Temperature Controller  
E5AX-P  
A 96 x 96 mm (DIN) Controller for  
Control Valves  
Controls motor valves without a potentiometer.  
Optimum PID control with feed-forward control  
circuitry.  
High precision regardless of the set temperature.  
Compatible with various inputs (input selected via  
internal switch).  
Models with communications capabilities also  
available.  
Ordering Information  
Electronic Temperature Controller  
Communica-  
tions  
None  
RS-232C  
RS-422*  
RS-485*  
BCD  
Transmission  
output*/**  
(4 to 20 mA)  
Communications  
Board Add-on Type  
Model  
E5AX-PRR E5AX-PRR01 E5AX-PRR02 E5AX-PRR03 E5AX-PRR20 E5AX-PRRF  
E5AX-PRRM  
*The Controller can also be equipped with a terminal block to connect communications. Specify a terminal block by adding “-X” to the model  
number. Example: E5AX-PRR02-X  
**Capable of transmitting the process value or output value, but remote setting by external input is not possible.  
Temperature Ranges  
Input (switch  
selectable)  
Thermocouple  
Temperature  
resistance  
thermometer  
K
J/L  
T/U  
Copper vs.  
constantan  
E
R
S
PT platinum  
resistance  
Chromel vs.  
alumel  
Iron vs.  
Chromel  
vs.  
Platinum vs.  
platinum  
Platinum vs.  
constantan  
platinum 10% thermometer  
constantan 13% rhodium  
rhodium  
0 to 1,700  
0 to 3,000  
(Pt100/JPt100)  
–99.9 to 450.0  
–99.9 to 800.0  
0.1  
Range  
%C  
%F  
–200 to 1,300 –100 to 850  
–200 to 400 0 to 600  
0 to 1,700  
0 to 3,000  
–300 to 2,300 –100 to 1,500 –300 to 700 0 to 1,100  
1
Resolution (%C/%F)  
(main settings and  
alarm)  
Communications Boards  
Communications  
RS-232C  
RS-422  
E53-X02  
RS-485  
E53-X03  
BCD  
E53-X20  
Transmission output  
(4 to 20 mA)  
Model  
E53-X01  
E53-XF  
1
E5AX-P  
E5AX-P  
Specifications  
Ratings  
Supply voltage  
100 to 240 VAC, 50/60 Hz (either frequency applicable with same unit)  
85% to 110% of rated supply voltage  
Operating voltage range  
Power consumption  
Approx. 10 VA (at 100 VAC) to 15 VA (at 240 VAC)  
Approx. 12 VA (at 100 VAC) to 15 VA (at 240 VAC) with communication function  
Input  
Thermocouple (K/J/T/E/R/S/L/U) or platinum resistance thermometer (Pt100/JPt100)  
selectable  
Potentiometer input  
Control output  
100 W to 2.5 kW  
Relay output: open, close; SPST-NO contacts; 3 A, 250 VAC (resistive load); inrush current: 1  
A max.  
Control mode  
PID control with auto-tuning  
Alarm output  
Relay output, SPST-NO contacts; 3 A, 250 VAC (resistive load)  
Digital setting via Up and Down Keys  
Setting method  
Indication method  
Other functions  
Digital indications (character heights PV: 15 mm and SV: 11 mm) (Color PV: red, SV: green)  
Upper and lower limits for set value  
Key protection  
Input shift  
Display unit selection (%C/%F)  
Normal and reverse output selection  
Valve position display  
Motor calibration function  
Watchdog timer function (Detects failures in the CPU and restores the CPU.)  
Manual output (balanceless-bumpless operation switchable)  
Communications  
Protocol  
RS-232C, RS-422, RS-485  
Half-duplex  
BCD  
Transmission output  
Transmission method  
Data select code  
4 to 20 mA DC  
Load: 600 W max.  
Resolution: Approx. 3,200  
Synchronization method  
Baud rate  
Start-stop synchronization  
150/300/600/1,200/2,400/4,800/9,600 bps  
ASCII (7-bit)  
---  
---  
Transmission code  
Communications Write to  
Main setting, set alarm value, proportional Main setting, set  
band, integral time, derivative time, AT  
start/stop etc.  
Write disabled  
Temperature  
Controller  
alarm value  
Read from  
Temperature  
Controller  
Main setting, set alarm value, proportional Main setting, set  
Process value (see note 3),  
valve position  
band, integral time, derivative time, set  
limit value, process value, valve position,  
error codes, etc.  
alarm value,  
process value, error  
codes, etc.  
Note: 1. The maximum total cable length must not exceed the following limits.  
RS-422: 500 m; RS-232C: 15 m; RS-485: 500 m  
2. A maximum of 32 Temperature Controllers can be connected to one host computer using serial communications (RS-422, RS-485).  
3. Outputs the temperature data within the set limits.  
2
E5AX-P  
E5AX-P  
Characteristics  
Setting accuracy  
(+0.3% of set value or +1%C, whichever greater), +1 digit max.  
Indication accuracy  
(+0.3% of set value or +1%C, whichever greater), +1 digit max. (Set value coincides with the  
indicated value, because no relative error exists between both values.)  
Disable band  
0.1% to 10.0% (in units of 0.1%)  
0.1% to 999.9 %C/%F (in units of 0.1%C/%F)  
1 to 3,999 s (in units of 1 s)  
Proportional band  
Integral time  
Derivative time  
0 to 3,999 s (in units of 1 s)  
Alarm output setting range  
Thermocouple: –999% to 9,999%C/%F (in units of 1%C/%F)  
Platinum resistance thermometer: –99.9% to 999.9%C/%F (in units of 0.1%C/%F)  
Alarm output hysteresis  
Sampling period  
0.0% to 999.9 %C/%F (in units of 0.1%C/%F)  
500 ms (temperature sensor input)  
500 ms  
Output refresh period  
Display refresh period  
Valve travel indication  
Full Open/close time  
Input shift  
500 ms (temperature sensor input)  
–99% to 999% (in units of 1%)  
1 to 999 s ( in units of 1 s)  
Thermocouple: –999% to 9,999%C/%F (in units of 1%C/%F)  
Platinum resistance thermometer: –99.9% to 999.9%C/%F (in units of 0.1%C/%F)  
Insulation resistance  
Dielectric strength  
Vibration resistance  
20 MW min. (at 500 VDC)  
2,000 VAC 50/60 Hz for 1 min between terminals of different polarities  
Malfunction: 2 to 55 Hz, 2G 10 min each in X, Y, and Z directions  
Destruction: 10 to 55 Hz, 0.75-mm double amplitude 2 hrs each in X, Y, and Z directions  
2
2
Shock resistance  
Life expectancy  
Malfunction: 200 m/s 3 times each in 6 directions  
Destruction: 300 m/s 3 times each in 6 directions  
Mechanical: 10,000,000 operations min.  
Electrical: 100,000 operations min.  
Ambient temperature  
Operating: –10% to 55%C (with no icing)  
Storage: –25% to 65%C (with no icing)  
Ambient humidity  
Memory protection  
Enclosure ratings  
Operating: 35% to 85%  
Non-volatile memory  
Front panel: IEC standard IP50  
Rear case: IEC standard IP20  
Terminals: IEC standard IP00  
Weight  
Standard: Approx. 350 g; Communications: Approx. 480 g; Mounting bracket: Approx. 50 g  
*The accuracy of U thermocouples under temperatures from –150% to 400%C (–240% to 700%F) is +2%C (+3.6%F) +1 digit. Accuracy is  
reduced below –150%C (–240%F). The accuracy of R and S thermocouples under 0% to 200%C (0% to 400%F) is +3%C (+5.4%F) +1 digit.  
3
E5AX-P  
E5AX-P  
Nomenclature  
Process Value (PV) Display  
Displays the process value, the character for  
parameter being displayed on the SV display  
and error messages.  
Auto-tuning Indicator  
Flashes on and off every  
second when auto-tun-  
ing is taking place.  
Manual Output Mode In-  
dicator  
Lights when in manual  
output mode.  
Open Output Indicator  
Lights when the open out-  
put is ON.  
Set Value (SV) Display  
Displays main setting and other  
parameters.  
Alarm Indicator  
Lights when the alarm output is ON.  
Close Output Indicator  
Lights when the close out-  
put is ON.  
A/M Key (Automatic/Manual)  
Press for 1 second minimum to switch  
between auto output mode and manual  
output mode.  
Level Key  
Press for 2 seconds mini-  
mum to change levels to  
set different groups of pa-  
rameters.  
Up Key  
Press to increase the main setting or  
other parameters. Successively in-  
creases the value when held down.  
Display Key  
Press to shift the display  
to the next parameter.  
Front Cover  
Down Key  
Press to decrease the main setting or other  
parameters. Successively decreases the  
value when held down.  
Operation  
NOTICE: Always turn off the power supply to the Electronic Temperature Controller before changing any switch settings.  
Settings  
1. Remove the internal mechanism from the housing. Lift the  
internal mechanism while pressing the hook at the bottom of  
the front panel.  
Protection switch  
(SW101, PROTECT)  
Hook  
Pull out the internal mechanism  
while holding down the hook with  
your finger.  
Alarm mode selector  
(SW205, ALM)  
Temperature sensor selector  
(SW206, INPUT)  
2. Four internal switches must be set on the E5AX: the  
temperature sensor selector, the operating mode selector,  
and the alarm mode selectors 1 and 2.  
Operating mode selector  
(SW 201, FUNCTION)  
The figures show the locations of these switches and the  
protection switches on the internal mechanisms. The  
protection switch can be used to disable key operation.  
Temperature Sensor Selector (SW206,  
INPUT)  
This selector selects the temperature sensor to be used. It is facto-  
ry-set to position 2 to designate a K-type (chromel-alumel thermo-  
couple) temperature sensor. The following table lists the other pos-  
4
E5AX-P  
E5AX-P  
sible settings for temperature sensors. Refer to temperature range  
charts under Ordering Information for further information.  
Operating Mode Selector (SW201,  
FUNCTION)  
The scale displayed (%C or %F) is selected by the operating mode  
selector (SW201).  
This DIP switch selects the operation modes listed in the following  
table.  
Pin  
Pin  
Function  
Not used.*  
Control setting  
number setting  
1
2
Leave turned OFF.  
Control output  
ON  
Normal (cooling)  
Reverse (heating)  
Enabled  
Switch  
setting  
Temperature  
sensor code  
Temperature range  
OFF  
ON  
Input shift  
3
4
5
6
%C  
%F  
OFF  
ON  
Disabled  
Enabled  
0
1
2
3
4
5
6
7
8
9
R
0 to 1,700  
0 to 1,700  
–200 to 1,300  
–100 to 850  
–200 to 400  
0 to 600  
0 to 3,000  
SP (set point)**  
protection cancel  
Display unit  
S
0 to 3,000  
OFF  
ON  
Disabled  
%F  
K
–300 to 2,300  
–100 to 1,500  
–300 to 700  
0 to 1,100  
J
OFF  
ON  
%C  
T
PID display  
Enabled  
E
OFF  
Disabled  
JPt100  
Pt100  
L
–99.9 to 450.0 –99.9 to 800.0  
–99.9 to 450.0 –99.9 to 800.0  
*Always operate with pin 1 OFF. Operating with pin 1 ON could re-  
sult in malfunction.  
–100 to 850  
–200 to 400  
–100 to 1,500  
–300 to 700  
**SP protection cancel is effective only when SW101 (key protec-  
tion) is on. If the SP protection cancel is ON, key protection (SW101  
ON) will not apply to the set point, i.e., you will be able to change the  
set point regardless of the setting of SW101.  
U
Alarm Mode Selector (SW205: ALM)  
Alarm mode selector is provided on all E5AX Temperature Controllers. Alarm modes, listed in the following table, can be selected using this  
switch. The switch is factory-set to position 2, i.e., the upper-limit alarm mode.  
Switch  
Mode (SW205)  
Alarm operation  
No alarm  
Alarm output  
When X is negative  
Setting range  
setting  
Display  
When X is positive  
OFF  
0
1
No display  
---  
X
X
Upper- and lower-limit  
alarm  
---  
Thermocouple:  
0%  
to  
)––(  
9,999%C/%F  
Platinum resistance thermometer:  
0% to 999.9%C/%F  
X
X
2
3
4
5
Upper-limit alarm  
Lower-limit alarm  
Thermocouple: –999% to  
9,999%C/%F  
–––(  
)–––  
–()–  
3––e  
X
X
X
X
Platinum resistance thermome-  
ter: –99.9% to 999.9%C/%F  
X
X
Upper- and lower-limit  
range alarm  
Thermocouple:  
0%  
to  
---  
---  
9,999%C/%F  
Upper- and lower-limit  
alarm with standby se-  
quence  
Platinum resistance thermometer:  
0% to 999.9%C/%F  
X
X
Y
6
7
8
Upper-limit alarm with  
standby sequence  
Thermocouple: –999% to  
9,999%C/%F  
–––e  
3–––  
1––(  
X
X
Lower-limit alarm with  
standby sequence  
Platinum resistance thermome-  
ter: –99.9% to 999.9%C/%F  
Y
Absolute-value alarm  
0%C  
0%C  
5
E5AX-P  
E5AX-P  
Key Protection Switch (SW101, PROTECT)  
When the key protection switch is set to the ON position, the Level Key, Up and Down Keys, and Auto-tuning Key cannot be operated. In effect,  
the Temperature Controller is write-protected and the set values (such as the alarm value) can be read out only. The set point, however, will not  
be protected if the SP protection disable is turned ON (pin 4 of SW201).  
6
E5AX-P  
E5AX-P  
Motor Calibration: calb  
The following setting are used to set the opening/closing time for controlling valves. Always set the following parameters when installing the  
controller. If a display is required for valve position, set the open and close positions at the same time.  
Down Keys to set the fully open/close time to a value between  
1 and 999 s in the units of 1 s.  
PV  
sl–l  
5. Press the Display Key. sl–l will be displayed and motor  
calibration will be complete. Press the Level Key for at least  
two seconds, confirm that in–t is displayed, and then press  
the Level Key again for at least two seconds to display the  
process value and return to the initial display mode.  
–200  
SV  
Lower setting limit  
Press a.  
Settings with a Potentiometer (with Valve Position Display)  
1. Turn on power and press the Level Key for at least two  
seconds. sl–l will be displayed. Then press the Display Key  
until calb is displayed.  
This is the initial mode when power is turned on for the first  
time.  
Press a.  
calb  
2. Simultaneously press the Up and Down Keys for at least one  
second. fr–h will be displayed, the OPEN output will turn ON,  
and the valve will start to open. Press the Display Key as soon  
as the valve stops by the limit switch built into the motor. The  
count value for the fully open position will be set.  
Motor calibration display  
Press the UP and Down  
keys simultaneously.  
a
3. Press the Display Key. fr–l will be displayed, the OPEN output  
will turn OFF, the CLOSE output will turn ON, and the valve  
will start to close. Press the Display Key as soon as the valve  
stops by the limit switch built into the motor. The count value  
for the fully close position will be set.  
fr–l  
Count value  
Fully open position  
Fully close position  
Fully open/close time  
Press a.  
4. Press the Display Key. mot will be displayed and the CLOSE  
output will turn OFF. The automatically set fully open/close  
time will be displayed. Use the Up and Down Keys to adjust  
the setting if required (value must be between 1 and 999 s in  
the units of 1 s).  
fr–l  
Count value  
Press a.  
5. Press the Display Key. sl–l will be displayed and motor  
calibration will be complete. Press the Level Key for at least  
two seconds, confirm that in–t is displayed, and then press  
the Level Key again for at least two seconds to display the  
process value and return to the initial display mode.  
mot  
30  
WARNING  
Never calibrate the motor during control operation. Make sure  
that control operations have been stopped before calibrating.  
Settings when Not Using a Potentiometer (No Valve Position  
Display)  
1. Turn on power and press the Level Key for at least two  
seconds. sl–l will be displayed. Then press the Display Key  
until calb is displayed.  
Note: 1. The output mode cannot be changed in motor calibra-  
tion mode.  
This is the initial mode when power is turned on for the first  
time.  
2. If the fully open position is less than the fully closed posi-  
tion, the value position will not be displayed and the dis-  
play will show “a––– ” for automatic and “m––– ” for manu-  
al operation. If a potentiometer is not being used for  
feedback, press the Display Key at steps 2 and 3 without  
regarding the position of the valve and then set the fully  
open/close time. Here too, the display for value position  
will show “a––– ” for automatic and “m––– ” for manual  
operation.  
2. Simultaneously press the Up and Down Keys for at least one  
second. fr–h will be displayed and the OPEN output will turn  
ON.  
3. Press the Display Key. fr–l will be displayed, the OPEN output  
will turn OFF, and the CLOSE output will turn ON.  
4. Press the Display Key. mot will be displayed and the CLOSE  
output will turn OFF. While mot is displayed, use the Up and  
7
E5AX-P  
E5AX-P  
Inputting Parameters  
The Temperature Controller has three display levels, 0, 1, and 2, in which only specific parameters can be set. Level 0 is the initial and is auto-  
matically entered at power application. To change the mode to set or change a different group of parameters, hold down the Level Key for 2  
seconds minimum. The display level mode changes as shown below. Actual displays vary with models and switch settings. If a display does not  
appear as expected, check your switch settings.  
Power ON  
Level 0  
Press the Level Key.  
Level 1  
Level 2  
Press the Level Key.  
Press the Level Key.  
Valve travel, main set-  
ting, alarm set value,  
input shift, PID con-  
stants  
Lower/upper setting limit,  
alarm hysteresis, disable  
band, motor calibration, Fully  
open/close position, Fully  
open/close time  
Input type, alarm mode  
Note: 1. Not displayed in automatic output mode. “m––– ” will be  
Level 0  
displayed if a potentiometer is not connected.  
2. Not displayed in manual output mode. “a––– ” will be dis-  
played if a potentiometer is not connected.  
PV Process value  
(Note 1)  
3. Not displayed when the alarm is disabled (SW203 set to  
0 or 9).  
m
0
SV  
Valve travel  
4. Not displayed when the input shift display is disabled  
(SW201, pin 3 OFF).  
Press a.  
5. Not displayed when PID display is disabled (SW201, pin  
6 OFF).  
Process value  
Main Setting  
Main setting  
0
The set point can be changed with the Up and Down Keys.  
Press a.  
Valve Travel  
The value travel can be monitored. If a potentiometer is not con-  
nected, the display will show “a––– ” for automatic and “m––– ” for  
manual operation. While “m ” is displayed in manual output mode,  
the Up Key will turn ON the OPEN output and the Down Key will turn  
ON the CLOSE output.  
(Note 2)  
Process value  
Valve travel  
a
0
Press a.  
Selecting the Output Mode  
(Note 3)  
al  
The A/M Key can be pressed for one second or longer to change  
between the automatic and manual output modes. The balance-  
less-bumpless function will operate to prevent the output from  
changing abruptly.  
Alarm value  
0
Press a.  
Automatic Output Mode  
(Note 4)  
in–5  
In automatic output mode, the control will function automatically.  
When the A/M Key is pressed and the automatic output mode is first  
entered, displays like the following will appear (display level 0).  
Input shift  
0
Press a.  
p
123  
80  
PV  
SV  
Process value  
Main setting  
(Note 5)  
Proportional band  
40.0  
Press a.  
i
Manual Output Mode  
In manual output mode, the controller can be operated with the Up  
and Down Keys. The Up Key will turn the OPEN output ON and light  
the OPEN indicator. The Down Key will turn ON the CLOSE output  
and light the CLOSE indicator.  
When the A/M Key is pressed and the manual output mode is first  
entered, displays like the following will appear (display level 0).  
(Note 5)  
Integral time  
240  
Press a.  
d
(Note 5)  
123  
PV  
SV  
Process value  
40  
Derivative time  
Valve position (%)  
m 80  
Press a.  
The MANU indicator will light and remain lit until the automatic out-  
put mode is returned to.  
8
E5AX-P  
E5AX-P  
Alarm: al  
Level 1  
When al is displayed on the PV display, the alarm value for alarm  
output can be set on the SV display. When the temperature exceeds  
or falls below the set alarm value, the corresponding alarm output is  
produced and the ALM indicator on the front panel lights. Usually,  
the alarm value is set as a deviation from the main setting, but it can  
also be set as an absolute value when the event alarm mode is se-  
lected. Set the alarm value by using the Up and Down Keys while al  
is displayed. The message is not displayed if the alarm mode selec-  
tor is set to position 0. Factory-set to upper-limit, alarm value  
0%C/%F  
PV  
SV  
ower setting limit  
pper setting limit  
Input Shift: in–5  
When pin 3 of the operating mode selector switch (SW201) is set to  
the ON position, the input shift function can be used. This function is  
used to shift the temperature display from the measured value by a  
desired value, as shown by the examples in the following table:  
Note 1)  
Input shift value  
Temperature mea-  
sured by sensor  
Displayed  
temperature  
larm hysteresis  
0 (without shift)  
100%C  
100%C  
100%C  
10 (shifted by  
110%C  
10%C)  
isable band  
–10 (shifted by  
–10%C)  
100%C  
90%C  
Note 2)  
This function can be used mainly for fine tuning compensation,  
while leaving the set temperature unaffected. Select this function by  
pressing the Display Key three times in display level 0.  
otor calibration display  
Press a.  
b r simultaneously.  
Proportional Band: p  
When the character p is displayed on the PV display, the propor-  
tional band (P constant) can be changed using the Up and Down  
Keys. The new value will be displayed on the SV display. It can be  
set in a range from 0.1% to 999.9%C/%F in units of 0.1%C/%F. The  
factory setting is 40.0%C/%F.  
(Note 3)  
Count value  
Fully open position  
NOTICE: The output value will change according to the differ-  
ence between the set value and the present value when  
the proportional band is changed during control operation.  
If this difference is too great, a drastic change will result.  
Always switch to the manual output mode before changing  
the proportional band.  
Count value  
Fully closed position  
Fully open/close time  
mot  
30  
Integral Time (Reset Time): i  
When the character i is displayed on the PV display, the integral time  
(I constant) can be changed using the Up and Down Keys. It can be  
set in a range from 0 to 3,999 seconds in units of 1 second. The fac-  
tory setting is 240 seconds.  
Press a.  
Note: 1. Not displayed when the alarm is disabled (SW205  
Derivative Time (Rate Time): d  
set to 0 or 9).  
The derivative time (D constant) can be changed when the charac-  
ter d is displayed on the PV display using the Up and Down Keys. It  
can be set in a range from 0 to 3,999 seconds in units of 1 second.  
The factory setting is 40 seconds.  
2. Motor calibration will be displayed when power is  
turned on for the first time.  
3. Displayed only when the motor calibration mode is  
entered.  
9
E5AX-P  
E5AX-P  
Lower/Upper Limits of Setting Range: sl–l, sl–h  
Input Type: in–t  
When in–t is displayed on the PV display, the present setting of the  
input type selector (SW206), is displayed on the SV display. The fol-  
lowing table shows the messages that may be displayed:  
400  
–200  
0
1,300  
Display  
r pr  
5 pr  
k ca  
j ic  
t cc  
e cr  
jpt  
Sensor  
SL-L  
SL-H  
R
Basically, the temperature range that can be measured is deter-  
mined by the temperature sensor to be used. For example, when a  
K-type (chromel-alumel thermocouple) temperature sensor is se-  
lected, the measurable range is from –200%C to 1,300%C. Howev-  
er, this temperature range can be narrowed, for example, to 0%C to  
400%C. To do this, set the lower-limit value of the temperature set-  
ting range, in this case to 0%C, on the SV display by using the Up  
and Down Keys while 5l–l is displayed on the PV display. Similarly,  
set the upper-limit value, 400%C, while 5l–h is displayed. If the pro-  
cess temperature falls below the set lower-limit value or exceeds  
the set upper-limit value, it is displayed on the PV display within the  
temperature range of the temperature sensor.  
S
K
J
T
E
JPt100*  
Hysteresis Alarm: hysa  
Pt100**  
pt  
The hysteresis alarm value for the alarm can be set in a range from  
0.0% to 999.9%C while hysa is displayed on the PV display using the  
Up and Down Keys. The factory setting is 0.2%C/%F.  
L
l ic  
u cc  
U
Disable band: db  
The disable band can be set in a range from 0.1% to 10.0% while db  
is displayed on the PV display using Up and Down Keys. The factory  
setting is 2.0%.  
*Meets JIS 1981.  
**Meets JIS 1989, DIN.  
Motor Calibration: calb  
AL (Alarm Mode): al  
Designate whether or not to perform motor calibration. To enter the  
mode, simultaneously press the Up and Down Keys for at least one  
second. Press the Display Key to return to sl–l.  
Whenal is displayed on the PV display in level 2, alarm output mode  
or the present setting of the corresponding alarm mode selector  
(SW205) is displayed on the SV display. The following table shows  
the messages that may be displayed.  
WARNING  
Never calibrate the motor during control operation. Make sure  
that control operations have been stopped before calibrating.  
Display  
Alarm mode  
No alarm  
No display  
fr–h  
fr–l  
mot  
Fully open position  
Fully closed position  
Opening/closing time  
Upper- and lower-limit alarm  
Upper-limit alarm  
)––(  
–––(  
)–––  
–()–  
The motor is calibrated. Refer to page 9.  
Level 2  
Lower-limit alarm  
In level 2, selected input sensor, and modes for alarm output can be  
monitored. Note that level 2 is a monitoring level only and thus no  
parameters can be changed. When the Level Key is pressed for 2  
seconds minimum after power application, 5l–l is displayed on the  
PV display. Hold down the Level Key again for 2 seconds minimum  
to display o on the PV display. Then, selected input sensor, and  
alarm modes can be monitored each time the Display Key is  
pressed.  
Upper- and lower-limit range  
alarm  
Upper- and lower-limit alarms  
with standby sequence  
3––e  
–––e  
3–––  
1––c  
Upper-limit alarm with standby  
sequence  
Lower-limit alarm with standby  
sequence  
Absolute-value alarm  
Input type  
Alarm mode  
–––(  
Press a.  
10  
E5AX-P  
E5AX-P  
Starting Control Operation  
The E5AX will start control operations as soon as power is turned on  
until power is turned off. If you don’t want control operations to be  
performed while setting parameters, turn off the power and then turn  
it back on after setting the desired parameters.  
Previous PID  
constants  
New PID constants  
Main setting  
Auto-tuning  
When the Level Key and Mode Key are pressed at the same time for  
1 second minimum, the Temperature Controller automatically starts  
tuning the PID constants. While auto-tuning is in operation, the au-  
to-tuning indicator on the front panel will flash. The Temperature  
Controller executes control based on the set PID constants (factory  
set to P = 40%C, I = 240 seconds, and D = 40 seconds) until the tem-  
perature of the controlled system reaches the set temperature. After  
that, the Temperature Controller automatically adjusts the PID con-  
stants using the limit cycle method. When the auto-tuning indicator  
turns off, the auto-tuning is terminated and PID constants are re-  
newed.  
AT indicator flashes  
Limit Cycle Method: the optimum PID constants are calculated by  
this method by varing the control output variable and generating ex-  
ternal oscillation.  
Auto-tuning can be carried out regardless of whether the Tempera-  
ture Controller is performing reverse (heating) or normal (cooling)  
operation. To stop auto-tuning, hold down the Level Key and Mode  
Key again simultaneously for 1 second minimum. All settings will re-  
turn to those prior to the beginning of auto-tuning. Automatic tuning  
can be executed at any time: at power application, while the temper-  
ature is rising, or after the control action has stabilized.  
Error Messages  
The Temperature Controller is provided with self-diagnostic functions, and will display an error message on the PV display when an error is  
detected.  
Message  
Cause  
Control output  
Normal Reverse  
Open: ON  
Alarm output  
Input temperature has exceeded the upper  
limit of the temperature range by more than  
20%C.  
Open: OFF  
Close: ON  
Sends alarm signal in ac-  
cordance with the set  
alarm mode.  
ffff  
Close: OFF  
Input temperature has fallen below the lower  
limit of the temperature range by more than  
20%C.*  
Open: ON  
Close: OFF  
Open: OFF  
Close: ON  
Sends alarm signal in ac-  
cordance with the set  
alarm mode.  
––––  
The thermocouple has burned out or  
Open: OFF  
Open: ON  
Close: OFF  
Sends alarm signal in ac-  
cordance with the set  
alarm mode. Proportional  
alarm output is OFF, how-  
ever.  
5.err (flashes)  
short-circuit bar has been removed. The plati- Close: ON  
num resistance thermometer has burned out  
or A and B terminals have been short-cir-  
cuited.  
Memory failure (e111) or A/D converter failure Open: OFF  
Open: OFF  
Close: OFF  
OFF  
e111 (flashes)  
e333 (flashes)  
(e333) has occurred. Temperature Controller  
must be repaired if recovery is not made by  
turning power off once and on again.  
Close: OFF  
*When the temperature resistance thermometer is used, this message is displayed when the temperature has fallen below -99.9%C.  
11  
E5AX-P  
E5AX-P  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
12  
11 5  
_96  
89  
Mounting  
Screw  
2 to 10  
RS-422 RS-485  
4 to 20 mA  
transmission output  
RDB  
RDA  
SG  
SG  
SDA  
SDB  
Communications connector  
(RS-232C and BCD connector is shown.) (RS-422 and 485 terminals are shown.)  
Communications board  
Communications board  
(4 to 20 mA transmission output is shown.)  
Panel Cutout  
Side-by-side Mounting  
of N Controllers  
92+00.8  
L
92+00.8  
92+00.8  
+1  
L = (96N – 3.5)  
120 min.  
0
Installation  
Open  
Close  
Control  
output  
Ground FG terminal 18 under  
noise-interfered environment.  
100 to 240 VAC, 50/60 Hz  
Alarm output  
Use these terminals when connecting a platinum  
resistance thermometer (remove short bar from  
terminals 14 and 15).  
Potentiometer  
input  
(see Note 1)  
Use these terminals when connecting a thermo-  
couple (do not remove short bar from terminals  
14 and 15).  
Note: 1. Connect a valve position indicator if required.  
2. Do not connect unused terminals.  
12  
E5AX-P  
E5AX-P  
Precautions  
Mounting  
Stickers Inside Frontcover  
Stickers indicating the temperature sensor type (R, S, K, J, T, E, L,  
and U) are supplied with the Temperature Controller. Attach the  
proper stickers to the front panel as shown below.  
The dimensions of the Temperature Controller conform to DIN  
43700. Recommended panel thickness is 1 to 8 mm.  
Do not install the Temperature Controller in a location exposed to  
excessive dust or corrosive gases. Moreover, avoid locations sub-  
ject to heavy vibration or shock, water or oil spray, or high tempera-  
tures. Any of these condition will affect product life.  
Isolate the Temperature Controller from equipment that generates  
strong, high-frequency noises such as high-frequency welders, be-  
cause such equipment may prevent proper operation.  
Attach the two mounting brackets supplied with E5AX on the top  
and bottom of the Temperature Controller. Tighten the screws of the  
mounting brackets with your fingers.  
Mounting bracket  
Sticker identifying input type  
Connection Examples  
With Solderless Terminal  
Use M3.5 solderless terminals with the Temperature Controller’s  
M3.5 self-rising pressure plate screws.  
Solder-dipped Leads  
Strip 6 to 12 mm of the lead wires and carefully arrange the wire tips.  
Do not tighten the terminal screw with excessive force, because do-  
ing so may damage them. The terminal block of the Temperature  
Controller is constructed so that the lead wires can be connected to  
all the terminals from the same direction.  
Top  
Bottom  
Input Connection  
To reduce inductive noise influence, the lead wires connecting the  
input to the Temperature Controller must be separated from the  
power lines and load lines.  
Use the specified compensating conductors for thermocouples.  
When using a thermocouple as the temperature sensor, attach the  
short-circuit bar shown in the terminal block diagram on the hous-  
ing. Use lead wires having a small resistance for temperature resis-  
tance thermometers.  
Be sure to remove the short-circuit bar from the terminals when a  
temperature resistance thermometer is used.  
Sequenced Circuits  
Several seconds are required until the relay in turned ON after pow-  
er has been supplied to the Temperature Controller. Therefore, take  
this time delay into consideration when designing sequenced cir-  
cuits which incorporate a Temperature Controller.  
13  
E5AX-P  
E5AX-P  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
Cat. No. H54-E1-1A In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Temperature Control Devices Division  
29th Fl., Crystal Tower Bldg.  
1-2-27, Shiromi, Chuo-ku,  
Printed in Japan  
0791-1M  
Osaka 540 Japan  
Phone: 06-949-6070 Fax: 06-949-6084  
14  

相关型号:

E5AX-PRR02

Temperature Controller
OMRON

E5AX-PRR03

Temperature Controller
OMRON

E5AX-PRR20

Temperature Controller
OMRON

E5AX-PRRF

Temperature Controller
OMRON

E5AX-PRRM

Temperature Controller
OMRON

E5AZ-C3ML

Digital Temperature Controllers
OMRON

E5AZ-C3MLD

Digital Temperature Controllers
OMRON

E5AZ-C3MT

Digital Temperature Controllers
OMRON

E5AZ-C3MTD

Digital Temperature Controllers
OMRON

E5AZ-C3T

Digital Temperature Controllers
OMRON

E5AZ-Q3HML

Digital Temperature Controllers
OMRON

E5AZ-Q3HMLD

Digital Temperature Controllers
OMRON