G3PE-515BDC12-24 [OMRON]

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4;
G3PE-515BDC12-24
型号: G3PE-515BDC12-24
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4

文件: 总6页 (文件大小:579K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Solid State Relays for Heaters  
G3PE-Single-phase  
CSM_G3PE-Single-phase_DS_E_2_1  
Compact, Slim-profile SSRs with Heat  
Sinks. Models with No Zero Cross for  
a Wide Range of Applications.  
• RoHS compliant.  
• Models also available with no zero cross  
• Surge pass protection improved surge dielectric strength for  
output currents. (OMRON testing)  
• Compact with a slim profile.  
• Mount to DIN Track or with screws.  
• Conforms to UL, CSA, and EN standards (TÜV certification).  
Refer to Safety Precautions for All G3PE  
Models.  
Ordering Information  
List of Models  
Number of  
phases  
Insulation  
method  
Operation  
indicator  
Rated input  
voltage  
Zero cross  
function  
Applicable load *  
Model  
15 A, 100 to 240 VAC G3PE-215B DC12-24  
25 A, 100 to 240 VAC G3PE-225B DC12-24  
35 A, 100 to 240 VAC G3PE-235B DC12-24  
45 A, 100 to 240 VAC G3PE-245B DC12-24  
15 A, 100 to 240 VAC G3PE-215BL DC12-24  
25 A, 100 to 240 VAC G3PE-225BL DC12-24  
35 A, 100 to 240 VAC G3PE-235BL DC12-24  
45 A, 100 to 240 VAC G3PE-245BL DC12-24  
15 A, 200 to 480 VAC G3PE-515B DC12-24  
25 A, 200 to 480 VAC G3PE-525B DC12-24  
35 A, 200 to 480 VAC G3PE-535B DC12-24  
45 A, 200 to 480 VAC G3PE-545B DC12-24  
15 A, 200 to 480 VAC G3PE-515BL DC12-24  
25 A, 200 to 480 VAC G3PE-525BL DC12-24  
35 A, 200 to 480 VAC G3PE-535BL DC12-24  
45 A, 200 to 480 VAC G3PE-545BL DC12-24  
Yes  
No  
Phototriac  
coupler  
Single-phase  
Yes (yellow)  
12 to 24 VDC  
Yes  
No  
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering  
Data on page 3.  
1
G3PE-Single-phase  
Specifications  
Certification  
UL508, CSA22.2 No.14, and EN60947-4-3  
Ratings  
Input (at an Ambient Temperature of 25°C)  
Item  
Rated voltage  
Model  
Voltage level  
Operating voltage  
range  
Rated input current  
Must operate voltage  
Must release voltage  
G3PE-@@@B  
7 mA max.  
12 to 24 VDC  
9.6 to 30 VDC  
9.6 VDC max.  
1.0 VDC max.  
G3PE-@@@BL  
15 mA max.  
Output  
Model  
G3PE-215B(L) G3PE-225B(L) G3PE-235B(L) G3PE-245B(L) G3PE-515B(L) G3PE-525B(L) G3PE-535B(L) G3PE-545B(L)  
Item  
Rated load voltage  
Load voltage range  
100 to 240 VAC (50/60 Hz)  
75 to 264 VAC (50/60 Hz)  
200 to 480 VAC (50/60 Hz)  
180 to 528 VAC (50/60 Hz)  
Applicable load current  
0.1 to 15 A  
(at 40°C)  
0.1 to 25 A  
(at 40°C)  
0.5 to 35 A  
(at 25°C)  
0.5 to 45 A  
(at 25°C)  
0.1 to 15 A  
(at 40°C)  
0.1 to 25 A  
(at 40°C)  
0.5 to 35 A  
(at 25°C)  
0.5 to 45 A  
(at 25°C)  
*
150 A  
(60 Hz,  
1 cycle)  
220 A  
(60 Hz,  
1 cycle)  
150 A  
(60 Hz,  
1 cycle)  
220 A  
(60 Hz,  
1 cycle)  
Inrush current  
resistance  
440 A  
(60 Hz, 1 cycle)  
440 A  
(60 Hz, 1 cycle)  
Permissible I2t  
(reference value)  
121A2s  
260A2s  
1,260A2s  
128A2s  
1,350A2s  
6,600A2s  
Applicable load  
(resistive load)  
3 kW  
(at 200 VAC)  
5 kW  
(at 200 VAC)  
7 kW  
(at 200 VAC)  
9 kW  
(at 200 VAC)  
6 kW  
(at 400 VAC)  
10 kW  
(at 400 VAC)  
14 kW  
(at 400 VAC)  
18 kW  
(at 400 VAC)  
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering  
Data on page 3.  
Characteristics  
Model  
G3PE  
-215B  
G3PE  
-225B  
G3PE  
-235B  
G3PE  
-245B  
G3PE  
-215BL  
G3PE  
-225BL  
G3PE  
-235BL  
G3PE  
-245BL  
Item  
Operate time  
Release time  
1/2 of load power source cycle + 1 ms max.  
1/2 of load power source cycle + 1 ms max.  
1 ms max.  
Output ON voltage drop 1.6 V (RMS) max.  
Leakage current  
10 mA max. (at 200 VAC)  
Insulation resistance  
Dielectric strength  
Vibration resistance  
Shock resistance  
100 MΩ min. (at 500 VDC)  
2,500 VAC, 50/60 Hz for 1 min  
10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track)  
Destruction: 294 m/s2 (Mounted to DIN track)  
Ambient storage  
temperature  
30 to 100°C (with no icing or condensation)  
30 to 80°C (with no icing or condensation)  
45% to 85%  
Ambient operating  
temperature  
Ambient operating  
humidity  
Weight  
Approx. 240 g  
Approx. 400 g  
Approx. 240 g  
Approx. 400 g  
Model  
Item  
G3PE  
-515B  
G3PE  
-525B  
G3PE  
-535B  
G3PE  
-545B  
G3PE  
-515BL  
G3PE  
-525BL  
G3PE  
-535BL  
G3PE  
-545BL  
Operate time  
Release time  
1/2 of load power source cycle + 1 ms max.  
1/2 of load power source cycle + 1 ms max.  
1 ms max.  
Output ON voltage drop 1.8 V (RMS) max.  
Leakage current  
20 mA max. (at 480 VAC)  
Insulation resistance  
Dielectric strength  
Vibration resistance  
Shock resistance  
100 MΩ min. (at 500 VDC)  
2,500 VAC, 50/60 Hz for 1 min  
10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track)  
Destruction: 294 m/s2 (Mounted to DIN track)  
Ambient storage  
temperature  
30 to 100°C (with no icing or condensation)  
30 to 80°C (with no icing or condensation)  
45% to 85%  
Ambient operating  
temperature  
Ambient operating  
humidity  
Weight  
Approx. 240 g  
Approx. 400 g  
Approx. 240 g  
Approx. 400 g  
2
G3PE-Single-phase  
Engineering Data  
Input Voltage vs. Input Impedance and Input Voltage vs. Input Current  
G3PE-2@@B  
G3PE-2@@BL  
G3PE-5@@B  
10  
9
8
7
6
5
4
3
2
1
0
15  
14  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
0
10  
9
8
7
6
5
4
3
2
1
0
Ta = 25°C  
Ta = 25°C  
Ta = 25°C  
Input current  
Input current  
Input current  
Input impedance  
Input impedance  
Input impedance  
0
5
10  
15  
20  
25  
30 35  
0
5
10  
15  
20  
25  
30 35  
0
5
10  
15  
20  
25  
30 35  
Input voltage (V)  
Input voltage (V)  
Input voltage (V)  
G3PE-5@@BL  
15  
14  
13  
12  
11  
10  
9
Ta = 25°C  
Input current  
8
7
6
5
4
Input impedance  
3
2
1
0
0
5
10  
15  
20  
25  
30 35  
Input voltage (V)  
Load Current vs. Ambient Temperature  
G3PE-215B(L), G3PE-225B(L)  
G3PE-515B(L), G3PE-525B(L)  
G3PE-235B(L), G3PE-245B(L)  
G3PE-535B(L), G3PE-545B(L)  
30  
50  
G3PE-245B(L)  
G3PE-545B(L)  
45  
40  
35  
30  
25  
G3PE-225B(L)  
G3PE-525B(L)  
G3PE-235B(L)  
20  
15  
G3PE-215B(L)  
G3PE-515B(L)  
G3PE-535B(L)  
20  
18  
17  
14  
10  
7
10  
0
0
30 20  
0
20  
40  
60  
80 100  
30 20  
0
20 25 40  
60  
80 100  
Ambient temperature (°C)  
Ambient temperature (°C)  
Inrush Current Resistance: Non-repetitive  
Keep the inrush current to below the inrush current resistance value (i.e., below the broken line) if it occurs repetitively.  
G3PE-215B(L), G3PE-515B(L)  
G3PE-225B(L), G3PE-525B(L)  
G3PE-235B(L), G3PE-245B(L)  
G3PE-535B(L), G3PE-545B(L)  
500  
250  
200  
250  
200  
400  
300  
200  
150  
100  
150  
100  
50  
0
50  
0
100  
0
10  
30 50 100  
300 500 1,000 3,000 5,000  
Energized time (ms)  
10  
30 50 100  
300 500 1,000 3,000 5,000  
Energized time (ms)  
10  
30 50 100  
300 500 1,000 3,000 5,000  
Energized time (ms)  
3
G3PE-Single-phase  
Close Mounting (3 or 8 SSRs)  
G3PE-215B(L)  
20  
G3PE-225B(L)  
30  
G3PE-235B(L)  
40  
G3PE-245B(L)  
50  
25  
3 Relays  
3 Relays  
40  
3 Relays  
8 Relays  
30  
28  
26  
15  
3 Relays  
20  
19  
13  
12  
31  
30  
29  
8 Relays  
20  
10  
15  
8 Relays  
20  
8 Relays  
10  
8
7
11  
10  
5.7  
5
11  
10  
5
0
0
0
0
40 20  
0
20  
40  
60  
80 100  
40 20  
0
20  
40  
60  
80 100  
40 20  
0
20  
40  
60  
80 100  
40 20  
0
20  
40  
60  
80 100  
25  
25  
Ambient temperature (°C)  
Ambient temperature (°C)  
Ambient temperature (°C)  
Ambient temperature (°C)  
G3PE-515B(L)  
G3PE-525B(L)  
G3PE-535B(L)  
G3PE-545B(L)  
20  
30  
50  
40  
25  
3 Relays  
40  
3 Relays  
30  
28  
26  
15  
3 Relays  
3 Relays  
20  
13  
12  
31  
30  
29  
17  
16  
15  
8 Relays  
20  
10  
8 Relays  
20  
8 Relays  
8 Relays  
10  
11  
10  
5.7  
5
7
11  
10  
6
5
0
0
0
0
40 20  
0
20 25 40  
60  
80 100  
40 20  
0
20  
40  
60  
80 100  
40 20  
0
20  
40  
60  
80 100  
40 20  
0
20 25 40  
60  
80 100  
Ambient temperature (°C)  
Ambient temperature (°C)  
Ambient temperature (°C)  
Ambient temperature (°C)  
Close Mounting Example  
DIN Track  
4
G3PE-Single-phase  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
Solid State Relays  
G3PE-215B(L)  
G3PE-225B(L)  
Two,  
4.6 dia.  
0.2  
13  
Two, M4  
G3PE-515B(L)  
G3PE-525B(L)  
100 max.  
0.2  
24  
68  
90  
84  
Two,  
M3.5  
4.6 × 5.6  
4.2  
6.3  
4.5  
elliptical hole  
22.5 max.  
Note: Without terminal cover.  
Note: With terminal cover.  
Mounting Holes  
Terminal Arrangement/Internal Circuit Diagram  
0.3  
13  
G3PE-5@@B  
G3PE-2@@B  
(+)  
A1  
(+)  
A1  
1
1
(100)  
(85)  
(90)  
0.3  
90  
A2  
A2  
2
2
) (  
) (  
Three, 4.5 dia.  
or M4  
0.2  
G3PE-235B(L)  
G3PE-245B(L)  
G3PE-535B(L)  
G3PE-545B(L)  
25  
4.6 dia.  
Two, M5  
100 max.  
68  
24  
0.2  
90  
84  
Two,  
M3.5  
4.6 × 5.6  
13.5  
6
elliptical hole  
44.5 max.  
Note: Without terminal cover.  
Note: With terminal cover.  
Mounting Holes  
Terminal Arrangement/Internal Circuit Diagram  
0.3  
25  
G3PE-5@@B  
G3PE-2@@B  
(+)  
A1  
(+)  
A1  
1
1
(100)  
(90)  
(85)  
0.3  
90  
A2  
A2  
2
2
) (  
) (  
Three, 4.5 dia.  
or M4  
5
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)  
from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS  
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT  
LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the products.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,  
safety equipment, and installations subject to separate industry or government regulations.  
·
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or  
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the  
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
2010.1  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2010 All Right Reserved.  

相关型号:

G3PE-515BLDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PE-525BDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PE-525BLDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PE-535BDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PE-535BLDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PE-545BDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PE-545BLDC12-24

Trigger Output SSR, 1-Channel, 2500V Isolation, ROHS COMPLIANT PACKAGE-4
OMRON

G3PF

Solid State Relays with Built-in Current Transformer
OMRON

G3PF-225B

Solid State Relays with Built-in Current Transformer
OMRON

G3PF-225B-CTB

Solid State Relays with Built-in Current Transformer
OMRON

G3PF-225B-STB

Solid State Relays with Built-in Current Transformer
OMRON

G3PF-235B

Solid State Relays with Built-in Current Transformer
OMRON