Digital Temperature Controllers
E5AN
Compact and Intelligent Temperature
Controllers
• Depth of only 78 mm.
• Various temperature inputs: thermocouple, platinum resistance
thermometer, infrared temperature sensor, and analog inputs.
• Auto-tuning and self-tuning available. Auto-tuning is possible
even while self-tuning is being executed.
• Heating or heating/cooling control is available.
• Event input allows multiple SP selection and run/stop function.
• Water-resistant construction (NEMA4X: equivalent to IP66).
• Conforms to UL, CSA, and IEC safety standards as well as CE
marking.
96(W) x 96(H) x 78(D) mm
®
Model Number Structure
ꢀ Model Number Legend
E5AN- @ @ @ M @ -500
1
2
3
4
5
1. Output type
4. Option Unit
M: Option Unit can be mounted
5. Input type
R:
Q:
C:
Relay
Voltage (for driving SSR)
Current
TC: Thermocouple
2. Number of alarms
3: Three alarms
P:
Platinum resistance thermometer
3. Heater burnout alarm
Blank:Not available
H:
Available
Ordering Information
ꢀ Standard Models
Size
Power supply
No. of alarm
points
Control output Heater burnout Thermocouple model Platinum resistance
voltage
alarm
thermometer model
E5AN-R3MP-500
E5AN-R3HMP-500
E5AN-Q3MP-500
E5AN-Q3HMP-500
E5AN-C3MP-500
E5AN-R3MP-500
E5AN-R3HMP-500
E5AN-Q3MP-500
E5AN-Q3HMP-500
E5AN-C3MP-500
1/4 DIN
96(W) x 96(H) x
78(D) mm
100 to 240 VAC
3
3
Relay
No
Yes
No
Yes
No
No
Yes
No
Yes
No
E5AN-R3MTC-500
E5AN-R3HMTC-500
E5AN-Q3MTC-500
E5AN-Q3HMTC-500
E5AN-C3MTC-500
E5AN-R3MTC-500
E5AN-R3HMTC-500
E5AN-Q3MTC-500
E5AN-Q3HMTC-500
E5AN-C3MTC-500
Voltage
(for driving SSR)
Current
Relay
24 VAC/VDC
Voltage
(for driving SSR)
Current
Note 1. A Current Transformer (CT) is not provided with the Unit. If using a heater burnout alarm, be sure to order one when ordering the E5AN.
2. When the heating and cooling function or the heater burnout alarm is used, one of the alarm outputs will be disabled for each function used.
3. Specify the power supply specifications when ordering.
Digital Temperature Controllers E5AN
I-11
ꢀ Option Units
ꢀ Current Transformer (Sold
The E5AN provides communication or event input functionality when
mounted with one of the following Option Units.
Separately)
Model
E54-CT1
E54-CT3
12.0 dia.
Name
Model
E53-AK01
E53-AK03
E53-AKB
Function
RS-232C communication
RS-485 communication
Event input
Hole diameter
5.8 dia.
Communication Unit
ꢀ Terminal Cover
Event Input Unit
Model
E53-COV11
Note: The Terminal Cover comes with the E5AN and does not have
to be purchased separately.
Specifications
ꢀ Ratings
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz/24 VDC
Operating voltage range
Power consumption
Sensor input
85% to 110% of rated supply voltage
9 VA
5 VA/4 W
K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Thermocouple:
Infrared temperature sensor:
Voltage input:
10 to 70°C, 60 to 120°C, 115 to 165°C, 160 to 260°C
0 to 50 mV
Control output
Relay output
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations
12 VDC +15%
−20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
Voltage output
Current output
/
4 to 20 mA DC, load: 600 Ω max., resolution: approx. 2,600
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations
2-PID or ON/OFF control
Alarm output
Control method
Setting method
Indication method
Digital setting using front panel keys
7-segment digital display and single-lighting indicator
Character height: PV: 15.0 mm; SV: 9.5 mm
Other functions
According to Controller model
−10 to 55°C (with no condensation or icing)
25% to 85%
Ambient temperature
Ambient humidity
Storage temperature
−25 to 65°C (with no condensation or icing)
I-12
Digital Temperature Controllers E5AN
ꢀ Input Ranges
Platinum Resistance Thermometer Input/Thermocouple Input
Platinum resistance thermometer input
Input type
Name
Platinum resistance thermometer
Pt100 JPt100
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
850
800
700
600
500
400
500.0
500.0
300
200
100
0
−100
−200
100.0
0.0
100.0
0.0
4
−199.9
−199.9
−200
Set value
0
1
2
3
Thermocouple input
ES1A Infrared
Input type
Name
Thermocouple
E
Temperature Sensor
Analog input
0 to 50 mV
K10 to K60 to K115 to K160 to
K
J
T
L
U
N
R
S
B
70°C
120°C 165°C 260°C
1800
1800
1700
1600
1500
1400
1300
1200
Usable in the
following
1700
1700
ranges by
scaling:
−1999 to 9999
or −199.9 to
999.9
1300
1300
1100
1000
900
800
700
600
500
400
300
850
850
600
500.0
400.0
400
400.0
400
400.0
260
120
0
165
0
200
100
0
−100
−200
70
0
100
11
−20.0
−20.0
0
0
0
0
−100
−100
−200
−199.9
−200 −199.9 −200
−200
Set value
0
1
2
3
4
17
5
6
7
18
8
9
10
12
13
14
15
16
Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC751
Shaded ranges indicate default settings.
ES1A models with a temperature range of 160°C to 260°C have been discontinued.
Digital Temperature Controllers E5AN
I-13
ꢀ Characteristics
Indication accuracy
Thermocouple:
( 0.5% of indicated value or 1°C, whichever greater) 1 digit max. (see note)
Platinum resistance thermometer:
( 0.5% of indicated value or 1°C, whichever greater) 1 digit max.
Analog input: 0.5% FS 1 digit max.
CT input: 5% FS 1 digit max.
Hysteresis
0.1 to 999.9 EU (in units of 0.1 EU)
0.1 to 999.9 EU (in units of 0.1 EU)
0 to 3999 s (in units of 1 s)
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
0 to 3999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
0.0% to 100.0% (in units of 0.1%)
−1999 to 9999 (decimal point position depends on input type)
500 ms
20 MΩ min. (at 500 VDC)
2000 VAC, 50 or 60 Hz for 1min (between different charging terminals)
10 to 55 Hz, 10 m/s2 for 2 hours each in X, Y and Z directions
300 m/s2, 3 times each in 3 axes, 6 directions (relay: 100 m/s2)
Approx. 310 g
Mounting bracket: Approx. 60 g
Degree of protection
Memory protection
EMC
Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
EEPROM (non-volatile memory) (number of writes: 100,000)
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (amplitude modulated, 80 MHz to
1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3)
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
2 kV I/O signal-line (level 4)
Approved standards
UL3121-1, CSA22.2 No. 142, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the terminal cover is mounted.
Note: The indication of K thermocouples in the −200 to 1300°C range, and T and N thermocouples at a temperature of −100°C or less, and U and
L thermocouples at any temperature is 2°C 1 digit maximum. The indication of B thermocouples at a temperature of 400°C or less is un-
restricted.
The indication of R and S thermocouples at a temperature of 200°C or less is 3°C 1 digit maximum.
ꢀ Communications Specifications
Transmission path connection
RS-485:
Multiple points
RS-232C: Point-to-point
RS-485 (two-wire, half duplex)/RS-232C
Start-stop synchronization
1,200/2,400/4,800/9,600/19,200 bps
ASCII
Communications method (see note 1)
Synchronization method
Baud rate
Transmission code
Data bit length (see note 2)
Stop bit length (see note 2)
Error detection
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSWAY
Block check character (BCC): with CompoWay/F
Flow control
Not available
RS-485/RS-232C
Not available
40 bytes
Interface (see note 1)
Retry function
Communications buffer
Note 1. RS-232C communications are only supported for the E5AN and E5EN models.
2. The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
I-14
Digital Temperature Controllers E5AN
ꢀ Current Transformer (Sold Separately) Ratings
Dielectric strength
Vibration resistance
Weight
1,000 VAC (1 min)
50 Hz 98 m/s2
E54-CT1: Approx. 11.5 g
E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Armature (2)
Plug (2)
ꢀ Heater Burnout Alarm Specifications
Max. heater current
Single-phase AC: 50 A (see note 1)
Input current readout accuracy
Heater burnout alarm setting range
Min. detection ON time
5%FS 1 digit max.
0.0 to 50.0 A (0.1 A units) (see note 2)
190 ms (see note 3)
Note 1. When heater burnout is detected on a 3-phase heater, use the K2CU-F@@A-@GS (with gate input terminal).
2. When the set value is “00 A,” the heater burnout alarm will always be OFF. When the set value is “50.0 A,” the heater burnout alarm will
always be ON.
3. When the control output ON time is less than 190 ms, heater burnout detection and heater current measurement will not be carried out.
ꢀ Engineering Data
Electrical Life Expectancy Curve for Relays (Reference Values)
500
300
E5AN, E5EN
100
250 VAC, 30 VDC
(resistive load)
cosφ = 1
50
30
10
5
3
E5CN
250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
0
1
2
3
4
5
6
Switching current (A)
E54-CT1
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400 2
Winding resistance: 18 2 Ω
100 V
50 Hz
∞
10
1 kΩ
Distortion
factor 10%
1
100 mV
10
3%
1%
100 Ω
RL = 10 Ω
1
100 µV
10
1
10
100 mA
1
10
100 1,000 A
Thru-current (Io) A (r.m.s.)
Digital Temperature Controllers E5AN
I-15
E54-CT3
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON Temperature Controller is 50 A.)
Number of windings: 400 2
Winding resistance: 8 0.8 Ω
100 V
50 Hz
∞
Distortion
factor 10%
3%
10
1 kΩ
500 Ω
1%
1
100 mV
10
100 Ω
50 Ω
RL = 10 Ω
1
100 µV
10
1
10
100 mA
1
10
100 1,000 A
Thru-current (Io) A (r.m.s.)
Wiring Terminals
• The voltage output (control output) is not electrically insulated from
the internal circuits. When using a grounding thermocouple, do not
connect the control output terminals to the ground. If the control
output terminals are connected to the ground, errors will occur in
the measured temperature values as a result of leakage current.
• Standard insulation is applied to the power supply I/O sections. If
reinforced insulation is required, connect the input and output ter-
minals to a device without any exposed current-carrying parts or to
a device with standard insulation suitable for the maximum operat-
ing voltage of the power supply I/O section.
Event input
Contact inputs
Communications
Non-contact input
RS-232C RS-485
←SD
←RD
←B (+)
←A (−)
11
12
13
11
12
13
Current output
4 DC to 20 mA
Voltage output Relay output
Input power supply
Control output 1
←SG
←Do not use
Heater burnout
detection input
12 VDC
40 mA
ALM3/Control
output 2
ALM2
Analog input
Alarm output
ALM1/Heater
burnout
Note: Two input power supplies are available: 100 to 240 VAC or 24 VDC.
I-16
Digital Temperature Controllers E5AN
Nomenclature
Temperature
unit
Operation
indicators
No.1 display
No.2 display
Up key
Level key
Down key
Mode key
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Panel Cutouts
Mounted Separately
Group Mounted
(96 × number of units -3.5)+1.0
0
Group mounting does
not allow waterproofing.
•
•
Recommended panel thickness is 1 to 8 mm.
Group mounting is not possible in the vertical
direction. (Maintain the specified mounting
space between Controllers when they are
group mounted.)
•
•
To mount the E5AN so that it is waterproof,
apply the waterproof packing to the E5AN.
When two or more E5ANs are mounted, make
sure that the surrounding temperature does
not exceed the allowable operating
temperature specified in the specifications.
Digital Temperature Controllers E5AN
I-17
Current Transformer (Sold Separately)
Terminal Cover
E53-COV11
E54-CT1
E54-CT3
2.36 dia.
13
5.8 dia.
12 dia.
6.5 dia.
92.3
40 x 40
Two, 3.5 dia.
Two, M3 (depth: 4)
6.5
10.5
8
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
I-18
Digital Temperature Controllers E5AN
相关型号: