C J 1 S Y S T E M P O W E R A N D E X P A N S I O N  
Power and Expansion Selection  
This section provides tools to calculate the CJ1 system current consumption total needed to select  
the power supply. When the number of modules or power requirements exceeds the capability of the  
power supplies available, I/O expansion racks solve the problem. If the number of modules per rack  
exceeds 10 or the current consumption is greater than the capacity of the power supply units, use the  
CPU and expansion rack configuration.  
What is the basic configuration?  
A CJ1 system consists of a power supply, a CPU, and up to 10 basic I/O, special I/O and  
CPU bus units, and an end cover. See page B-109.  
What goes on expansion I/O racks?  
The expansion I/O rack contains a power supply, an I/O interface module and the remaining  
I/O modules. Each expansion rack requires a power supply, the I/O interface module and up  
to 10 more modules.  
Where are ratings to calculate overall current consumption?  
All the current consumption ratings for the CPU, basic I/O, special I/O and CPU bus units  
are collected in the tables on pages B-110 to B-111.  
Which power supply is right?  
Compare the current consumption total of basic I/O, special I/O, and CPU bus units to  
determine which power supply to use.  
Input Voltage  
100 to 240 VAC  
24 VDC  
Output rating  
5 A, 5 VDC with 2 A RUN output  
25 W max.  
2.8 A, 5 VDC  
14 W max.  
CJ1W-PA202  
B-110  
5 A, 5 VDC  
25 W max.  
CJ1W-PD025  
B-110  
Output capacity  
Power supply model  
See page  
CJ1W-PA205R  
B-110  
Note: If more than 10 modules are required or the current consumption exceeds the output  
capacity of the power supplies, go to page B-109 for configuration of I/O expansion racks.  
The same power supply units can be used for both CPU and I/O expansion racks.  
How many expansion I/O racks can be used?  
Depending on the CPU chosen, the system can be expanded with up to three additional racks of  
basic I/O, special I/O and CPU bus units.  
40  
3
20  
1
Maximum I/O modules  
per CPU  
30  
2
10  
0
10  
0
Maximum I/O expansion  
racks per CPU  
CJ1G-CPU44H  
CJ1G-CPU45H  
CJ1H-CPU65H  
CJ1H-CPU66H  
CJ1M-CPU13  
CJ1M-CPU23  
CPU models  
CJ1G-CPU42H  
CJ1G-CPU43H  
CJ1M-CPU12  
CJ1M-CPU22  
CJ1M-CPU11  
CJ1M-CPU21  
Note: Order one CJ1W-IC101 I/O control module for the CPU rack and one CJ1W-II101 I/O  
interface module for each I/O expansion rack. Connect the modules with a cable of  
the appropriate length. Second and third I/O expansion racks connect between I/O  
interface modules. See page B-117 for details.  
B-108  
System Power and Expansion  
System Configuration  
J Basic Configuration  
A CJ1 Series basic configuration consists of a CPU, Power Supply Unit, Basic I/O Modules, Special I/O Modules, CPU  
Bus Modules, and an End Cover. Add up the current consumption of all the modules and the CPU according to the  
formula on the following page and then select the Power Supply Unit right for the application.  
Configuration Modules  
Basic Configuration  
(Basic I/O Modules,  
Special I/O Modules,  
Power  
Supply  
Unit  
CPU Bus Modules)  
CPU  
End Cover  
J CPU and Expansion Racks  
If the number of modules per rack exceeds 10 or the current consumption is greater than the capacity of the Power Supply  
Units, use the CPU and Expansion Rack configuration. This divides the load from the modules across two Power Supply  
Units. To ensure communication and automatic channel assignment in programming, order an I/O Control Module for the  
CPU Rack and an I/O Interface Module on each Expansion Rack.  
Configuration Modules  
CPU Rack  
(Basic I/O Modules,  
Special I/O Modules,  
Power  
Supply  
Unit  
CPU Bus Modules)  
I/O Control Module  
CPU  
End Cover  
Memory Card  
Configuration Modules  
(Basic I/O Modules,  
Special I/O Modules,  
CPU Bus Modules)  
Expansion Rack  
(Up to 3 Expansion  
Racks Allowed)  
Power  
Supply  
Unit  
I/O Interface Module  
End Cover  
I/O Connecting Cable  
B-109  
Programmable Controller CJ1  
System Power and Expansion  
Current Consumption  
Calculate All Aspects of Current Consumption  
J Calculating Maximum Current Consumption  
A. Calculate Maximum Current Supply (See the table below.)  
Current required at 5 VDC by all Modules in column (A) Maximum current consumption shown in table  
Current required at 24 VDC by all Modules in column (B) Maximum current consumption shown in table  
Current required at 24 VDC for service power supply in column (C) Maximum current consumption shown in table  
B. Calculate Maximum Total Power Supply (See the table below.)  
A × 5 VDC + B × 24 VDC + C × 24 VDC Maximum total power consumption shown in column (D)  
The amount of current/power that can be supplied to the Modules mounted in a Rack is limited by the capacity of the  
Power Supply Unit.  
Design the system so that the total current consumption of the Modules does not exceed the maximum current for  
each voltage group and the total power consumption does not exceed the maximum for the Power Supply Unit.  
Reference Table for Maximum Current Consumption  
The following table shows the maximum currents and power that can be supplied by Power Supply Units on CPU Racks  
and Expansion Racks.  
Power Supply Unit  
Maximum current consumption  
(D) Maximum total  
power consumption  
(A) 5-V group  
(B) 24-V group  
(C) 24-V group  
relay driver power supply  
0.8 A  
service power supply  
CJ1W-PA205R  
CJ1W-PA202  
CJ1W-PD025  
5.0 A  
2.8 A  
5.0 A  
None  
None  
None  
25 W  
14 W  
25 W  
0.4 A  
0.8 A  
Note:1. When calculating current/power consumption in a CPU Rack — be sure to include the power required by the  
CPU itself. When expanding the configuration, be sure to include the power required by the I/O Control Module.  
2. When calculating current/power consumption in an Expansion Rack — be sure to include the power required by  
the I/O Interface Module itself.  
J Example Calculations  
In this example, the following modules are mounted to a CJ1 Series CPU Rack with a CJ1W-PA205R Power Supply Unit.  
Module  
Model  
Quantity  
5 VDC  
24 VDC  
CPU  
CJ1G-CPU45  
CJ1W-IC101  
CJ1W-ID211  
CJ1W-ID231  
CJ1W-OC201  
1
1
2
2
2
1
1
0.910 A  
0.020 A  
0.080 A  
0.090 A  
0.090 A  
0.120 A  
0.350 A  
I/O Control Module  
Input Modules  
Output Modules  
0.048 A  
Special I/O Module CJ1W-DA041  
CPU Bus Module  
CJ1W-CLK21  
Calculation  
Current  
0.910+0.020+0.080×2+0.090×2+ 0.048 A×2  
0.090×2+0.120+0.350  
consumption  
Result  
1.92 A (5.0 A)  
0.096 A (0.8 A)  
0.096 A×24 V = 2.304 W  
Power consumption  
Calculation  
Result  
1.92×5 V = 9.60 W  
9.60+2.304 = 11.904 W (25 W)  
B-110  
Programmable Controller CJ1  
System Power and Expansion  
Current Consumption  
J Current Consumption Tables  
5-Volt Group: CPUs and Expansion Modules  
Special I/O Modules  
Module  
Model  
Current  
Category Module  
Model  
Current  
consumption  
at 5 V (A)  
consumption  
at 5 V (A)  
CJ1H-CPU66H/  
CJ1H-CPU65H  
0.99  
CPUs  
CJ1W-AD081-V1  
CJ1W-AD041-V1  
CJ1W-DA041  
CJ1W-DA021  
CJ1W-DA08V  
CJ1W-DA08C  
CJ1W-MAD42  
0.42  
0.42  
0.12  
0.12  
0.14  
0.14  
0.58  
Special  
I/O  
Analog Input  
(See note.)  
Modules  
(These values include  
current consumption for  
a Programming Console  
or CX-Programmer.)  
Modules  
CJ1G-CPU45H/  
CJ1G-CPU44H/  
CJ1G-CPU43H/  
CJ1G-CPU42H  
0.91  
Analog  
Output  
Modules  
(See note.)  
CJ1G-CPU45/  
CJ1G-CPU44  
0.91  
(See note.)  
Mixed  
Analog  
Module  
CJ1M-CPU11/  
CJ1M-CPU12  
CJ1M-CPU13  
0.58  
Temperature CJ1W-TCjjj  
Control  
0.25  
0.25  
CJ1M-CPU21/  
CJ1M-CPU22  
CJ1M-CPU23  
0.64  
Modules  
CJ1W-NC113/133  
CJ1W-NC213/233  
Position  
Control  
Modules  
I/O Control Module  
I/O Interface Module  
CJ1W-IC101  
CJ1W-II101  
CJ1W-TER01  
0.02  
0.13  
CJ1W-NC413/433  
CJ1W-CT021  
0.36  
0.28  
High-speed  
Counter  
End Cover  
(Included in CPU or  
Expansion Module.)  
Module  
CJ1W-V600C11  
CJ1W-V600C12  
0.26  
0.32  
Note: Add 0.15 A per Module when the NT-AL001-E is connected.  
ID Sensor  
Modules  
Basic I/O Modules and Interrupt Input Module  
Category Name  
Model  
Current  
CPU Bus Communication Modules  
consumption  
at 5 V (A)  
Category Name  
Model  
Current  
consumption  
at 5 V (A)  
CJ1W-ID201  
CJ1W-ID211  
CJ1W-ID231  
CJ1W-ID232  
CJ1W-ID261  
CJ1W-ID262  
CJ1W-IA111  
CJ1W-IA201  
CJ1W-OD201  
CJ1W-OD202  
CJ1W-OD203  
CJ1W-OD204  
CJ1W-OD211  
CJ1W-OD212  
CJ1W-OD231  
CJ1W-OD232  
CJ1W-OD233  
CJ1W-OD261  
CJ1W-OD262  
CJ1W-OD263  
CJ1W-OC201  
CJ1W-OC211  
CJ1W-OA201  
CJ1W-INT01  
CJ1W-IDP01  
CJ1W-MD231  
CJ1W-MD232  
CJ1W-MD233  
CJ1W-MD261  
CJ1W-MD263  
CJ1W-MD563  
0.06  
0.08  
0.09  
0.09  
0.09  
0.09  
0.09  
0.08  
0.09  
0.11  
0.10  
0.10  
0.10  
0.10  
0.14  
0.15  
0.14  
0.17  
0.17  
0.17  
0.09  
0.11  
0.22  
0.08  
0.08  
0.13  
0.13  
0.13  
0.14  
0.14  
0.19  
Basic  
DC Input  
Input  
Modules  
Ethernet  
CJ1W-ETN21  
CJ1W-CLK21-V1  
CJ1W-DRM21  
0.38  
0.35  
0.33  
CPU Bus  
Modules  
Modules  
Module  
Controller  
Link Module  
DeviceNet  
Module  
AC Input  
Modules  
0.40  
0.40  
ProfiBus-DP CJ1W-PRM21  
Module  
CJ1W-PRT21  
Basic  
Transistor  
Output  
Modules  
CJ1W-SCU41  
CJ1W-SCU21  
0.38  
Serial  
(See note.)  
Communica-  
tions Module  
0.28  
(See note.)  
CompoBus/S CJ1W-SRM21  
0.15  
Master  
Module  
Note: Add 0.15 A per Module when the NT-AL001-E is connected.  
24-Volt Group: CJ1 Series Basic Output Modules  
Category Name  
Model  
Current  
consumption  
at 24 V (A)  
Relay  
Triac  
CJ1W-OC201  
0.048  
Basic  
Relay Output  
Units  
Output  
Modules  
(0.006×No.  
of points ON)  
CJ1W-OC211  
0.096  
Interrupt Input Module  
Pulse Catch Module  
Mixed  
(0.006×No.  
of points ON)  
B-111  
Programmable Controller CJ1  
System Power, Expansion and I/O Allocations  
I/O Allocations  
J Overview  
In CJ1 Series PLCs, I/O memory is allocated based on  
the following: Basic I/O are automatically assigned words  
based on position in the rack. In contrast, for Communica-  
tions and Bus I/O, the user assigns the word allocations  
within set ranges.  
J Allocations to Basic I/O  
Module Groups  
Allocations to Expansion Racks  
I/O allocation to Basic I/O Modules continues from the CPU  
Rack to the Expansion Racks. Words are allocated from  
left to right, and each module is allocated as many words  
as it requires in word units— just like modules in the CPU  
Rack. A Rack’s first word setting can be changed to any  
word from CIO 0000 to CIO 9999.  
Allocated words in the CIO Area: CIO 0000 to CIO 0079  
Basic I/O Modules can be mounted to the CPU Rack and to  
the Expansion Racks.  
CPU Rack Allocations  
Basic I/O Modules on the CPU Rack are allocated words  
left to right (i.e., from the module nearest the CPU) starting  
from CIO 0000. Modules are allocated as many words as  
required in word units. Words can be reserved using  
CX-Programmer Software.  
Words allocated from the left.  
CIO  
0000  
0000  
CH  
Up to 10 modules  
can be mounted.  
CPU Rack  
CIO  
CPU Rack  
0000  
Words allocated from the left.  
Expansion Rack  
Words  
allocated  
in order  
from Rack  
nearest  
An example of : words allocated from the left.  
CPU Rack  
CPU Rack.  
IN  
IN  
IN  
OUT OUT  
16  
16  
32  
32  
64  
CIO  
CIO  
CIO  
CIO  
CIO  
0000 0001 0002 0004 0006  
to to to  
0003 0005 0009  
Expansion Rack  
Modules with between 1 and 16 I/O points are allocated 1  
word (16 bits), and modules having between 17 and 32 I/O  
points are allocated 2 words (32 bits). For example, 8-point  
Relay Modules are allocated 1 word, with bits 00 to 07  
actually allocated to the I/O points.  
B-112  
Programmable Controller CJ1  
System Power, Expansion and I/O Allocations  
I/O Allocations  
Special I/O Allocations for CompoBus/S  
J CompoBus/S and Special I/O  
Allocations  
Unit number  
Words allocated  
0
1
2
CIO 2000 to CIO 2009  
CIO 2010 to CIO 2019  
CIO 2020 to CIO 2029  
When allocating I/O in CPU memory, CompoBus/S is  
considered a Special I/O Module. These modules can be  
mounted to the CPU Rack and Expansion Racks. Each  
CompoBus/S Module is allocated ten words in the Special  
I/O Module Area (CIO 2000 to CIO 2959). Refer to the  
table provided to the right.  
15  
95  
CIO 2150 to CIO 2159  
Note: During I/O allocation to Basic I/O Modules, Special  
I/O Modules are ignored. (Slots containing Special  
I/O Modules are treated as empty slots.)  
CIO 2950 to CIO 2959  
Allocations for All Networking and  
Communications Modules — Except Special I/O  
J Allocations for All Networking and  
Communications Modules — Except  
CompoBus/S  
Unit number  
Words allocated  
0
1
2
CIO 1500 to CIO 1524  
CIO 1525 to CIO 1549  
CIO 1550 to CIO 1574  
Each CPU Bus Module is allocated 25 words in the CPU  
Bus Module Area (CIO 1500 to CIO 1899).  
CPU Bus Modules can be mounted to the CPU Rack or  
Expansion Racks.  
Each Module is allocated 25 words in the CPU Bus Module  
Area according to its unit number, as shown in the table to  
the right.  
15  
CIO 1875 to CIO 1899  
Note: CPU Bus Modules are ignored during I/O allocation  
to Basic I/O Modules. The same unit numbers can be  
used for Special I/O Modules and CPU Bus Modules.  
B-113  
Programmable Controller CJ1  
System Power and Expansion  
Power Supply Units  
J Features  
Select the Power Supply Unit to match the current con-  
sumption requirements of a Basic Configuration CJ1 Series  
system or a CPU Rack and Expansion Rack system.  
Choose 100-120 VAC/200-240 VAC or 24 VDC models.  
Power Supply Units  
CJ1W-PA205R  
CJ1W-PA202  
Separate RUN output on CJ1W-PA205R Power Supply  
Unit provides confirmation of operation for troubleshoot-  
ing and remote diagnostics.  
CJ1W-PD025  
J Specifications  
Item  
Specifications  
CJ1W-PA205R  
Power Supply Unit  
Supply voltage  
CJ1W-PA202  
CJ1W-PD025  
100 to 240 VAC (wide-range), 50/60 Hz  
85 to 264 VAC, 47 to 63 Hz  
24 VDC  
Operating voltage and  
frequency ranges  
19.2 to 28.2 VDC  
Power consumption  
100 VA max.  
50 VA max.  
50 W max.  
Inrush current  
(See note 3.)  
100 to 120-VAC input: 15 A/8 ms  
max. (with cold start at room  
temperature)  
100 to 120-VAC input: 20 A/8 ms At 24 VDC: 30 A/20 ms max. for  
max.(with cold start at room  
temperature)  
cold start at room temperature  
200 to 240-VAC input: 30 A/8 ms  
max. (at cold start under room  
temperature)  
200 to 240-VAC input: 40 A/8 ms  
max. (with cold start at room  
temperature)  
Output capacity  
Output terminal  
5.0 A, 5 VDC (including supply to  
the CPU);  
2.8 A, 5 VDC (including supply to 5.0 A, 5 VDC (including supply to  
the CPU); CPU);  
0.4 A, 24 VDC (total: 14 W max.) 0.8 A, 24 VDC;(total: 25 W max.)  
0.8 A, 24 VDC (total: 25 W max.)  
Not provided  
RUN output  
Contact configuration: SPST-NO  
Switching capacity:  
None provided  
(See note 2.)  
250 VAC, 2 A (resistive load)  
120 VAC, 0.5 A (inductive load)  
24 VDC, 2 A (resistive load)  
24 VDC, 2 A (inductive load)  
Insulation resistance  
(See note 1.)  
20 Mmin. (at 500 VDC) between AC external and GR terminals  
20 Mmin. (at 500 VDC) between  
DC external and GR terminals  
Dielectric strength  
(See note 1.)  
1,000 VAC 50/60 Hz for 1 min  
between DC external and GR  
terminals  
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals  
Leakage current: 10 mA max.  
1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals  
Leakage current: 10 mA max.  
Leakage current: 10 mA max.  
(This table continues on the next page.)  
Note: 1. Disconnect the Power Supply Unit’s LG terminal from the GR terminal when testing insulation and dielectric strength. Testing  
the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the  
CPU.  
2. Supported only when mounted to CPU Rack.  
3. These values are based on the condition that the Unit is cold-started at room temperature. Thermistor elements with current  
suppression characteristics are used in the inrush current limiting circuits provided in the power supply. The inrush current may  
exceed as much as twice these values if the ambient temperature is high or when the power supply is hot-started with insuffi-  
cient cooling down time because the thermistors are not sufficiently cooled down. When selecting fuses or breakers for external  
circuits, ensure a sufficient allowance for fuse or current detection characteristics.  
B-114  
Programmable Controller CJ1  
System Power and Expansion  
Power Supply Units  
Specifications (continued)  
Item  
Specifications  
Power Supply Unit  
Noise immunity  
Vibration resistance  
CJ1W-PA205R  
CJ1W-PA202  
CJ1W-PD025  
Conforms to IEC61000-4-4, 2 kV (power lines)  
2
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s in X, Y, and Z directions for  
80 minutes. (Time coefficient: 8 minutes ×coefficient factor 10 = total time 80 min.)  
2 2  
147 m/s , 3 times each in X, Y, and Z directions (Relay Output Module: 100 m/s )  
Shock resistance  
Operating temperature  
Operating humidity  
Atmosphere  
0 to 55_C  
10% to 90% (with no condensation)  
Must be free from corrosive gases.  
-20 to 75_C (excluding battery)  
Less than 100 Ω  
Storage temperature  
Grounding  
Enclosure  
Mounted in a panel.  
Item  
Specifications  
CJ1 Series CPU Rack  
dimensions  
Refer to Dimensions” in the Reference Section of this catalog  
Dimensions  
60 × 90 × 65 mm (W × H × D) power supply only, not including terminal block)  
Safety measures  
Conforms to cULus and EC directives.  
B-115  
Programmable Controller CJ1  
System Power and Expansion  
CPU Rack Configuration Checklist  
J CPU Rack Configuration  
Item  
Products  
Requirements  
CJ1 Series  
CPU Rack  
One of each Module required for every CPU Rack.  
CJ1 Series CPU  
(Provided with 1 End Cover as a  
standard accessory.)  
CJ1 Series Power Supply Unit  
CJ1 Series Basic I/O Module  
CJ1 Series Special I/O Module  
CJ1 Series CPU Bus Module  
End Cover (CJ1W-TER01)  
Total number of Modules: 10 Modules max.  
(Mounting 11 or more Modules will result in a fatal error.)  
Required on the right-hand side of CJ1 Series CPU Racks. (One End Cover is  
provided with each CPU as a standard accessory. Not mounting an End Cover on  
the right-hand side of the CPU Rack will result in a fatal error.)  
Memory Card  
Install as required.  
I/O Control Module  
(CJ1W-IC101)  
Required for connection to CJ1 Series Expansion Racks. Connect to the right-hand  
side of the CPU Rack.  
I/O Connecting Cable  
Required for connecting CPU Racks to Expansion Racks.  
J Products Used in CPU Racks  
Item  
Model  
Specifications  
CJ1 Series  
CPUs  
CJ1H-CPU66H I/O bits: 2,560 (3 Expansion Racks), program capacity: 120K steps, LD execution time: 0.02 µs, Data  
Memory: 256K words (DM: 32K words, EM: 32K words x 7 banks)  
CJ1H-CPU65H I/O bits: 2,560 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.02 µs, Data  
Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)  
CJ1G-CPU45H I/O bits: 1,280 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.04 µs, Data  
Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)  
CJ1G-CPU44H I/O bits: 1,280 (3 Expansion Racks), program capacity: 30K steps, LD execution time: 0.04 µs, Data  
Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)  
CJ1G-CPU43H I/O bits: 960 (2 Expansion Racks), program capacity: 20K steps, LD execution time: 0.04 µs,  
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)  
CJ1G-CPU42H I/O bits: 960 (2 Expansion Racks), program capacity: 10K steps, LD execution time: 0.04 µs,  
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)  
CJ1M-CPU23  
CJ1M-CPU22  
CJ1M-CPU21  
CJ1M-CPU13  
CJ1M-CPU12  
CJ1M-CPU11  
I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs,  
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs  
I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs,  
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs  
I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs,  
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs  
I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs,  
Data Memory: 32K words, (No EM)  
I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs,  
Data Memory: 32K words, (No EM)  
I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs,  
Data Memory: 32K words, (No EM)  
CPM2A-BAT01 Can also be used with CPM2A and CQM1H PLCs.  
This battery cannot be used for CS1 Series PLCs.  
Battery Set  
CJ1W-BAT01  
Can be used with CJ1M only.  
This battery cannot be used for CJ1G/H or CS1 Series PLCs.  
CJ1W-PA205R 100 to 240 VAC (with RUN output); output capacity: 5 A, 5 VDC  
CJ1 Series  
Power  
CJ1W-PA202  
CJ1W-PD025  
CJ1W-IC101  
100 to 240 VAC; output capacity: 2.8 A, 5 VDC  
24 VDC; Output capacity: 5 A, 5 VDC  
Supply  
I/O Control  
Module  
Used to connect a CJ1 Series Expansion Rack to a CJ1 Series CPU Rack. Connect to the right-hand  
side of the CPU. Connect to an I/O Interface Module mounted on a CJ1 Series Expansion Rack using  
a CS1/CJ1 Series Connecting Cable.  
End Cover  
CJ1W-TER01  
Required on the right-hand side of CJ1 Series CPU Racks. (Not mounting an End Cover on the  
right-hand side of the CPU Rack will result in a fatal error.)  
Note: One is provided with CPUs and I/O Interface Modules as a standard accessory.  
PFP-50N  
PFP-100N  
PFP-100N2  
PFP-M  
Length: 50 cm; height: 7.3 mm  
Length: 1 m; height: 7.3 mm  
Length: 1 m; height: 16 mm  
Din Track  
and  
Accessories  
There are two locking clips provided with each CPU and I/O Interface Module as standard accessories  
to secure the Modules on the DIN Track.  
B-116  
Programmable Controller CJ1  
System Power and Expansion  
Expansion Rack Configuration Checklist  
J Expansion Rack Configuration  
CJ1 Series Expansion Racks can be connected to CJ1 Series CPU Racks or other CJ1 Series Expansion Racks.  
Rack  
Configuration  
Requirements  
CJ1 Series Expansion  
Rack  
One of each Module required for every Expansion Rack. Connect  
the I/O Interface Module to the right of the Power Supply Unit.  
CJ1 Series Power Supply Unit  
I/O Interface Module CJ1W-II101  
(Provided with 1 End Cover as a  
standard accessory.)  
Note: An I/O Control Module is required for each CJ1 Series  
Expansion Rack.  
Total number of Modules: 10 Modules max.  
CJ1 Series Basic I/O Module  
CJ1 Series Special I/O Module  
CJ1 Series CPU Bus Module  
(Mounting 11 or more Modules will result in a fatal error.)  
CS1/CJ1 Series I/O Connecting Cable Required to connect I/O Control Modules to I/O Interface  
Modules.  
Note: The total length of CS1/CJ1 Series I/O Connecting Cable  
used in the system must not exceed 12 m. Correct  
operation is not ensured if the total cable length exceeds  
12 m.  
J Capacity Overview  
CPU Models  
Maximum I/O Modules per CPU  
Maximum I/O Expansion Racks per CPU  
(depending on power supply capacity)  
(depending on power supply capacity)  
20  
30  
40  
1
2
3
CJ1M-CPU13  
CJ1M-CPU23  
CJ1G-CPU42H  
CJ1G-CPU43H  
CJ1G-CPU44H  
CJ1G-CPU45H  
CJ1H-CPU65H  
CJ1H-CPU66H  
J Products Used in Expansion Racks  
Item  
Model  
Specifications  
Cable  
Length  
CJ1 Series Power  
Supply Unit  
CJ1W-PA205R  
CJ1W-PA202  
CJ1W-PD025  
CJ1W-II101  
100 to 240 VAC (with RUN output), output capacity: 5 A, 5 VDC  
100 to 240 VAC, output capacity: 2.8 A, 5 VDC  
24 VDC, 5A, 5 VDC  
I/O Interface  
Module  
One is required for each CJ1 Series Expansion Rack. An End Cover is  
provided as a standard accessory. (Connect to an I/O Control Module on a  
CPU Rack or to another I/O Interface Module on an Expansion Rack using  
CS1/CJ1 Series Connecting Cable.)  
End Cover  
CJ1W-TER01  
Required for the right-hand side of CJ1 Series Expansion Racks. One is  
provided with I/O Interface Modules as a standard. (Not connecting an End  
Cover will result in a fatal error.)  
CS1W-CN313  
CS1W-CN713  
CS1W-CN223  
CS1W-CN323  
CS1W-CN523  
CS1W-CN133  
CS1W-CN133-B2  
0.3 m  
0.7 m  
2 m  
CJ1/CS1 Series  
I/O Connecting  
Cables  
Used to connect I/O Interface Modules (CJ1W-II101) to I/O Control Modules  
(CJ1W-IC101) or to other I/O Interface Modules.  
3 m  
5 m  
10 m  
12 m  
Special Ordering Information  
Order one CJ1W-IC101 I/O Control Module for the CPU rack and one CJ1W-II101 I/O Interface Module for each I/O  
Expansion rack.  
Connect the modules with a cable of the appropriate length.  
The second and third I/O Expansion racks connect between I/O Interface Modules.  
B-117  
Programmable Controller CJ1  

相关型号:

CJ1M-CPU22

CJ1 SYSTEM POWER AND EXPANSION
OMRON

CJ1M-CPU23

CJ1 SYSTEM POWER AND EXPANSION
OMRON

CJ1W-AD041-V1

CJ1 Programmable Controllers
OMRON

CJ1W-AD04U

CJ-series Process Analog I/O Unit
OMRON

CJ1W-AD081-V1

CJ1 Programmable Controllers
OMRON

CJ1W-ADjjj

Reference Information
OMRON

CJ1W-B7A04

CJ1 Ordering Guide
OMRON

CJ1W-B7A14

CJ1 Ordering Guide
OMRON

CJ1W-B7A22

CJ1 Ordering Guide
OMRON

CJ1W-BAT01

CJ1 Ordering Guide
OMRON

CJ1W-CIF11

CJ1 Ordering Guide
OMRON

CJ1W-CLK

SYSMAC CJ-series Controller Link Units
OMRON