CJ1M-CPU21 [OMRON]
CJ1 SYSTEM POWER AND EXPANSION; CJ1系统功耗,扩展型号: | CJ1M-CPU21 |
厂家: | OMRON ELECTRONICS LLC |
描述: | CJ1 SYSTEM POWER AND EXPANSION |
文件: | 总10页 (文件大小:487K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
C J 1 S Y S T E M P O W E R A N D E X P A N S I O N
Power and Expansion Selection
This section provides tools to calculate the CJ1 system current consumption total needed to select
the power supply. When the number of modules or power requirements exceeds the capability of the
power supplies available, I/O expansion racks solve the problem. If the number of modules per rack
exceeds 10 or the current consumption is greater than the capacity of the power supply units, use the
CPU and expansion rack configuration.
What is the basic configuration?
A CJ1 system consists of a power supply, a CPU, and up to 10 basic I/O, special I/O and
CPU bus units, and an end cover. See page B-109.
What goes on expansion I/O racks?
The expansion I/O rack contains a power supply, an I/O interface module and the remaining
I/O modules. Each expansion rack requires a power supply, the I/O interface module and up
to 10 more modules.
Where are ratings to calculate overall current consumption?
All the current consumption ratings for the CPU, basic I/O, special I/O and CPU bus units
are collected in the tables on pages B-110 to B-111.
Which power supply is right?
Compare the current consumption total of basic I/O, special I/O, and CPU bus units to
determine which power supply to use.
Input Voltage
100 to 240 VAC
24 VDC
Output rating
5 A, 5 VDC with 2 A RUN output
25 W max.
2.8 A, 5 VDC
14 W max.
CJ1W-PA202
B-110
5 A, 5 VDC
25 W max.
CJ1W-PD025
B-110
Output capacity
Power supply model
See page
CJ1W-PA205R
B-110
Note: If more than 10 modules are required or the current consumption exceeds the output
capacity of the power supplies, go to page B-109 for configuration of I/O expansion racks.
The same power supply units can be used for both CPU and I/O expansion racks.
How many expansion I/O racks can be used?
Depending on the CPU chosen, the system can be expanded with up to three additional racks of
basic I/O, special I/O and CPU bus units.
40
3
20
1
Maximum I/O modules
per CPU
30
2
10
0
10
0
Maximum I/O expansion
racks per CPU
CJ1G-CPU44H
CJ1G-CPU45H
CJ1H-CPU65H
CJ1H-CPU66H
CJ1M-CPU13
CJ1M-CPU23
CPU models
CJ1G-CPU42H
CJ1G-CPU43H
CJ1M-CPU12
CJ1M-CPU22
CJ1M-CPU11
CJ1M-CPU21
Note: Order one CJ1W-IC101 I/O control module for the CPU rack and one CJ1W-II101 I/O
interface module for each I/O expansion rack. Connect the modules with a cable of
the appropriate length. Second and third I/O expansion racks connect between I/O
interface modules. See page B-117 for details.
B-108
System Power and Expansion
System Configuration
J Basic Configuration
A CJ1 Series basic configuration consists of a CPU, Power Supply Unit, Basic I/O Modules, Special I/O Modules, CPU
Bus Modules, and an End Cover. Add up the current consumption of all the modules and the CPU according to the
formula on the following page and then select the Power Supply Unit right for the application.
Configuration Modules
Basic Configuration
(Basic I/O Modules,
Special I/O Modules,
Power
Supply
Unit
CPU Bus Modules)
CPU
End Cover
J CPU and Expansion Racks
If the number of modules per rack exceeds 10 or the current consumption is greater than the capacity of the Power Supply
Units, use the CPU and Expansion Rack configuration. This divides the load from the modules across two Power Supply
Units. To ensure communication and automatic channel assignment in programming, order an I/O Control Module for the
CPU Rack and an I/O Interface Module on each Expansion Rack.
Configuration Modules
CPU Rack
(Basic I/O Modules,
Special I/O Modules,
Power
Supply
Unit
CPU Bus Modules)
I/O Control Module
CPU
End Cover
Memory Card
Configuration Modules
(Basic I/O Modules,
Special I/O Modules,
CPU Bus Modules)
Expansion Rack
(Up to 3 Expansion
Racks Allowed)
Power
Supply
Unit
I/O Interface Module
End Cover
I/O Connecting Cable
B-109
Programmable Controller CJ1
System Power and Expansion
Current Consumption
Calculate All Aspects of Current Consumption
J Calculating Maximum Current Consumption
A. Calculate Maximum Current Supply (See the table below.)
•
•
•
Current required at 5 VDC by all Modules in column (A) ≤ Maximum current consumption shown in table
Current required at 24 VDC by all Modules in column (B) ≤ Maximum current consumption shown in table
Current required at 24 VDC for service power supply in column (C) ≤ Maximum current consumption shown in table
B. Calculate Maximum Total Power Supply (See the table below.)
•
•
A × 5 VDC + B × 24 VDC + C × 24 VDC ≤ Maximum total power consumption shown in column (D)
The amount of current/power that can be supplied to the Modules mounted in a Rack is limited by the capacity of the
Power Supply Unit.
•
Design the system so that the total current consumption of the Modules does not exceed the maximum current for
each voltage group and the total power consumption does not exceed the maximum for the Power Supply Unit.
Reference Table for Maximum Current Consumption
The following table shows the maximum currents and power that can be supplied by Power Supply Units on CPU Racks
and Expansion Racks.
Power Supply Unit
Maximum current consumption
(D) Maximum total
power consumption
(A) 5-V group
(B) 24-V group
(C) 24-V group
relay driver power supply
0.8 A
service power supply
CJ1W-PA205R
CJ1W-PA202
CJ1W-PD025
5.0 A
2.8 A
5.0 A
None
None
None
25 W
14 W
25 W
0.4 A
0.8 A
Note:1. When calculating current/power consumption in a CPU Rack — be sure to include the power required by the
CPU itself. When expanding the configuration, be sure to include the power required by the I/O Control Module.
2. When calculating current/power consumption in an Expansion Rack — be sure to include the power required by
the I/O Interface Module itself.
J Example Calculations
In this example, the following modules are mounted to a CJ1 Series CPU Rack with a CJ1W-PA205R Power Supply Unit.
Module
Model
Quantity
5 VDC
24 VDC
CPU
CJ1G-CPU45
CJ1W-IC101
CJ1W-ID211
CJ1W-ID231
CJ1W-OC201
1
1
2
2
2
1
1
0.910 A
0.020 A
0.080 A
0.090 A
0.090 A
0.120 A
0.350 A
—
I/O Control Module
Input Modules
—
—
—
Output Modules
0.048 A
—
Special I/O Module CJ1W-DA041
CPU Bus Module
CJ1W-CLK21
Calculation
—
Current
0.910+0.020+0.080×2+0.090×2+ 0.048 A×2
0.090×2+0.120+0.350
consumption
Result
1.92 A (≦5.0 A)
0.096 A (≦0.8 A)
0.096 A×24 V = 2.304 W
Power consumption
Calculation
Result
1.92×5 V = 9.60 W
9.60+2.304 = 11.904 W (≦25 W)
B-110
Programmable Controller CJ1
System Power and Expansion
Current Consumption
J Current Consumption Tables
5-Volt Group: CPUs and Expansion Modules
Special I/O Modules
Module
Model
Current
Category Module
Model
Current
consumption
at 5 V (A)
consumption
at 5 V (A)
CJ1H-CPU66H/
CJ1H-CPU65H
0.99
CPUs
CJ1W-AD081-V1
CJ1W-AD041-V1
CJ1W-DA041
CJ1W-DA021
CJ1W-DA08V
CJ1W-DA08C
CJ1W-MAD42
0.42
0.42
0.12
0.12
0.14
0.14
0.58
Special
I/O
Analog Input
(See note.)
Modules
(These values include
current consumption for
a Programming Console
or CX-Programmer.)
Modules
CJ1G-CPU45H/
CJ1G-CPU44H/
CJ1G-CPU43H/
CJ1G-CPU42H
0.91
Analog
Output
Modules
(See note.)
CJ1G-CPU45/
CJ1G-CPU44
0.91
(See note.)
Mixed
Analog
Module
CJ1M-CPU11/
CJ1M-CPU12
CJ1M-CPU13
0.58
Temperature CJ1W-TCjjj
Control
0.25
0.25
CJ1M-CPU21/
CJ1M-CPU22
CJ1M-CPU23
0.64
Modules
CJ1W-NC113/133
CJ1W-NC213/233
Position
Control
Modules
I/O Control Module
I/O Interface Module
CJ1W-IC101
CJ1W-II101
CJ1W-TER01
0.02
0.13
—
CJ1W-NC413/433
CJ1W-CT021
0.36
0.28
High-speed
Counter
End Cover
(Included in CPU or
Expansion Module.)
Module
CJ1W-V600C11
CJ1W-V600C12
0.26
0.32
Note: Add 0.15 A per Module when the NT-AL001-E is connected.
ID Sensor
Modules
Basic I/O Modules and Interrupt Input Module
Category Name
Model
Current
CPU Bus Communication Modules
consumption
at 5 V (A)
Category Name
Model
Current
consumption
at 5 V (A)
CJ1W-ID201
CJ1W-ID211
CJ1W-ID231
CJ1W-ID232
CJ1W-ID261
CJ1W-ID262
CJ1W-IA111
CJ1W-IA201
CJ1W-OD201
CJ1W-OD202
CJ1W-OD203
CJ1W-OD204
CJ1W-OD211
CJ1W-OD212
CJ1W-OD231
CJ1W-OD232
CJ1W-OD233
CJ1W-OD261
CJ1W-OD262
CJ1W-OD263
CJ1W-OC201
CJ1W-OC211
CJ1W-OA201
CJ1W-INT01
CJ1W-IDP01
CJ1W-MD231
CJ1W-MD232
CJ1W-MD233
CJ1W-MD261
CJ1W-MD263
CJ1W-MD563
0.06
0.08
0.09
0.09
0.09
0.09
0.09
0.08
0.09
0.11
0.10
0.10
0.10
0.10
0.14
0.15
0.14
0.17
0.17
0.17
0.09
0.11
0.22
0.08
0.08
0.13
0.13
0.13
0.14
0.14
0.19
Basic
DC Input
Input
Modules
Ethernet
CJ1W-ETN21
CJ1W-CLK21-V1
CJ1W-DRM21
0.38
0.35
0.33
CPU Bus
Modules
Modules
Module
Controller
Link Module
DeviceNet
Module
AC Input
Modules
0.40
0.40
ProfiBus-DP CJ1W-PRM21
Module
CJ1W-PRT21
Basic
Transistor
Output
Modules
CJ1W-SCU41
CJ1W-SCU21
0.38
Serial
(See note.)
Communica-
tions Module
0.28
(See note.)
CompoBus/S CJ1W-SRM21
0.15
Master
Module
Note: Add 0.15 A per Module when the NT-AL001-E is connected.
24-Volt Group: CJ1 Series Basic Output Modules
Category Name
Model
Current
consumption
at 24 V (A)
Relay
Triac
CJ1W-OC201
0.048
Basic
Relay Output
Units
Output
Modules
(0.006×No.
of points ON)
CJ1W-OC211
0.096
Interrupt Input Module
Pulse Catch Module
Mixed
(0.006×No.
of points ON)
B-111
Programmable Controller CJ1
System Power, Expansion and I/O Allocations
I/O Allocations
J Overview
In CJ1 Series PLCs, I/O memory is allocated based on
the following: Basic I/O are automatically assigned words
based on position in the rack. In contrast, for Communica-
tions and Bus I/O, the user assigns the word allocations
within set ranges.
J Allocations to Basic I/O
Module Groups
Allocations to Expansion Racks
I/O allocation to Basic I/O Modules continues from the CPU
Rack to the Expansion Racks. Words are allocated from
left to right, and each module is allocated as many words
as it requires in word units— just like modules in the CPU
Rack. A Rack’s first word setting can be changed to any
word from CIO 0000 to CIO 9999.
Allocated words in the CIO Area: CIO 0000 to CIO 0079
Basic I/O Modules can be mounted to the CPU Rack and to
the Expansion Racks.
CPU Rack Allocations
Basic I/O Modules on the CPU Rack are allocated words
left to right (i.e., from the module nearest the CPU) starting
from CIO 0000. Modules are allocated as many words as
required in word units. Words can be reserved using
CX-Programmer Software.
Words allocated from the left.
CIO
0000
0000
CH
Up to 10 modules
can be mounted.
CPU Rack
CIO
CPU Rack
0000
Words allocated from the left.
Expansion Rack
Words
allocated
in order
from Rack
nearest
An example of : words allocated from the left.
CPU Rack
CPU Rack.
IN
IN
IN
OUT OUT
16
16
32
32
64
CIO
CIO
CIO
CIO
CIO
0000 0001 0002 0004 0006
to to to
0003 0005 0009
Expansion Rack
Modules with between 1 and 16 I/O points are allocated 1
word (16 bits), and modules having between 17 and 32 I/O
points are allocated 2 words (32 bits). For example, 8-point
Relay Modules are allocated 1 word, with bits 00 to 07
actually allocated to the I/O points.
B-112
Programmable Controller CJ1
System Power, Expansion and I/O Allocations
I/O Allocations
Special I/O Allocations for CompoBus/S
J CompoBus/S and Special I/O
Allocations
Unit number
Words allocated
0
1
2
CIO 2000 to CIO 2009
CIO 2010 to CIO 2019
CIO 2020 to CIO 2029
When allocating I/O in CPU memory, CompoBus/S is
considered a Special I/O Module. These modules can be
mounted to the CPU Rack and Expansion Racks. Each
CompoBus/S Module is allocated ten words in the Special
I/O Module Area (CIO 2000 to CIO 2959). Refer to the
table provided to the right.
15
95
CIO 2150 to CIO 2159
Note: During I/O allocation to Basic I/O Modules, Special
I/O Modules are ignored. (Slots containing Special
I/O Modules are treated as empty slots.)
CIO 2950 to CIO 2959
Allocations for All Networking and
Communications Modules — Except Special I/O
J Allocations for All Networking and
Communications Modules — Except
CompoBus/S
Unit number
Words allocated
0
1
2
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
Each CPU Bus Module is allocated 25 words in the CPU
Bus Module Area (CIO 1500 to CIO 1899).
CPU Bus Modules can be mounted to the CPU Rack or
Expansion Racks.
Each Module is allocated 25 words in the CPU Bus Module
Area according to its unit number, as shown in the table to
the right.
15
CIO 1875 to CIO 1899
Note: CPU Bus Modules are ignored during I/O allocation
to Basic I/O Modules. The same unit numbers can be
used for Special I/O Modules and CPU Bus Modules.
B-113
Programmable Controller CJ1
System Power and Expansion
Power Supply Units
J Features
Select the Power Supply Unit to match the current con-
sumption requirements of a Basic Configuration CJ1 Series
system or a CPU Rack and Expansion Rack system.
•
•
Choose 100-120 VAC/200-240 VAC or 24 VDC models.
Power Supply Units
CJ1W-PA205R
CJ1W-PA202
Separate RUN output on CJ1W-PA205R Power Supply
Unit provides confirmation of operation for troubleshoot-
ing and remote diagnostics.
CJ1W-PD025
J Specifications
Item
Specifications
CJ1W-PA205R
Power Supply Unit
Supply voltage
CJ1W-PA202
CJ1W-PD025
100 to 240 VAC (wide-range), 50/60 Hz
85 to 264 VAC, 47 to 63 Hz
24 VDC
Operating voltage and
frequency ranges
19.2 to 28.2 VDC
Power consumption
100 VA max.
50 VA max.
50 W max.
Inrush current
(See note 3.)
100 to 120-VAC input: 15 A/8 ms
max. (with cold start at room
temperature)
100 to 120-VAC input: 20 A/8 ms At 24 VDC: 30 A/20 ms max. for
max.(with cold start at room
temperature)
cold start at room temperature
200 to 240-VAC input: 30 A/8 ms
max. (at cold start under room
temperature)
200 to 240-VAC input: 40 A/8 ms
max. (with cold start at room
temperature)
Output capacity
Output terminal
5.0 A, 5 VDC (including supply to
the CPU);
2.8 A, 5 VDC (including supply to 5.0 A, 5 VDC (including supply to
the CPU); CPU);
0.4 A, 24 VDC (total: 14 W max.) 0.8 A, 24 VDC;(total: 25 W max.)
0.8 A, 24 VDC (total: 25 W max.)
Not provided
RUN output
Contact configuration: SPST-NO
Switching capacity:
None provided
(See note 2.)
250 VAC, 2 A (resistive load)
120 VAC, 0.5 A (inductive load)
24 VDC, 2 A (resistive load)
24 VDC, 2 A (inductive load)
Insulation resistance
(See note 1.)
20 MΩ min. (at 500 VDC) between AC external and GR terminals
20 MΩ min. (at 500 VDC) between
DC external and GR terminals
Dielectric strength
(See note 1.)
1,000 VAC 50/60 Hz for 1 min
between DC external and GR
terminals
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals
Leakage current: 10 mA max.
1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals
Leakage current: 10 mA max.
Leakage current: 10 mA max.
(This table continues on the next page.)
Note: 1. Disconnect the Power Supply Unit’s LG terminal from the GR terminal when testing insulation and dielectric strength. Testing
the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the
CPU.
2. Supported only when mounted to CPU Rack.
3. These values are based on the condition that the Unit is cold-started at room temperature. Thermistor elements with current
suppression characteristics are used in the inrush current limiting circuits provided in the power supply. The inrush current may
exceed as much as twice these values if the ambient temperature is high or when the power supply is hot-started with insuffi-
cient cooling down time because the thermistors are not sufficiently cooled down. When selecting fuses or breakers for external
circuits, ensure a sufficient allowance for fuse or current detection characteristics.
B-114
Programmable Controller CJ1
System Power and Expansion
Power Supply Units
Specifications (continued)
Item
Specifications
Power Supply Unit
Noise immunity
Vibration resistance
CJ1W-PA205R
CJ1W-PA202
CJ1W-PD025
Conforms to IEC61000-4-4, 2 kV (power lines)
2
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s in X, Y, and Z directions for
80 minutes. (Time coefficient: 8 minutes ×coefficient factor 10 = total time 80 min.)
2 2
147 m/s , 3 times each in X, Y, and Z directions (Relay Output Module: 100 m/s )
Shock resistance
Operating temperature
Operating humidity
Atmosphere
0 to 55_C
10% to 90% (with no condensation)
Must be free from corrosive gases.
-20 to 75_C (excluding battery)
Less than 100 Ω
Storage temperature
Grounding
Enclosure
Mounted in a panel.
Item
Specifications
CJ1 Series CPU Rack
dimensions
Refer to “Dimensions” in the Reference Section of this catalog
Dimensions
60 × 90 × 65 mm (W × H × D) power supply only, not including terminal block)
Safety measures
Conforms to cULus and EC directives.
B-115
Programmable Controller CJ1
System Power and Expansion
CPU Rack Configuration Checklist
J CPU Rack Configuration
Item
Products
Requirements
CJ1 Series
CPU Rack
One of each Module required for every CPU Rack.
CJ1 Series CPU
(Provided with 1 End Cover as a
standard accessory.)
CJ1 Series Power Supply Unit
CJ1 Series Basic I/O Module
CJ1 Series Special I/O Module
CJ1 Series CPU Bus Module
End Cover (CJ1W-TER01)
Total number of Modules: 10 Modules max.
(Mounting 11 or more Modules will result in a fatal error.)
Required on the right-hand side of CJ1 Series CPU Racks. (One End Cover is
provided with each CPU as a standard accessory. Not mounting an End Cover on
the right-hand side of the CPU Rack will result in a fatal error.)
Memory Card
Install as required.
I/O Control Module
(CJ1W-IC101)
Required for connection to CJ1 Series Expansion Racks. Connect to the right-hand
side of the CPU Rack.
I/O Connecting Cable
Required for connecting CPU Racks to Expansion Racks.
J Products Used in CPU Racks
Item
Model
Specifications
CJ1 Series
CPUs
CJ1H-CPU66H I/O bits: 2,560 (3 Expansion Racks), program capacity: 120K steps, LD execution time: 0.02 µs, Data
Memory: 256K words (DM: 32K words, EM: 32K words x 7 banks)
CJ1H-CPU65H I/O bits: 2,560 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.02 µs, Data
Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)
CJ1G-CPU45H I/O bits: 1,280 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.04 µs, Data
Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)
CJ1G-CPU44H I/O bits: 1,280 (3 Expansion Racks), program capacity: 30K steps, LD execution time: 0.04 µs, Data
Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
CJ1G-CPU43H I/O bits: 960 (2 Expansion Racks), program capacity: 20K steps, LD execution time: 0.04 µs,
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
CJ1G-CPU42H I/O bits: 960 (2 Expansion Racks), program capacity: 10K steps, LD execution time: 0.04 µs,
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
CJ1M-CPU23
CJ1M-CPU22
CJ1M-CPU21
CJ1M-CPU13
CJ1M-CPU12
CJ1M-CPU11
I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs
I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs
I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs
I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM)
I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM)
I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs,
Data Memory: 32K words, (No EM)
CPM2A-BAT01 Can also be used with CPM2A and CQM1H PLCs.
This battery cannot be used for CS1 Series PLCs.
Battery Set
CJ1W-BAT01
Can be used with CJ1M only.
This battery cannot be used for CJ1G/H or CS1 Series PLCs.
CJ1W-PA205R 100 to 240 VAC (with RUN output); output capacity: 5 A, 5 VDC
CJ1 Series
Power
CJ1W-PA202
CJ1W-PD025
CJ1W-IC101
100 to 240 VAC; output capacity: 2.8 A, 5 VDC
24 VDC; Output capacity: 5 A, 5 VDC
Supply
I/O Control
Module
Used to connect a CJ1 Series Expansion Rack to a CJ1 Series CPU Rack. Connect to the right-hand
side of the CPU. Connect to an I/O Interface Module mounted on a CJ1 Series Expansion Rack using
a CS1/CJ1 Series Connecting Cable.
End Cover
CJ1W-TER01
Required on the right-hand side of CJ1 Series CPU Racks. (Not mounting an End Cover on the
right-hand side of the CPU Rack will result in a fatal error.)
Note: One is provided with CPUs and I/O Interface Modules as a standard accessory.
PFP-50N
PFP-100N
PFP-100N2
PFP-M
Length: 50 cm; height: 7.3 mm
Length: 1 m; height: 7.3 mm
Length: 1 m; height: 16 mm
Din Track
and
Accessories
There are two locking clips provided with each CPU and I/O Interface Module as standard accessories
to secure the Modules on the DIN Track.
B-116
Programmable Controller CJ1
System Power and Expansion
Expansion Rack Configuration Checklist
J Expansion Rack Configuration
CJ1 Series Expansion Racks can be connected to CJ1 Series CPU Racks or other CJ1 Series Expansion Racks.
Rack
Configuration
Requirements
CJ1 Series Expansion
Rack
One of each Module required for every Expansion Rack. Connect
the I/O Interface Module to the right of the Power Supply Unit.
CJ1 Series Power Supply Unit
I/O Interface Module CJ1W-II101
(Provided with 1 End Cover as a
standard accessory.)
Note: An I/O Control Module is required for each CJ1 Series
Expansion Rack.
Total number of Modules: 10 Modules max.
CJ1 Series Basic I/O Module
CJ1 Series Special I/O Module
CJ1 Series CPU Bus Module
(Mounting 11 or more Modules will result in a fatal error.)
CS1/CJ1 Series I/O Connecting Cable Required to connect I/O Control Modules to I/O Interface
Modules.
Note: The total length of CS1/CJ1 Series I/O Connecting Cable
used in the system must not exceed 12 m. Correct
operation is not ensured if the total cable length exceeds
12 m.
J Capacity Overview
CPU Models
Maximum I/O Modules per CPU
Maximum I/O Expansion Racks per CPU
(depending on power supply capacity)
(depending on power supply capacity)
20
30
40
1
2
3
CJ1M-CPU13
CJ1M-CPU23
CJ1G-CPU42H
CJ1G-CPU43H
CJ1G-CPU44H
CJ1G-CPU45H
CJ1H-CPU65H
CJ1H-CPU66H
J Products Used in Expansion Racks
Item
Model
Specifications
Cable
Length
CJ1 Series Power
Supply Unit
—
CJ1W-PA205R
CJ1W-PA202
CJ1W-PD025
CJ1W-II101
100 to 240 VAC (with RUN output), output capacity: 5 A, 5 VDC
100 to 240 VAC, output capacity: 2.8 A, 5 VDC
24 VDC, 5A, 5 VDC
I/O Interface
Module
One is required for each CJ1 Series Expansion Rack. An End Cover is
provided as a standard accessory. (Connect to an I/O Control Module on a
CPU Rack or to another I/O Interface Module on an Expansion Rack using
CS1/CJ1 Series Connecting Cable.)
—
End Cover
CJ1W-TER01
Required for the right-hand side of CJ1 Series Expansion Racks. One is
provided with I/O Interface Modules as a standard. (Not connecting an End
Cover will result in a fatal error.)
—
CS1W-CN313
CS1W-CN713
CS1W-CN223
CS1W-CN323
CS1W-CN523
CS1W-CN133
CS1W-CN133-B2
0.3 m
0.7 m
2 m
CJ1/CS1 Series
I/O Connecting
Cables
Used to connect I/O Interface Modules (CJ1W-II101) to I/O Control Modules
(CJ1W-IC101) or to other I/O Interface Modules.
3 m
5 m
10 m
12 m
Special Ordering Information
•
Order one CJ1W-IC101 I/O Control Module for the CPU rack and one CJ1W-II101 I/O Interface Module for each I/O
Expansion rack.
•
•
Connect the modules with a cable of the appropriate length.
The second and third I/O Expansion racks connect between I/O Interface Modules.
B-117
Programmable Controller CJ1
相关型号:
©2020 ICPDF网 联系我们和版权申明