H7CX-A114USDG Multifunction Preset Counter
Prototype PCB
Part No.:   H7CX-A114USDG
Download: Download   Right selection Save Target As
View Datasheet (Html)   No need to install PDF reader software
Description:   Multifunction Preset Counter
File Size :   2406 K    
Page : 43 Pages
Logo:   
Maker   OMRON [ OMRON ELECTRONICS LLC ]http://www.omron.com
Buy Now :   
  H7CX-A114USDG Datasheet PDF page 14 H7CX-A114USDG Datasheet PDF page 15 H7CX-A114USDG Datasheet PDF page 16 H7CX-A114USDG Datasheet PDF page 17 H7CX-A114USDG Datasheet PDF page 19 H7CX-A114USDG Datasheet PDF page 20 H7CX-A114USDG Datasheet PDF page 21 H7CX-A114USDG Datasheet PDF page 22  
100%
I
Self-diagnostic Function
The following displays will appear if an error occurs.
Main display
Sub-display
Error
Present value underflow
(See note 3.)
Output status
No change
Correction method
Either press the reset key or turn ON
reset input.
Set value after
reset
No change
No change
------
(----)
(See notes 1 and
2.)
No change
ffffff
(ffff)
(See notes 1 and
2.)
e1
e2
e2
Not lit
Not lit
sum
Present value overflow
(See note 4.)
No change
Either press the reset key or turn ON
reset input. (See note 5.)
No change
CPU
Memory error (RAM)
Memory error (EEP)
(See note 6.)
OFF
OFF
OFF
Either press the reset key or reset the No change
power supply.
Reset the power supply.
No change
Reset to the factory settings using the 0
reset key.
Note: 1.
2.
3.
4.
The display for 4-digit models is given in parentheses.
Display flashes (1-second cycles).
Occurs when the present value or the total count value goes below
−99,999
(−999 with 4-digit models).
Occurs when the present value (or measurement value) reaches 999,999 (9,999 with 4-digit models) under the following conditions:
The output mode is K-2, D, L, or H.
The H7CX is set for dual counter or tachometer operation.
5.
Except when the H7CX is set for tachometer operation.
6.
Includes the case where the EEPROM has reached its overwrite lifetime.
I
Response Delay Time When
Resetting (Transistor Output)
The following table shows the delay from when the reset signal is
input until the output is turned OFF.
(Reference values)
I
Wiring
Wiring input lines in the same conduit as power lines or other high-
voltage lines may result in malfunction due to noise. Wire the input
lines separately, away from lines carrying high-voltages. In addition,
make the input wiring as short as possible and use shield lines or
metal wiring conduits.
Pay attention to terminal polarity to ensure correct wiring.
Minimum reset signal width
1 ms
20 ms
Output delay time
0.8 to 1.2 ms
15 to 25 ms
I
Mounting
Tighten the two mounting screws on the Adaptor. Tighten them alter-
nately, a little at a time, so as to keep them at an equal tightness.
The H7CX’s panel surface is water-resistive (conforming to NEMA 4
and IP66). In order to prevent the internal circuit from water penetra-
tion through the space between the timer and operating panel, attach
a waterproof packing between the timer and installation panel and
secure the waterproof packing with the Y92F-30 Flush-mounting
Adapter.
0.5 to 1 mm
I
Output Delay Time
The following table shows the delay from when the present value
passes the set value until the output is produced.
Actual measurements in N and K-2 modes.
Control output type Maximum counting
speed
Contact output
Transistor output
30 Hz
5 kHz
30 Hz
5 kHz
(Reference values)
Output delay time
16.5 to 24.0 ms
3.7 to 5.6 ms
12.0 to 20.0 ms
0.2 to 0.55 ms
It is recommended that the space between
the screw head and the adapter should be
0.5 to 1 mm.
Note:
The above times may vary slightly depending on the mode or
operating conditions.
I
Maximum Counting Speed for
Batch Counter
The maximum counting speed for batch counter operation is 5 kHz.
The batch counter counts the number of times the count reaches the
set value.