General Purpose Relay  
G7L  
• A high-capacity, high-withstand voltage relay compatible with  
momentary voltage drops.  
• No contact chattering for momentary voltage drops up to 50%  
of rated voltage.  
• UL Class B construction standard.  
• Wide-range AC-activated coil that handles 100 to 120 VAC at  
either 50 or 60 Hz.  
• Miniature hinge for maximum switching capacity, particularly  
for inductive loads.  
• Flame resistant materials (UL94V-0-qualifying) used for  
all insulation material.  
• Quick-connect, screw, and PCB terminals available.  
• Standard models are UL, CSA, and TUV approved; VDE  
versions now available.  
• Conforming to IEC 950.  
Ordering Information  
To Order: Select the part number and add the desired coil voltage rating (e.g., G7L-1A-T-CB-AC100/120).  
Replaces G5D series.  
Type  
Contact form  
SPST-NO  
Model  
Screw terminal  
Quick-connect terminal  
G7L-1A-T-CB (see note 1)  
G7L-2A-T-CB (see note 1)  
G7L-1A-TJ-CB (see note 1)  
G7L-2A-TJ-CB (see note 1)  
G7L-1A-TUB-CB  
G7L-2A-TUB-CB  
G7L-1A-TUBJ-CB  
G7L-2A-TUBJ-CB  
PCB terminal  
E bracket  
E bracket  
G7L-1A-B-CB (see note 1)  
G7L-2A-B-CB (see note 1)  
G7L-1A-BJ-CB (see note 1)  
G7L-2A-BJ-CB (see note 1)  
G7L-1A-BUB-CB  
G7L-2A-BUB-CB  
G7L-1A-BUBJ-CB  
G7L-2A-BUBJ-CB  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
(with test button)  
Upper bracket  
Upper bracket  
(with test button)  
PCB mounting  
G7L-1A-P-CB  
G7L-2A-P-CB  
Note: 1. E bracket or socket must be used for mounting (part number R99-07G5D). Refer to Accessoriessection for options and part numbers.  
2. For VDE approved versions, please consult OMRON.  
748  
General Purpose Relay G7L  
Model Number Legend  
G7L- ❏ ❏ - ❏ ❏ ❏ ❏  
1 2  
3 4 5 6  
1. Contact form  
1A: SPST-NO  
2A: DPST-NO  
3. Mounting construction  
5. 80: VDE approved version  
No symbol: E bracket type  
(includes UL, CSA and TÜV)  
UB:  
Upper bracket type  
6. CB: Class B insulation  
7. Rated coil voltage  
2. Terminal shape  
4. Special functions  
T: Quick-connect terminals  
P: PCB terminals  
No symbol: Without test button  
J:  
With test button  
B: Screw terminals  
Accessories  
Quick-connect Terminals  
Description  
Model  
Model  
Contact form  
SPST-NO  
G7L-1A-TJ  
DPST-NO  
G7L-2A-TJ  
E-brackets  
G7L-1A-T  
G7L-2A-T  
R99-07G5D  
P7LF-D  
Track mounting adaptor  
Front connecting socket  
Cover  
P7LF-06 (see note)  
P7LF-C  
Screw Terminals  
Description  
Model  
Model  
Contact form  
SPST-NO  
G7L-1A-BJ  
DPST-NO  
G7L-2A-BJ  
E-brackets  
Track mounting adaptor  
G7L-1A-B  
G7L-2A-B  
R99-07G5D  
P7LF-D  
Note: P7LF-C cover is supplied with the P7LF-06 socket.  
Specifications  
Contact Data  
Load  
G7L-1A-T, G7L-1A-B  
G7L-2A-T, G7L-2A-B  
G7L-1A-P, G7L-2A-P  
Resistive load  
Inductive load  
Resistive load  
(cosφ = 1)  
Inductive load  
(cosφ = 0.4)  
Resistive load  
Inductive load  
(cosφ = 0.4)  
(cosφ = 1)  
30 A, 220 VAC  
Ag-alloy  
(cosφ = 0.4)  
(cosφ = 1)  
Rated load  
25 A, 220 VAC  
20 A, 220 VAC  
Contact material  
Carry current  
30 A  
25 A  
25 A  
20 A  
Max. operating voltage 250 VAC  
Max. operating current 30 A  
Max. switching capacity 6,600 VA  
20 A  
4,400 VA  
5,500 VA  
Min. permissible load  
100 mA, 5 VDC  
Note: P level: λ60 = 0.1 x 10-6 operation.  
Coil Internal Circuit  
DC operating coil  
AC operating coil  
General Purpose Relay G7L  
749  
Coil Data  
AC  
Rated voltage  
(V)  
Rated current  
(mA)  
Resistance  
Must operate  
75% max.  
Must release  
% of rated voltage  
15% min.  
Max. voltage  
110% max.  
Power  
()  
consumption  
6
283  
142  
18.90  
Approx.1.70  
to 2.50 VA  
12  
75  
24  
71  
303  
50  
34  
1,310  
5,260  
21,000  
100/120  
200/240  
17.00/20.40  
8.50/10.20  
75 volts  
18 volts  
36 volts  
132 volts  
264 volts  
150 volts  
DC  
Rated voltage  
(V)  
Rated current  
(mA)  
Resistance  
()  
Must operate  
75% max.  
Must release  
% of rated voltage  
15% min.  
Max. voltage  
110% max.  
Power  
consumption  
6
317  
158  
79  
18.90  
75  
Approx.1.90 W  
12  
24  
48  
100  
303  
40  
1,220  
5,260  
19  
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C (73°F) with tolerances of +15%/-20% for AC rated cur-  
rent and 15% for DC coil resistance.  
2. Performance characteristic data are measured at a coil temperature of 23°C (73°F).  
Characteristics  
Contact resistance  
50 mmax.  
Operate time  
30 ms max.  
Release time  
30 ms max.  
Max. operating  
frequency  
Mechanical  
Electrical  
1,800 operations/hour  
1,800 operations/hour (under rated load)  
1,000 Mmin. (at 500 VDC)  
Insulation resistance  
Dielectric strength  
4,000 VAC, min./5,000 VAC typical, 50/60 Hz for 1 minute between coil and contacts  
2,000 VAC, 50/60 Hz for 1 minute between contacts of same pole  
2,000 VAC, 50/60 Hz for 1 minute between contacts of different poles (DPST-NO type)  
Between coil and contact: 10,000 V (impulse wave used: 1.20 x 50 µs)  
10 to 55 Hz; 1.50 mm (0.06 in) double amplitude  
Impulse withstand voltage  
Vibration  
Mechanical  
durability  
Malfunction  
durability  
10 to 55 Hz; 1.50 mm (0.06 in) double amplitude  
1,000 m/s2 (approx. 100 G)  
Shock  
Mechanical  
durability  
1,000 m/s2 (approx.10 G)  
Malfunction  
durability  
Life expectancy  
Mechanical  
Electrical  
5,000,000 operations min. (at 1,800 operations/hour)  
100,000 operations min. (at 1,800 operations/hour under rated load)  
-20° to 85°C (-4° to 185°F)  
Ambient temperature  
Humidity  
35% to 85% RH  
Weight  
Quick-connect terminal type: approx. 90 g (3.17 oz)  
PCB terminal type: approx. 100 g (3.52 oz)  
Screw terminal type: approx. 120 g (4.23 oz)  
Note: Data shown are of initial value.  
750  
General Purpose Relay G7L  
Characteristic Data  
Maximum switching capacity  
Electrical service life  
Switching voltage (V)  
Switching current (A)  
Dimensions  
Unit: mm (inch)  
Relays  
G7L-1A-T  
(E Bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-T  
(E Bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
* E bracket must be ordered separately.  
General Purpose Relay G7L  
751  
G7L-1A-TJ  
(E Bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-TJ  
(E Bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-1A-TUB  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-TUB  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
*E bracket must be ordered separately.  
752  
General Purpose Relay G7L  
Unit: mm (inch)  
G7L-1A-TUBJ  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-TUBJ  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-1A-B  
(E bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-B  
(E bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
* E bracket must be ordered separately.  
General Purpose Relay G7L  
753  
G7L-1A-BJ  
(E bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-BJ  
(E bracket Attached)*  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-1A-BUB  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-BUB  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
* E bracket must be ordered separately.  
754  
General Purpose Relay G7L  
Unit: mm (inch)  
G7L-1A-BUBJ  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-BUBJ  
Mounting holes  
(Bottom view)  
Terminal arrangement/  
Internal connections  
(Top view)  
G7L-1A-P  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
G7L-2A-P  
Terminal arrangement/  
Internal connections  
(Top view)  
Mounting holes  
(Bottom view)  
General Purpose Relay G7L  
755  
Accessories  
E bracket  
R99-07G5D  
Mounting holes  
(Bottom view)  
Adaptor  
P7LF-D  
Mounting holes  
(Bottom view)  
Front connecting socket  
P7LF-06  
Mounting holes  
(Bottom view)  
Note: 1. To protect against electric shock, use the P7LF-C cover on terminals.  
2. P7LF-C cover is supplied with P7LF-06 socket.  
756  
General Purpose Relay G7L  
Unit: mm (inch)  
Cover  
P7LF-C  
Note: P7LF-C cover is supplied with P7LF-06 socket.  
Mounting track  
PFP-100N, PFP-50N  
PFP-100N2  
Note: 1. It is recommended that a panel thickness of 1.60 to 2.00 mm (0.06 to 0.08 in) be used.  
2. L = Length  
PFP-100N ................... L = 1 m (39.00 in)  
PFP-50N  
................... L = 50 cm (19.60 in)  
PFP-100N2 ................... L = 1 m (39.00 in)  
End plate  
PFP-M  
Spacer  
PFP-S  
General Purpose Relay G7L  
757  
Approvals  
UL recognized type (File No. E41643)/CSA certified type (File No. LR35535)  
Type  
G7L-1A-T-CB  
G7L-1A-TJ-CB  
G7L-1A-TUB-CB  
G7L-1A-TUBJ-CB  
G7L-1A-B-CB  
G7L-1A-BJ-CB  
G7L-1A-BUB-CB  
G7L-1A-BUBJ-CB  
G7L-1A-P-CB  
Contact form  
Terminal type  
Contact ratings  
30 A, 277 VAC, General Use, 100,000 c  
1.5 kW, 120 VAC, Tungsten  
SPST-NO  
Quick-connect  
1.5 HP, 120 VAC  
3 HP, 240/265/277 VAC, 100,000 c  
20 FLA/120 LRA, 120 VAC, 30,000 c  
17 FLA/102 LRA, 277 VAC, 30,000 c  
TV-10, 120 VAC  
20 A (2.4 kW), 120 VAC, Tungsten  
20 A, (4.8 kW), 240 VAC, Tungsten 6,000  
20 A, 277 VAC, Ballast 10,000 c  
Screw  
PCB  
G7L-2A-T-CB  
DPST-NO  
Quick-connect  
G7L-2A-TJ-CB  
G7L-2A-TUB-CB  
G7L-2A-TUBJ-CB  
G7L-2A-B-CB  
G7L-2A-BJ-CB  
G7L-2A-BUB-CB  
G7L-2A-BUBJ-CB  
G7L-2A-P-CB  
Screw  
PCB  
TÜV (File No. R9251551)  
Type  
Contact form  
SPST-NO  
Coil ratings  
Terminal type  
Contact ratings  
G7L-1A-T-CB  
G7L-1A-TJ-CB  
G7L-1A-TUB-CB  
G7L-1A-TUBJ-CB  
G7L-1A-B-CB  
G7L-1A-BJ-CB  
G7L-1A-BUB-CB  
G7L-1A-BUBJ-CB  
G7L-1A-P-CB  
6, 12, 24, 48,  
100, 110, 200,  
220 VDC  
Quick-connect  
25 A, 240 VAC, (cosφ = 1)  
25 A, 240 VAC, (cosφ = 0.4)  
12, 24, 50,  
100/120, 200/240  
VAC  
Screw  
30 A, 240 VAC, (cosφ = 1)  
25 A, 240 VAC, (cosφ = 0.4)  
30 A, 240 VAC, (cosφ = 0.4)  
PCB  
20 A, 240 VAC, (cosφ = 1)  
20 A, 240 VAC, (cosφ = 0.4)  
25 A, 240 VAC, (cosφ = 1)  
25 A, 240 VAC, (cosφ = 0.4)  
G7L-2A-T-CB  
DPST-NO  
Quick-connect  
G7L-2A-TJ-CB  
G7L-2A-TUB-CB  
G7L-2A-TUBJ-CB  
G7L-2A-B-CB  
G7L-2A-BJ-CB  
G7L-2A-BUB-CB  
G7L-2A-BUBJ-CB  
G7L-2A-P-CB  
Screw  
PCB  
25 A, 240 VAC, (cosφ = 1)  
25 A, 240 VAC, (cosφ = 0.4)  
20 A, 240 VAC, (cosφ = 1)  
20 A, 240 VAC, (cosφ = 0.4)  
VDE recognized type (Licence no. 1530 UG)  
Note: 1. Please consult OMRON for details of VDE approvals.  
2. The G7L relay conforms to the following standards: Electrical safety: DIN IEC 255 Teil 1-00/DIN VDE 0435 Teil 201/05. 83  
DIN VDE 0435 Teil 201 A1/05. 90  
DIN IEC 255 Teil 0-20/DIN VDE 0435 Teil 120/10. 81  
DIN EN 60 950/VDE 0805/11. 93  
EMC:  
prEN 50082-2, EN 55022  
3. The rated values approved by each of the safety standards (e.g., UL and CSA) may be different from the performance characteristics  
individually defined in this catalog.  
4. In the interest of product improvement, specifications are subject to change.  
758  
General Purpose Relay G7L  
Precautions  
Handling  
Operating Coil  
To preserve initial performance, do not drop or otherwise subject  
As a rule, either a battery or a DC power supply with a maximum  
5% ripple is used for the operating voltage for DC relays. Before  
using a rectified AC supply, confirm that the ripple is not greater  
than 5%. Ripple greater than this can lead to variations in the oper-  
ating and reset voltages.  
the power relay to shock.  
The case is not designed to be removed during normal handling  
and operation. Doing so may affect performance.  
Use the power relay in a dry environment free from excessive dust,  
As excessive ripple can generate beats, the insertion of a smooth-  
ing capacitor is recommended as shown below.  
SO2, H2S, or organic gas.  
Do not allow a voltage greater than the maximum allowable coil  
voltage to be applied continuously.  
Do not use the power relay outside of specified voltages and cur-  
rents.  
Do not allow the ambient operating temperature to exceed the  
specified limit.  
Installation  
Although there are not specific limits on the installation site, it  
should be as dry and dust-free as possible.  
PCB terminal-equipped relays weigh approximately 100 g. Be sure  
that the PCB is strong enough to support them. We recommend  
dual-side through-hole PCBs to reduce solder cracking from heat  
stress.  
Quick-connect terminals can be connected to fast on receptacle  
#250 and positive-lock connectors.  
Allow suitable slack on leads when wiring, and do not subject the  
terminals to excessive force.  
When driving a transistor, check the leakage current and connect a  
bleeder resistor if necessary.  
Cleaning PCB Terminals  
PCB terminals have semi-sealed construction which prevents flux  
from entering the relay base. It is recommended that the user  
should apply a tape seal over the vent hole prior to wave soldering  
or cleaning. The tape should then be removed after processing.  
Momentary voltage drops on coil input voltage should not exceed  
one second duration after contact mating with no shock or vibra-  
tion.  
Applications  
Compressors for package air conditioners and heater switching  
controllers  
Switching controllers for power tools or motors  
Power controllers for water heaters  
Power controllers for dryers  
Lamp control, motor drivers, and power supply switching in copy  
machines, facsimiles, and other OA equipment  
Lighting controllers  
Power controllers for packers or food processing equipment  
Magnetron control in microwaves  
General Purpose Relay G7L  
759  
Terms and Conditions of Sale  
1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed 12. Warranties. (a) Exclusive Warranty. Seller's exclusive warranty is that the  
part of all quotations, acknowledgments, invoices, purchase orders and other  
documents, whether electronic or in writing, relating to the sale of products or  
services (collectively, the "Products") by Omron Electronic Components LLC  
("Seller"). Seller hereby objects to any terms or conditions proposed in  
Buyer's purchase order or other documents which are inconsistent with, or in  
addition to, these Terms.  
Products will be free from defects in materials and workmanship for a period of  
twelve months from the date of sale by Seller (or such other period expressed  
in writing by Seller). Seller disclaims all other warranties, express or implied.  
(b) Limitations. SELLER MAKES NO WARRANTY OR REPRESENTATION,  
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-  
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.  
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE  
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR  
INTENDED USE. Seller further disclaims all warranties and responsibility of  
any type for claims or expenses based on infringement by the Products or oth-  
erwise of any intellectual property right. (c) Buyer Remedy. Seller's sole obli-  
gation hereunder shall be to replace (in the form originally shipped with Buyer  
responsible for labor charges for removal or replacement thereof) the non-  
complying Product or, at Seller's election, to repay or credit Buyer an amount  
equal to the purchase price of the Product; provided that in no event shall  
Seller be responsible for warranty, repair, indemnity or any other claims or  
expenses regarding the Products unless Seller's analysis confirms that the  
Products were properly handled, stored, installed and maintained and not sub-  
ject to contamination, abuse, misuse or inappropriate modification. Return of  
any Products by Buyer must be approved in writing by Seller before shipment.  
Seller shall not be liable for the suitability or unsuitability or the results from the  
use of Products in combination with any electrical or electronic components,  
circuits, system assemblies, or any other materials or substances or environ-  
ments. Any advice, recommendations or information given orally or in writing  
are not to be construed as an amendment or addition to the above warranty.  
2. Prices; Payment. All prices stated are current, subject to change without  
notice by Seller. Buyer agrees to pay the price in effect at time of shipment.  
Payments for Products received are due net 30 days unless otherwise stated  
in the invoice.  
3. Discounts. Cash discounts, if any, will apply only on the net amount of  
invoices sent to Buyer after deducting transportation charges, taxes and  
duties, and will be allowed only if (i) the invoice is paid according to Seller's  
payment terms and (ii) Buyer has no past due amounts owing to Seller.  
4. Currencies. If the prices quoted herein are in a currency other than U.S. dol-  
lars, Buyer shall make remittance to Seller at the then current exchange rate  
most favorable to Seller and which is available on the due date; provided that if  
remittance is not made when due, Buyer will convert the amount to U.S. dol-  
lars at the then current exchange rate most favorable to Seller available during  
the period between the due date and the date remittance is actually made.  
5. Governmental Approvals. Buyer shall be responsible for, and shall bear all  
costs involved in, obtaining any government approvals required for the impor-  
tation or sale of the Products.  
6. Taxes. All taxes, duties and other governmental charges (other than general  
real property and income taxes), including any interest or penalties thereon,  
imposed directly or indirectly on Seller or required to be collected directly or 13. Limitation on Liability; Etc. SELLER SHALL NOT BE LIABLE FOR SPECIAL,  
indirectly by Seller for the manufacture, production, sale, delivery, importation,  
consumption or use of the Products sold hereunder (including customs duties  
and sales, excise, use, turnover and license taxes) shall be charged to and  
remitted by Buyer to Seller.  
INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSS OF  
PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CON-  
NECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN  
CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in  
no event shall liability of Seller exceed the individual price of the Product on  
which liability is asserted.  
7. Financial. If the financial position of Buyer at any time becomes unsatisfactory  
to Seller, Seller reserves the right to stop shipments or require satisfactory  
security or payment in advance. If Buyer fails to make payment or otherwise 14. Indemnities. Buyer shall indemnify and hold harmless Seller, its affiliates and  
comply with these Terms or any related agreement, Seller may (without liability  
and in addition to other remedies) cancel any unshipped portion of Products  
sold hereunder and stop any Products in transit until Buyer pays all amounts,  
including amounts payable hereunder, whether or not then due, which are  
owing to it by Buyer. Buyer shall in any event remain liable for all unpaid  
accounts.  
its employees from and against all liabilities, losses, claims, costs and  
expenses (including attorney's fees and expenses) related to any claim, inves-  
tigation, litigation or proceeding (whether or not Seller is a party) which arises  
or is alleged to arise from Buyer's acts or omissions under these Terms or in  
any way with respect to the Products. Without limiting the foregoing, Buyer (at  
its own expense) shall indemnify and hold harmless Seller and defend or settle  
any action brought against Seller to the extent that it is based on a claim that  
any Product made to Buyer specifications infringed intellectual property rights  
of another party.  
8. Cancellation; Etc. Orders are not subject to rescheduling or cancellation  
unless Buyer indemnifies Seller fully against all costs or expenses arising in  
connection therewith.  
9. Force Majeure. Seller shall not be liable for any delay or failure in delivery 15. Property; Confidentiality. The intellectual property embodied in the Products is  
resulting from causes beyond its control, including earthquakes, fires, floods,  
strikes or other labor disputes, shortage of labor or materials, accidents to  
machinery, acts of sabotage, riots, delay in or lack of transportation or the  
requirements of any government authority.  
the exclusive property of Seller and its affiliates and Buyer shall not attempt to  
duplicate it in any way without the written permission of Seller. Notwithstand-  
ing any charges to Buyer for engineering or tooling, all engineering and tooling  
shall remain the exclusive property of Seller. All information and materials sup-  
plied by Seller to Buyer relating to the Products are confidential and propri-  
etary, and Buyer shall limit distribution thereof to its trusted employees and  
strictly prevent disclosure to any third party.  
10. Shipping; Delivery. Unless otherwise expressly agreed in writing by Seller:  
1. Shipments shall be by a carrier selected by Seller;  
2. Such carrier shall act as the agent of Buyer and delivery to such carrier  
shall constitute delivery to Buyer;  
16. Miscellaneous. (a) Waiver. No failure or delay by Seller in exercising any right  
and no course of dealing between Buyer and Seller shall operate as a waiver  
of rights by Seller. (b) Assignment. Buyer may not assign its rights hereunder  
without Seller's written consent. (c) Law. These Terms are governed by Illi-  
nois law (without regard to conflict of law principles). Federal and state courts  
in Illinois shall have exclusive jurisdiction for any dispute hereunder.  
(d) Amendment. These Terms constitute the entire agreement between Buyer  
and Seller relating to the Products, and no provision may be changed or  
waived unless in writing signed by the parties. (e) Severability. If any provision  
hereof is rendered ineffective or invalid, such provision shall not invalidate any  
other provision. (f) Setoff. Buyer shall have no right to set off any amounts  
against the amount owing in respect of this invoice.. (g) Definitions. As used  
herein, "including" means "including without limitation".  
3. All sales and shipments of Products shall be FOB shipping point (unless  
otherwise stated in writing by Seller), at which point title to and all risk of  
loss of the Products shall pass from Seller to Buyer, provided that Seller  
shall retain a security interest in the Products until the full purchase price is  
paid by Buyer;  
4. Delivery and shipping dates are estimates only.  
5. Seller will package Products as it deems proper for protection against  
normal handling and extra charges apply to special conditions.  
11. Claims. Any claim by Buyer against Seller for shortage or damage to the  
Products occurring before delivery to the carrier must be presented in writing  
to Seller within 30 days of receipt of shipment and include the original trans-  
portation bill signed by the carrier noting that the carrier received the Products  
from Seller in the condition claimed.  
Certain Precautions on Specifications and Use  
1. Suitability for Use. Seller shall not be responsible for conformity with any stan- 2. Programmable Products. Seller shall not be responsible for the user's  
dards, codes or regulations which apply to the combination of the Product in  
programming of a programmable product, or any consequence thereof.  
Buyer's application or use of the Product. At Buyer's request, Seller will pro- 3. Performance Data. Performance data given in this publication is provided as a  
vide applicable third party certification documents identifying ratings and limita-  
tions of use which apply to the Product. This information by itself is not  
sufficient for a complete determination of the suitability of the Product in combi-  
nation with the end product, machine, system, or other application or use.  
guide for the user in determining suitability and does not constitute a warranty  
It may represent the result of Seller's test conditions, and the users must corre  
late it to actual application requirements. Actual performance is subject to  
Seller's Warranty and Limitations of Liability.  
Buyer shall be solely responsible for determining appropriateness of the partic- 4. Change in Specifications. Product specifications and accessories may be  
ular Product with respect to Buyer's application, product or system. Buyer  
shall take application responsibility in all cases but the following is a non-  
exhaustive list of applications for which particular attention must be given:  
(i) Outdoor use, uses involving potential chemical contamination or electrical  
interference, or conditions or uses not described in this document.  
(ii)Energy control systems, combustion systems, railroad systems, aviation  
systems, medical equipment, amusement machines, vehicles, safety  
equipment, and installations subject to  
changed at any time based on improvements and other reasons. It is our prac  
tice to change part numbers when published ratings or features are changed  
or when significant construction changes are made. However, some specifica  
tions of the Product may be changed without any notice. When in doubt, spe  
cial part numbers may be assigned to fix or establish key specifications for you  
application. Please consult with your Seller representative at any time to con  
firm actual specifications of purchased Product.  
5. Errors and Omissions. The information in this publication has been carefully  
checked and is believed to be accurate; however, no responsibility is assumed  
for clerical, typographical or proofreading errors, or omissions.  
6. RoHS Compliance. Where indicated, our products currently comply, to the bes  
of our knowledge as of the date of this publication, with the requirements of the  
European Union's Directive on the Restriction of certain Hazardous Sub  
stances ("RoHS"), although the requirements of RoHS do not take effect unti  
July 2006. These requirements may be subject to change. Please consult ou  
website for current information.  
separate industry or government regulations.  
(iii)Use in consumer products or any use in significant quantities.  
(iv)Systems, machines and equipment that could present a risk to life or  
property. Please know and observe all prohibitions of use applicable to this  
product.  
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS  
RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM  
AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT  
THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE  
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
Complete “Terms and Conditions of Sale” for product purchase and use are on Omron’s website  
at www.components.omron.com under the “About Us” tab, in the Legal Matters section.  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
OMRON ON-LINE  
Global - http://www.omron.com  
USA - http://www.components.omron.com  
Canada - http://www.omron.ca  
OMRON ELECTRONIC  
COMPONENTS LLC  
55 E. Commerce Drive, Suite B  
Schaumburg, IL 60173  
OMRON CANADA, INC.  
885 Milner Avenue  
Toronto, Ontario M1B 5V8  
416-286-6465  
847-882-2288  
Cat. No. JB301-E3-01  
3/05  
Specifications subject to change without notice  
Printed in USA