CVM1D-DPL01 [OMRON]
Analog Circuit,;型号: | CVM1D-DPL01 |
厂家: | OMRON ELECTRONICS LLC |
描述: | Analog Circuit, |
文件: | 总8页 (文件大小:1443K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
RODUCT VERVIEW
P O
`
CVM1 Series
CVM1 Duplex
The CVM1D Duplex system’s
redundancy is a new option in Omron’s
large controllers. Two redundant CPUs
and power supplies ensure that
processes will continue operation when
a failure occurs. This makes the CVM1D
ideal for critical control system
applications. Besides its redundancy, the
CVM1D has several enhanced features
of the CV/CVM1 Series, including a
higher level of performance,
communications, and networking.
• Redundant CPUs
• High speed 0.125 µs processing
• Redundant power supplies
• Large 62K-word program and 24K-
word data memory capacity
• Hot standby simultaneous
processing
• Meets UL/CSA/CE standards
• Replace a CPU, power supply, and
• 275 instructions (500 variations)
I/O modules on-line
• Supports various software tools
• Synchronized program execution
and programming devices
and switching functions
• Duplex and simplex modes
• Supports existing CVM1, C500,
CV500 and 3G2A5 I/O modules
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
local Omron office
for further information
CVM1 Duplex Product Overview
1-800-55-OMRON
SYSTEM CONFIGURATION
CVM1 Duplex
Duplex and Simplex Operation
Duplex System (DPL)
CVM1D CPU rack is equipped with:
1. Two CPUs
Duplex Module
I/O
•
•
One active CPU controlling the system
One standby CPU operating in parallel with the active
CPU
2. A duplex unit that monitors errors in the two CPUs,
switches the CPU, I/O, and peripheral buses to the
standby CPU if an error occurs in the active CPU
3. Two power supplies operating simultaneously
Redundant Power
Supplies
I/O Expansion
Simplex System (SPL)
Redundant CPU’s
(only in a duplex system)
CVM1D CPU Rack is equipped with:
1. One CPU to control the system
2. A duplex unit that primarily operates the duplex
system. It also performs other functions including I/O
bus switching.
3. Two power supplies operating simultaneously
System Configuration
1. Basic System with a CVM1D CPU rack and expansion I/O racks
•
•
•
Uses up to 5 “CPU bus” modules (units).
Uses redundant power supplies.
I/O Modules can be replaced online.
**Example of a Duplex System with
an Expansion CPU Rack
2. System with a CVM1D CPU rack, expansion CPU rack, and
expansion I/O racks**
•
•
•
Uses up to 15 “CPU Bus” modules (units).
Uses redundant power supplies.
I/O Modules can be replaced online.
3. System with a CVM1D CPU rack, CVM1 or CV-series expansion
CPU rack, and CVM1 or CV-series expansion I/O racks
•
Demonstrates how to convert an existing CVM1 or CV-series
system to a duplex system
•
•
Uses redundant power supplies
I/O modules can be replaced online in the CPU Rack.
(Supported by the CVM1 or CV-series racks.)
CVM1 or CV-series expansion I/O racks without I/O interface
units cannot be connected.
•
4. System with a CVM1D CPU rack and C-series expansion I/O racks
•
Demonstrates how to upgrade an existing C2000H duplex
system to a CVM1D Duplex system.
•
•
Uses redundant power supplies.
I/O modules can be replaced online in the CPU rack, but not
the C-series racks.
•
C-series racks cannot be combined with CVM1 or CV-series
expansion I/O racks.
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
local Omron office
for further information
CVM1 Duplex Product Overview
1-800-55-OMRON
COMMUNICATION
CVM1 Duplex
The following diagram shows the communications networks supported by CVM1D Controllers.
Ethernet
•
•
•
Message communications
Host computer – PLC
PLC-PLC, or Computer-
Computer
•
•
•
FTP server function
Host computer-PLC
File transfers with the PLCs
Memory card
Controller Link
Easily assemble full-scale networks using
twisted-pair wiring
Supports high-capacity, high-speed, and
reliable data links as well as high volume
message communications
•
•
•
Supports communications between PLCs
and personal computers.
DeviceNet
Conforms to DeviceNet standards.
Remote I/O and message
communications.
•
High capacity, flexible remote
I/O
•
Message communications
support PLC- PLC
SYSMAC LINK
Two communications
methods (fiber optic
and coaxial cable)
Data link function for
intermode data links
without programming
Message service
communications, DeviceNet and
explicit messages.
•
•
•
SYSMAC BUS remote I/O
Remote I/O using I/O modules,
multi-drop, or fiber optic
connections
Uses remote I/O slave racks,
optical I/O modules, or I/O
terminals
Create multifunctional networks.
Supports many connection methods
and a wide variety of slaves
including: I/O terminals, remote
adapters, sensor terminals, I/O link
units, communications terminals, and
multiple I/O terminals
•
•
function
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
local Omron office
for further information
CVM1 Duplex Product Overview
1-800-55-OMRON
COMMUNICATION
CVM1 Duplex
Summary of Communications Networks: Information Level Communications
Network
Ethernet
Function
PLC ⇔ Host Computer
Communications
Message (FINS)
communications
Supporting Devices
Ethernet unit
Message (FINS)
communications
PLC ⇔ PLC
File Transfer Protocol (FTP)
server function
Memory Card in CPU Unit ⇔ Host
Computer
Socket service function
PLC ⇔ Computer directly connected to
the network
TCP/IP and UDP/IP
Message (FINS)
Controller
Link
Controller Link support
board and snit
communications
Data link (Offsets and
automatic settings can be
used.)
RS-232C to
Controller
Link
SYSMAC
LINK
Host computer and PLCs in the network
Host link commands and
RS-232C cable and
Controller Link unit
gateway functions
Message (FINS)
communications
Data Link
SYSMAC LINK Support
board and unit
PLC ⇔ Computer directly connected to
the network
Summary of Communications Networks: Control Level Communications
Network
Controller Link
Function
PLC ⇔ PLC
Communications
Devices
Controller Link Unit
Message (FINS)
communications
Data link (Offsets and
automatic settings can be
used.)
Automatic data link
Open network message (FINS) DeviceNet Master Unit and
communications
Message (FINS)
communications
Data Link
PC Link
DeviceNet
PC Link Unit
PLC ⇔ PLC
PLC ⇔ PLC
Configurator
SYSMAC LINK Unit
SYSMAC LINK
PLC ⇔ PLC
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
CVM1 Duplex Product Overview
local Omron office
for further information
1-800-55-OMRON
SPECIFICATIONS
CVM1 Duplex
Item
Power Supply
Specification
CVM1D-PA208
CVM1D-PA212
100 to 120 or 200 to 240 VAC (automatic voltage setting)
Rated Voltage
Frequency
Input-
Power
50/60 Hz ±5%
85 to 132 or 170 to 264 VAC
Operating Voltage Range
Supply
150VA max.
30A max.
8A
200VA max.
12A
Power Consumption
Inrush Current
Output Capacity
105% min.
6V min.
Less than 100 Ω
Mounted in panel
0.9 kg
Overcurrent Protection
Overvoltage Protection
Grounding
Enclosure
Weight
250 x 47 x 116 max.*
M3.5
0.8N m (8.1 kgf cm)
1.25 to YS3A, VD1.25 to 3.5
0.25 to 1.65 mm2
20MΩmin. (at 500 VDC)
Dimensions (mm) L x W x H
Terminal Screw Size
Applicable Mounting Torque
Applicable Crimp Terminal
Applicable Wire
Insulation Resistance
between AC external terminals and GR terminals
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals,
leakage current: 10mA max.
Dielectric Strength
Noise Immunity
Vibration Resistance
1,500 Vp-p, pulse width: 100ns to 1 µs, rise time: 1ns (via noise simulation)
10 to 57Hz, 0.075mm amplitude, 57 to 150Hz, acceleration: 1 G in X, Y and Z
directions for 80 minutes (time coefficient: 8 minutes x coefficient factor 10 =
total time of 80 minutes) (according to JIS C0911)
15G 3 times each in the X, Y and Z directions (according to JIS C0912)
Start input
Output while PLC is operating
0 to 55°C
10% to 90% (with no condensation)
Must be free of corrosive gases
Shock Resistance
External Input Signal
External Output Signal
Ambient Operating Temperature
Ambient Operating Humidity
Atmosphere
-25 to 75°C
CPU, CPU expansion, or I/O
expansion backplanes
Ambient Storage Temperature
Mounting Location
CPU, CPU expansion, or I/O
expansion backplanes
*Depth dimensions may vary due to cabling and connections.
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
CVM1 Duplex Product Overview
local Omron office
for further information
1-800-55-OMRON
PERFORMANCE SPECIFICATIONS
CVM1 Duplex
Item
Specification
CVM1D-CPU21 **
Stored program
CPU
Control Method
I/O Control Method
Programming
Instruction Length
Ladder Instruction
Execution Time
Cyclic refreshing
Ladder diagrams
1 to 8 words/instruction, 1 address/instruction
275 (500 variations)
0.125 to 0.375 µs
0.5 to 8.25 µs
62K words
Basic
Special
Program Capacity
I/O Bits
2,048 (words 0000 to 0127)
2,048
2,048
Remote I/O Bits
SYSMAC BUS/2
SYSBUS
SYSMAC BUS/2 : 12,800 (words 0200 to 999)
SYSBUS : 4,096 (words 2300 to 2555)
1,152 (words 0128 to 0199)
Remote I/O Bits
Work Bits
6,400 (words 1900 to 2299)
3,200 : 100000 to 119915 (words 1000 to 1199)
4,800 : 120000 to 149915 (words 1200 to 1499)
6,400 : 150000 to 189915 (words 1500 to 1899)
8 (TR0 to TR7)
4,096 : G00000 to 25515 (words G000 to 255)
8,192 : A00000 to 51115 (words A000 to 511)
1,024 bits (T0000 to 1023)
Link Bits
Holding Bits
CPU Bus Unit Bits
Temporary Bits
CPU Bus Link Bits
Auxiliary Bits
Timers
Timer : 0 to 999.9 s, High Speed Timer : 0 to 99.99 s
1,024 bits (C0000 to 1023)
Counters
0 to 9999 counts
24K words (D00000 to 24575)
Data Memory
256K words (E00000 to 32765 x 8 banks)
3 words (DR0 to DR2)
3 words (IR0 to IR2)
2K words (non-synchronous processing)
Memory cards : RAM, EEPROM, or EPROM
START input : RUN mode
Expansion DM
Data Registers
Index Registers
Trace Memory
File Memory
Control Input Signal
PC begins operating when input is ON and stops when it is OFF
Input specifications : 24VDC, 10mA
RUN output : The RUN output terminals are ON (closed) while
the PC is operating
Control Output Signal
Maximum switching capacity : 250VAC/2A (resistive load),
24VDC/2A, 250VAC/0.5A (inductive load: cos (=0.4)
Holding bits and contents of counters and data memory
Service life: 5 years
Memory Protection
Battery Life
The memory backup time when the PC is not powered varies
with ambient temperature
CPU failure (watchdog timer), I/O verify error, I/O bus error,
memory failure, remote I/O error, battery error, link error, special
I/O error, and others
Self-diagnostics
** The CVM1D only operates in synchronous RUN mode.
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
local Omron office
for further information
CVM1 Duplex Product Overview
1-800-55-OMRON
DIMENSIONS
CVM1 Duplex
• CPU Rack (Unit : mm)
The diagram below shows the rack without one power supply and an I/O control unit.
465
100
123
4
8
6
• Expansion CPU and Expansion I/O Racks (Unit : mm)
The diagram below shows the rack without one power supply and an I/O control unit.
4
6
5
‚
100
123
486
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
local Omron office
for further information
CVM1 Duplex Product Overview
1-800-55-OMRON
ORDERING INFORMATION
CVM1 Duplex
CVM1 Duplex
Description
Part Number
Standards
CVM1D CPU
CVM1D-CPU21
UL, CSA, CE
Two required for a duplex system
Duplex Module
Required in a simplex and duplex system
CPU Backplane
5-slot
Expansion CPU Backplane
10-slot
Expansion I/O Backplane
10-slot
CVM1D-DPL01
CVM1D-BC051
CVM1D-BI101
CVM1D-BI102
CVM1D-PA208
CVM1D-PA212
UL, CSA, CE
UL, CSA, CE
UL, CSA, CE
UL, CSA, CE
UL, CSA, CE
UL, CSA
Power Supply
12A output capacity/85 to 135VAC operating voltage range *
Power Supply
8A output cpapcity/170 to 264VAC operating voltage range *
Programming Console
CX-Programmer Software
(Configure as CVM1-CPU21-V2 CPU) **
Operation Manual
CVM1-PRS21-EV1
WS02-CXPC1-EV2.x
UL, CSA, CE
W351
W350
Installation Manual
* Requires 2 power supplies of the same type per backplane.
** SYSWIN, CX-Programmer, SYSMAC-CPT, SYSMAC Support Software (SSS), and CVSS can be used
also.
OMRON ELECTRONICS INC.
One Commerce Drive
Schaumburg, IL 60173
Please contact your
local Omron office
for further information
CVM1 Duplex Product Overview
1-800-55-OMRON
相关型号: