G9SA  
Safety Relay Unit  
The G9SA Series Offers a Complete  
Line of Compact Units  
H Several types of 45-mm wide Units are  
available: a 3-pole model, a 5-pole model,  
models with 3 poles and 2 OFF-delay poles  
H 17.5-mm wide Expansion Units with 3 poles  
and 3 OFF-delay poles are also available  
H Simple expansion connection  
H OFF-delay models have 15-step OFF-delay  
settings  
H Conforms to EN standards (BG approval)  
H Approved by UL and CSA  
R
H DIN-rail mounting or screw mounting  
Ordering Information  
J EMERGENCY-STOP UNITS  
Main contacts Auxiliary contact  
Number of input channels  
1 channel or 2 channels  
possible  
Rated voltage  
24 VAC/VDC  
100 to 240 VAC  
24 VAC/VDC  
100 to 240 VAC  
Category  
4
Part number  
G9SA-301  
3PST-NO  
5PST-NO  
SPST-NC  
SPST-NC  
1 channel or 2 channels  
possible  
G9SA-501  
J EMERGENCY-STOP OFF-DELAY UNITS  
Main  
contacts  
OFF-delay  
contacts  
Auxiliary  
contact  
Number of  
input  
channels  
OFF-  
delay  
time  
Rated voltage  
Category  
Part number  
3PST-NO  
DPST-NO  
SPST-NC  
1 channel or 7.5 s  
2 channels  
Main contacts: 4  
OFF-delay contacts: 3  
G9SA-321-T075  
G9SA-321-T15  
G9SA-321-T30  
24 VAC/VDC  
100 to 240 VAC  
24 VAC/VDC  
100 to 240 VAC  
24 VAC/VDC  
possible  
15 s  
30 s  
100 to 240 VAC  
Note: The following 15-step OFF-delay time settings are available:  
T075:  
T15:  
T30:  
0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s  
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s  
2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, and 30 s  
J EXPANSION UNIT  
The Expansion Unit connects to a G9SA-301, G9SA-501, or G9SA-321.  
Main contacts  
3PST-NO  
Auxiliary contact  
SPST-NC  
Category  
4
Part number  
G9SA-EX301  
2
G9SA  
J EXPANSION UNITS WITH OFF-DELAY OUTPUTS  
The Expansion Unit connects to a G9SA-301, G9SA-501, or G9SA-321.  
Main contact form  
3PST-NO  
Auxiliary contact  
SPST-NC  
OFF-delay time  
Category  
3
Part number  
7.5 s  
15 s  
30 s  
G9SA-EX031-T075  
G9SA-EX031-T15  
G9SA-EX031-T30  
Note: The following 15-step OFF-delay time settings are available:  
T075:  
T15:  
T30:  
0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s  
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s  
2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, and 30 s  
J MODEL NUMBER LEGEND  
G9SA-jjjjjj-jjjj  
1
2
3
4
5
6
1. Function  
4. Contact Configuration (Auxiliary Output)  
None: Emergency stop  
EX: Expansion Unit  
2. Contact Configuration (Safety Output)  
0:  
1:  
None  
SPST-NC  
5. Input Configuration (for G9SA-301/501/321)  
0:  
3:  
5:  
None  
3PST-NO  
5PST-NO  
None: 1-channel or 2-channel input possible  
6. OFF-Delay Time (Max. Setting Time)  
None: No OFF-delay  
3. Contact Configuration (OFF-Delay Output)  
T075: 7.5 seconds  
0:  
2:  
3:  
None  
DPST-NO  
3PST-NO  
T15: 15 seconds  
T30: 30 seconds  
Specifications  
J RATINGS  
Power Input  
Item  
G9SA-501  
G9SA-321-Tj  
Power supply voltage  
24 VAC/VDC: 24 VAC, 50/60 Hz, or 24 VDC  
100 to 240 VAC: 100 to 240 VAC, 50/60 Hz  
85% to 110% of rated power supply voltage  
Operating voltage range  
Power consumption  
(See Note)  
24 VAC/VDC: 2.8 VA/2.6 W max.  
100 to 240 VAC: 11 VA max.  
24 VAC/VDC: 3.5 VA/3.3 W max.  
100 to 240 VAC: 12.5 VA max.  
Note: When an Expansion Unit is connected, the power consumption is increased by 2 VA/2 W max.  
Inputs  
Item  
G9SA-501  
Input current (See Note)  
60 mA max.  
Note: When an Expansion Unit is connected, the input current is increased by 30 mA max.  
Contacts  
G9SA-301/501/321-Tj/EX301/EX031-Tj  
Item  
Resistive load (cos φ =1)  
250 VAC, 5 A  
5 A  
Rated load  
Rated carry current  
3
G9SA  
J CHARACTERISTICS  
Item  
G9SA-301  
G9SA-501/321-Tj  
G9SA-EX301/EX031-Tj  
Contact resistance (See Note 1)  
Operating time  
100 mΩ  
30 ms max. (not including bounce time)  
10 ms max. (not including bounce time)  
100 Mmin. (at 500 VDC)  
Response time (See Note 2)  
Insulation resistance (See Note 3)  
Dielectric  
strength  
2,500 VAC, 50/60 Hz for 1 min  
Between different outputs  
Between inputs and outputs  
Between power inputs and outputs  
Between power inputs and other  
inputs (only for 100 to 240-V models)  
Vibration resistance  
10 to 55 Hz, 0.75-mm double amplitude  
2
Shock  
Destruction  
Malfunction  
Mechanical  
Electrical  
300 m/s  
100 m/s  
resistance  
2
Life  
expectancy  
5,000,000 operations min. (at approx. 7,200 operations/hr)  
100,000 operations min. (at approx. 1,800 operations/hr)  
5 VDC, 1 mA  
Minimum permissible load (reference value)  
Ambient temperature  
Operating: --25°C to 55°C (with no icing or condensation)  
Storage: --25°C to 85°C (with no icing or condensation)  
Ambient humidity  
Operating: 35% to 85%  
Storage: 35% to 85%  
Terminal tightening torque  
Weight (See Note 4)  
Approved standards  
EMC  
0.98 NSm  
Approx. 210 g  
Approx. 270 g  
Approx. 130 g  
EN954-1, EN60204-1, UL508, CSA C22.2 No. 14  
EMI: EN55011 group 1 class A  
EMS: EN50082-2 group 1  
Note: 1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.  
2. The response time is the time it takes for the main contact to open after the input is turned OFF.  
3. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.  
4. Weight shown is for 24-VAC/VDC type. For 100 to 240-VAC type, add approximately 20 g.  
4
G9SA  
Dimensions  
Unit: mm (inch)  
J G9SA-301  
G9SA-501  
G9SA-321-TV  
Terminal Arrangement  
G9SA-501  
G9SA-321-Tj  
G9SA-301  
91  
(3.58)  
OFF-  
delay  
time  
setting  
switch  
(See  
Note.)  
G9SA-301: Twenty, M3  
G9SA-501: Twenty-four, M3  
Mounting Holes  
G9SA-321-Tj: Twenty-four, M3  
4.6 dia.  
(0.18)  
Two, 4.2 dia. or M4  
(0.17)  
OFF-delay time  
setting switch  
(See Note.)  
76 max.  
(2.99)  
84±0.3  
(3.31)  
Connector cover  
35±0.3  
(1.38)  
45 max.  
(1.77)  
111 max.  
(4.37)  
Note: The OFF-delay time setting switch is found on the G9SA-321-Tj only.  
11  
G9SA  
J G9SA-EX301  
G9SA-EX031-TV  
Mounting Holes  
Two, 4.2 dia. or M4  
Terminal Arrangement  
G9SA-EX301  
G9SA-EX031-Tj  
91  
(3.58)  
±
0.3  
87  
(3.43)  
OFF-delay time  
setting switch  
(See Note.)  
Eight, M3  
4.6 dia.  
(0.18)  
76 max.  
(2.99)  
OFF-delay time  
setting switch  
(See Note.)  
70  
(2.76)  
111 max.  
(4.37)  
17.5 max.  
(0.69)  
Note: The OFF-delay time setting switch is found on the G9SA-EX031-Tj only.  
12  

相关型号:

G9SA-321-T30

Sicherheitsmodul
ETC

G9SA-501

Sicherheitsmodul
ETC

G9SA-EX031-T075

Special Relay
OMRON

G9SA-EX031-T15

Special Relay
OMRON

G9SA-EX031-T30

Special Relay
OMRON

G9SA-TH301

Special Relay
OMRON

G9SB

Ultra Slim Safety Relay Unit
OMRON

G9SB-200-B

Ultra Slim Safety Relay Unit
OMRON

G9SB-200-D

Ultra Slim Safety Relay Unit
OMRON

G9SB-2002-A

Ultra Slim Safety Relay Unit
OMRON

G9SB-2002-C

Ultra Slim Safety Relay Unit
OMRON

G9SB-301-B

Ultra Slim Safety Relay Unit
OMRON