G3NA-225B-AC200-240
更新时间:2024-09-18 18:17:59
品牌:OMRON
描述:Trigger Output SSR, 1-Channel, 2500V Isolation,
G3NA-225B-AC200-240 概述
Trigger Output SSR, 1-Channel, 2500V Isolation, 固态继电器
G3NA-225B-AC200-240 规格参数
是否Rohs认证: | 符合 | 生命周期: | Obsolete |
Reach Compliance Code: | unknown | HTS代码: | 8541.40.95.00 |
风险等级: | 5.82 | 其他特性: | UL RECOGNIZED, WITH ZERO CROSSOVER CIRCUIT |
配置: | SINGLE | 最大绝缘电压: | 2500 V |
元件数量: | 1 | 最大通态电流: | 4 A |
最高工作温度: | 80 °C | 最低工作温度: | -30 °C |
光电设备类型: | TRIGGER OUTPUT SSR | Base Number Matches: | 1 |
G3NA-225B-AC200-240 数据手册
通过下载G3NA-225B-AC200-240数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载Solid State Relay
G3NA
■ All models feature the same compact dimensions to
provide a uniform mounting pitch
■ Built-in varistor effectively absorbs external surges
■ Operation indicator (red LED) enables monitoring
operation
■ Protective cover for greater safety
■ All models approved by UL/CSA; TUV approved
models available
■ Wide range of outputs: 5 to 40 A, up to 480 VAC/
200 VDC
■ Optional Y92B heat sinks allow relays to reach
maximum rated loads
■ 25-amp version ideal for many industrial control
applications
Ordering Information
Zero cross
function
Rated input
voltage
Part number
Isolation
Applicable output load
With indicator
Phototriac
5 A at 24 to 240 VAC
(see note 1)
Yes
5 to 24 VDC
G3NA-205B-DC5-24
G3NA-205B-AC100-120
G3NA-205B-AC200-240
G3NA-210B-DC5-24
G3NA-210B-AC100-120
G3NA-210B-AC200-240
G3NA-410B-DC5-24
G3NA-410B-AC100-240
G3NA-D210B-DC5-24
G3NA-D210B-AC100-240
G3NA-220B-DC5-24
G3NA-220B-AC100-120
G3NA-220B-AC200-240
G3NA-420B-DC5-24
G3NA-420B-AC100-240
G3NA-225B-DC5-24
G3NA-225B-AC100-120
G3NA-225B-AC200-240
G3NA-425B-DC5-24
G3NA-425B-AC100-240
G3NA-240B-DC5-24
G3NA-240B-AC100-120
G3NA-240B-AC200-240
G3NA-440B-DC5-24
G3NA-440B-AC100-240
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
10 A at 24 to 240 VAC
(see note 1)
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
Photocoupler
Phototriac
10 A at 200 to 480 VAC
(see note 1)
100 to 240 VAC
5 to 24 VDC
10 A at 5 to 200 VDC
No
100 to 240 VAC
5 to 24 VDC
20 A at 24 to 240 VAC
(see note 1)
Yes
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
Photocoupler
Phototriac
20 A at 200 to 480 VAC
(see note 1)
100 to 240 VAC
5 to 24 VDC
25 A at 24 to 240 VAC
(see note 1)
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
Photocoupler
Phototriac
25 A at 200 to 480 VAC
(see note 1)
100 to 240 VAC
5 to 24 VDC
40 A at 24 to 240 VAC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
Photocoupler
40 A at 200 to 480 VAC
(see note 1)
100 to 240 VAC
NOTE: 1. Loss time increases under 75 VAC (Refer to "Precautions Section").
2. To order TUV approved versions, contact your local OMRON representative.
G3NA
G3NA
■ ACCESSORIES
Heat Sinks
Types
Applicable solid-state relays
Part number
Y92B-A100
Y92B-A150N
Y92B-A250
Y92B-N50
Standard mount
G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-220B, G3NA-410B, G3NA-420B
G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B
G3NA-440B
Track mount
G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B
G3NA-220B, G3NA-420B
Y92B-N100
Y92B-N150
G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B
Mounting Track and Accessories
Description
Part number
R99-11
Mounting bracket for G3NA-240B. Changes pitch to 56 mm (2.21 in.) from 47.5 mm (1.73 in.),
the same pitch as G3N-240B.
DIN Rail Track, 50 cm (1.64 feet) length; use with Y92B-N■■■heat sinks
PFP-50M
PFP-100M
PFP-S
DIN Rail Track, 1 m (3.28 feet) length; use with Y92B-N■■■heat sinks
Spacer
End cap
PFP-M
Specifications
■ INPUT RATINGS
(Ambient temperature: 25°C [77°F])
Rated
Operating
Voltage Level
Type
voltage
voltage range
Impedance
Must operate voltage
Must release voltage
1 VDC min.
G3NA-2■■B
5 to 24 VDC
4 to 32 VDC
7 mA max. (see note 2) 4 VDC max.
36 kΩ ±20% 75 VAC, max. (see note 3)
200 to 240 VAC 150 to 264 VAC 72 kΩ ±20% 150 VAC max. (see note 3)
5 to 24 VDC 4 to 32 VDC 5 mA max. (see note 2) 4 VDC max.
100 to 240 VAC 75 to 132 VAC 72 kΩ ±20% 75 VAC max.
5 to 24 VDC 4 to 32 VDC 5 mA max. (see note 2) 4 VDC max.
100 to 240 VAC 75 to 132 VAC 72 kΩ ±20% 75 VAC max.
100 to 120 VAC 75 to 132 VAC
20 VAC min. (see note 3)
40 VAC min. (see note 3)
1 VDC min.
G3NA-4■■B
20 VAC min.
G3NA-D210B
1 VDC min.
20 VAC min.
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at
100 to 120 VAC, the input impedance is measured at 120 VAC).
2. With constant current input circuit system.
3. Refer to the "Characteristic Data" for further details.
■ OUTPUT RATINGS
Applicable load
Rated
load voltage
Load
voltage range
Load current
With heat sink*
0.1 to 5 A
Type
Without heat sink
0.1 to 3 A
0.1 to 4 A
0.2 to 4 A
0.1 to 4 A
0.2 to 4 A
0.1 to 4 A
0.1 to 4 A
0.1 to 6 A
0.2 to 6 A
0.1 to 4 A
Surge current
G3NA-205B
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
G3NA-225B
G3NA-425B
G3NA-240B
G3NA-440B
G3NA-D210B
24 to 240 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
5 to 200 VDC
19 to 264 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
4 to 220 VDC
60 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
20 A (10 ms)
0.1 to 10 A
0.2 to 10 A
0.1 to 20 A
0.2 to 20 A
0.1 to 25 A
0.1 to 25 A
0.1 to 40 A
0.2 to 40 A
0.1 to 10 A
*When the appropriate size OMRON heat sink is used.
2
G3NA
G3NA
■ CHARACTERISTICS
G3NA-205B, -210B,
-220B, -225B
G3NA-410B, -420B,
-425B, -440B
Type
G3NA-240B
G3NA-D210B
Operate time
DC input
1/2 of load power source cycle + 1 ms max.
1 1/2 of load power source cycle + 1 ms max.
1/2 of load power source cycle + 1 ms max.
1 1/2 of load power source cycle + 1 ms max.
1 ms max.
30 ms max.
5 ms max.
30 ms max.
1.5 V max.
AC input
DC input
AC input
Release time
Output ON voltage drop
Leakage current
1.6 V (RMS) max.
1.6 V (RMS) max.
1.8 V (RMS max.)
5 mA max. at 100 VAC
10 mA max.
at 200 VAC
5 mA max.
at 200 VDC
10 mA max. at 200 VAC
20 mA max. at 400 VAC
Insulation resistance
Dielectric strength
Vibration
100 MΩ min at 500 VDC
2,500 VAC, 50/60 Hz for 1 minute
10 to 55 Hz, 1.5 mm double amplitude
1,000 m/s2 (approx. 100G)
Malfunction
Malfunction
Operating
Storage
Shock
Ambient temperature
-30° to 80°C (-22° to 176°F) with no icing
-30° to 100°C (-22° to 212°F) with no icing
45% to 85% RH
Humidity
Weight
Approx. 60 g (2.1 oz.)
Approx. 70 g (2.5 oz.)
Approx. 80 g (2.8 oz.) Approx. 70 g (2.5 oz.)
Note: Data shown are of initial value.
■ CHARACTERISTIC DATA
Load Current vs. Ambient Temperature Characteristics
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
G3NA-205B
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
G3NA-225B
G3NA-425B
G3NA-240B
G3NA-440B
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
3
G3NA
G3NA
■ CHARACTERISTIC DATA (continued)
Load Current vs. Ambient Temperature Characteristics
G3NA-D210B
Ambient temperature (°C)
Surge Current Resistivity
G3NA-210B
G3NA-410B
G3NA-220B, G3NA-225B,
G3NA-420B, G3NA-425B
G3NA-205B
Energizing time (ms)
Energizing time (ms)
Energizing time (ms)
G3NA-240B
G3NA-440B
G3NA-D210B
Energizing time (ms)
Energizing time (ms)
4
G3NA
G3NA
Temperature Characteristics
(with must operate voltage and
must release voltage)
Heat Sink Size vs. Load Current
G3NA-220B
G3NA-2■■B AC input
Ambient temperature (°C)
Load current (A)
Note: The heat sink size refers to the combined area of the sides of the heat sink that radiate heat. For example, when a current of
18 A is allowed to flow through the SSR at 40°C, the graph shows that the heat sink size is about 450 cm2. Therefore, if the
heat sink is square, one side of the heat sink must be 15 cm (152 x 2 = 450) or longer.
Dimensions
Unit: mm (inch)
■ SOLID-STATE RELAYS
G3NA-205B, G3NA-210B, G3NA-220B,
G3NA-225B, G3NA-410B,
G3NA-420B, G3NA-425B
Terminal arrangement/
Internal connections
(Top view)
Mounting holes
(Bottom view)
Four -
M4 x 10 (0.39)
4.5 (0.18) dia.
Two,
Load
Load
(
4.4 (0.17) dia. or M4
power
supply
Load
1
2
47.6 ± 0.2
(1.87 ± 0.01)
(-)
4
(+)
3
13.8 (0.54)
25 (0.98) max.
27 (1.06) max.
Input
43 (1.69) max.
G3NA-240B, G3NA-440B
Terminal arrangement/
Internal connections
(Top view)
Mounting holes
(Bottom view)
4.5 (0.18) dia.
Two,
M5 x 12 (0.47)
Two,
58
(2.28)
min.
Load
Load
4.4 (0.17) dia. or M4
44
(1.73)
power
supply
47.5
(1.87)
Load
1
2
47.6 ± 0.2
(1.87 ± 0.01)
Operation
indicator
(-)
4
(+)
3
Two,
M4 x 10
(0.39)
Input
4.5 (0.18)
25 (0.98)
13.8 (0.54)
25 (0.98) max.
43 (1.69) max.
27 (1.06) max.
5
G3NA
G3NA
Unit: mm (inch)
■ SOLID-STATE RELAYS (continued)
G3NA-D210B
Terminal arrangement/
Internal connections
(Top view)
Mounting holes
(Bottom view)
Four,
M4 x 10 (0.39)
4.5 (0.18) dia.
Two,
Load
Load
58
4.4 (0.17) dia. or M4
(2.28)
max.
44
(1.73)
power
supply
Load
47.5
(1.87)
1
-
2
+
47.6 ±
(1.87 ±
Operation
indicator
(-)
4
(+)
3
Input
4.5 (0.18)
25 (0.98)
13.8 (0.54)
25 (0.98) max.
43 (1.69) max.
27 (1.06) max.
■ HEAT SINKS
Track Mount Heat Sink – Y92B-N50
Mounting holes
(Top view)
Two, M3 holes
4.6 (0.18) dia.
Two, 3.2 (0.13) dia. holes
Two, M4 holes
47
(1.85)
max.
44
(1.73)
max.
Two, 4.4 (0.17) dia.
or M4 holes
35
(1.38)
30
(1.18)
30.5 ± 0.3
(1.20 ± 0.01)
35 ± 0.2
(1.38 ± 0.01)
5.6
(0.22)
5
4.5 (0.18)
(0.20)
6 (0.24)
47.6 (1.87)
90 ± 0.4
77 (3.03) max.
90 ± 0.3 (3.54 ± 0.01)
100 (3.94) max.
51 (2.01) max.
(3.54 ± 0.02)
Weight: approx. 200 g (7 oz.)
Track Mount Heat Sink – Y92B-N100
Mounting holes
(Top view)
Two, M3 holes
Two, 3.2 (0.13) dia. holes
Two, M4 holes
4.6 (0.18) dia.
71
(2.80)
max.
Two, 4.4 (0.17) dia.
or M4 holes
74
(2.91)
max.
35
(1.38)
30 (1.18)
35 ± 0.2
(1.38 ± 0.01)
30.5 ± 0.3
(1.20 ± 0.01)
5 (0.20)
28
(1.10)
4.5 (0.18)
5.6
(0.22)
90 ± 0.4
(3.54 ± 0.02)
13 (0.51)
100 (3.94) max.
47.6 (1.87)
77 (3.03) max.
90 ± 0.3 (3.54 ± 0.01)
Weight: approx. 400 g (14 oz.)
100 (3.94) max.
6
G3NA
G3NA
Track Mount Heat Sink – Y92B-N150
Mounting holes
(Top view)
47.6
(1.87)
Two, 3.2 (0.13) dia. holes
Two,
M4 holes
4.6 (0.18) dia.
100
(3.94)
max.
Two, 4.4 (0.17) dia.
or M4 holes
104
(4.09)
max.
35
(1.38)
30 (1.18)
35 ± 0.2
(1.38 ± 0.01)
90 ± 0.4
(3.54 ± 0.02)
5 (0.20)
28
56 ± 0.3
(2.21 ± 0.01)
5.6
(0.22)
4.5 (0.18)
(1.10)
13 (0.51)
77 (3.03) max.
90 ± 0.3 (3.54 ± 0.01)
100 (3.94) max.
Weight: approx. 560 g (20 oz.)
100 (3.94) max.
Standard Mount Heat Sinks
Y92B-A100
Y92B-A150
Mounting holes
Y92B-A100,Y92B-A150N
Y92B-A250
Three, M4 holes
Four, 4.4 (0.17) dia.
or M4 holes
90 ± 0.1
(3.54 ± 0.004)
90 ± 0.1
(3.54 ± 0.004)
R2.2
(0.09)
47.6 (1.87)
90 ± 0.1
(3.54 ± 0.004)
50 ± 0.1 (1.97 ± 0.004)
56 ± 0.5 (2.21 ± 0.02)
50 ± 0.1
(1.97 ± 0.004)
100 (3.93) max.
150 (5.91) max.
Standard Mount Heat Sinks
Y92B-A250
Mounting holes
Three, M4 holes
Four, 4.4 (0.17) dia.
or M4 holes
80.5
(3.17)
max.
90 ± 0.1
(3.54 ± 0.004)
90 ± 0.1
(3.54 ± 0.004)
1.5
(0.06)
100.5
(3.94)
max.
R2.2
(0.09)
47.6 (1.87)
9.6 (0.38)
2 (0.08)
1.5
(0.06)
50 ± 0.1
(1.97 ± 0.004)
50 ± 0.1 (1.97 ± 0.004)
56 ± 0.5 (2.21 ± 0.02)
250 (9.84) max.
30 (1.18)
45.5 (1.79) max.
R99-11 Mounting Bracket for G3NA-240B
16 (0.63)
8 (0.32)
12.5
(0.49)
5
(0.20)
56
(2.21)
21
(0.83)
Note: Use mounting bracket R99-11 to mount the
G3NA-240B with a pitch of 56 mm (2.21 in)
instead of 47.5 mm (1.87 in) to match the pitch
of G3N-240B.
4 (0.16)
4.6 (0.18)
7
G3NA
G3NA
■ APPROVALS
UL (File No. E64562)/CSA (File No. LR35535)
Contact ratings
SSR type
Input voltage
5 to 24 VDC
Load type
Without heat sink
With heat sink (see note 1)
G3NA-205B
General use/Tungsten
Motor
3 A, 240 VAC
5 A, 240 VAC
100 to 120 VAC
200 to 240 VAC
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
10 A, 240 VAC
G3NA-210B
G3NA-220B
G3NA-225B
G3NA-240B
G3NA-410B
G3NA-420B
G3NA-425B
G3NA-440B
G3NA-D210B
General use/Tungsten
Motor
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
5 FLA, 30 LRA, 240 VAC
20 A, 240 VAC
General use/Tungsten
Motor
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
10 FLA, 60 LRA, 240 VAC
25 A, 240 VAC
General use/Tungsten
Motor
2.5 FLA, 15 LRA, 240 VAC
6 A, 240 VAC
12 FLA, 72 LRA, 240 VAC
40 A, 240 VAC
General use/Tungsten
Motor
5 FLA, 30 LRA, 240 VAC
4 A, 480 VAC
20 FLA, 120 LRA, 240 VAC
10 A, 480 VAC
5 to 24 VDC
General use/Tungsten
Motor
100 to 240 VAC
2.5 FLA, 15 LRA, 480 VAC
4 A, 480 VAC
5 FLA, 30 LRA, 480 VAC
20 A, 480 VAC
General use/Tungsten
Motor
2.5 FLA, 15 LRA, 480 VAC
4 A, 480 VAC
10 FLA, 60 LRA, 480 VAC
25 A, 480 VAC
General use/Tungsten
Motor
2.5 FLA, 15 LRA, 480 VAC
6 A, 480 VAC
12 FLA, 72 LRA, 480 VAC
40 A, 480 VAC
General use/Tungsten
Motor
5 FLA, 30 LRA, 480 VAC
4 A, 200 VDC
20 FLA, 120 LRA, 480 VAC
10 A, 200 VDC
General use
Note: 1. When used with the proper OMRON heat sink part number or an appropriately dimensioned equivalent.
2. The rated values approved by each of the safety standards (e.g., UL, CSA, and TUV) may be different from the performance
characteristics individually defined in this catalog.
3. In the interest of product improvement, specifications are subject to change.
Installation
Close Mounting
Heat Sink Mounting
When mounting solid-state relays (SSRs) side by side, provide
a space equivalent to the width of a single SSR between two
adjacent SSRs. Otherwise, reduce the current flow to 1/2 to
1/3 of the rated current
To mount an SSR in a heat sink, first apply a heat conductive
grease to the metal back surface of the SSR. Press the SSR
firmly onto the heat sink to ensure a good seal. Screw the
SSR down to the heat sink.
Next, wire the screw terminals and securely tighten the screws.
8
G3NA
G3NA
Precautions
■ LOAD CONNECTION
■ ZERO CROSS FUNCTION
Before connecting a load that generates a high surge current,
such as a lamp load, to the SSR, make sure that the SSR can
withstand the surge current of the load.
An SSR with a zero cross function operates when an AC load
voltage reaches the zero point or its vicinity. This reduces
clicking noises when the load is input, and minimizes the
influence of an inductive load, such as a lamp, heater, or
motor, on the power supply because the inrush current of the
load is reduced. This can also minimize the scale of the surge
current protection circuit.
OMRON's data sheet shows the non-repetitive peak value of
the surge current that flows through the SSR. Normally, use
1/2 the non-repetitive peak surge current as the standard
value. If a surge current exceeding that value is expected,
connect a quick-blowing fuse to protect the SSR.
For an AC load, use a power supply rated at 50 or 60 Hz. The
maximum operating frequency is 10 Hz. The G3NA has a
built-in varistor for over-voltage protection.
Half-wave rectifier loads
If the SSR is not provided with a zero cross function, a half-
wave rectifier load can be switched with no problem. If the
SSR is equipped with a zero cross function, allow about 20%
of the load current to flow through the SSR.
■ LIFE EXPECTANCY (MTTF)
The mean time to failure (MTTF) for most SSRs is 100,000
hours. This, however, varies with the operating conditions. To
ensure long life and stable operation of SSRs, plan for a
constant operating environment, especially when the
equipment incorporating SSRs is used under severe
conditions such as high operating temperature, fluctuations in
temperature, or continuous energizing.
Note: Connect bleeder resistor R.
Varistor
Low-capacity loads
Use the following elements for surge absorption:
Operating
voltage
Varistor
voltage
Surge
resistance
Note: Connect bleeder resistor R.
100 to 120 VAC
200 to 240 VAC
380 to 480 VAC
240 to 270 V
440 to 470 V
820 to 1,000 V
1,000 A min.
Capacitive loads
The supply voltage plus the charge voltage of the capacitor is
applied to both ends of the SSR when it is OFF. Therefore,
use an SSR model with an input voltage rating twice the size
of the supply voltage.
The applied voltage should be carefully determined before
use, because the loss time for the output signal increases if
the applied voltage and current are low.
Limit the charge current of the capacitor to less than half the
peak surge current value allowed for the SSR.
For a DC or L load, a diode should be connected in parallel to
the load to absorb the counter electromotive force of the load.
9
G3NA
G3NA
OMRON ELECTRONICS, INC.
One East Commerce Drive
Schaumburg, IL 60173
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC RLY6
9/97
Specifications subject to change without notice.
Printed in the U.S.A.
10
G3NA-225B-AC200-240 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
G3NA-225B-UTU-100TO120VAC | OMRON | Trigger Output SSR, 1-Channel | 获取价格 | |
G3NA-225B-UTU-5TO24VDC | OMRON | Trigger Output SSR, 1-Channel | 获取价格 | |
G3NA-240B | OMRON | Solid State Relay | 获取价格 | |
G3NA-240B-5TO24VDC | OMRON | Trigger Output SSR, 1-Channel, 2500V Isolation | 获取价格 | |
G3NA-240B-AC200-240 | OMRON | Trigger Output SSR, 1-Channel, 2500V Isolation, | 获取价格 | |
G3NA-240B-DC5-24 | OMRON | Trigger Output SSR, 1-Channel, 2500V Isolation, | 获取价格 | |
G3NA-240B-TUV | OMRON | Trigger Output SSR, 1-Channel, 2500V Isolation | 获取价格 | |
G3NA-240B-UTU | OMRON | 暂无描述 | 获取价格 | |
G3NA-240B-UTU-100TO120VAC | OMRON | Trigger Output SSR, 1-Channel | 获取价格 | |
G3NA-240B-UTU-5TO24VDC | OMRON | Trigger Output SSR, 1-Channel | 获取价格 |
G3NA-225B-AC200-240 相关文章
- 2024-09-20
- 6
- 2024-09-20
- 9
- 2024-09-20
- 8
- 2024-09-20
- 6