and RTD Modules for Compact FieldPoint
NI

CFP-TC-120

Thermocouple and RTD Modules for Compact FieldPoint
NI

CFP-TC-125

Thermocouple and RTD Modules for Compact FieldPoint
NI

CFP018-3R0

DC to DC Converters Distributed Power Supplies for Systems, Insulation Type
TDK

CFP025-3R0

DC to DC Converters Distributed Power Supplies for Systems, Insulation Type
TDK