I
Operating Procedures (Counter Function)
Settings for Basic Operations
Settings for basic functions can be performed with just the DIP switch.
Be sure to set pin 1 to ON.
1
ON
2
3
4
5
6
7
8
OFF
Note:
All of the pins are factory-set to OFF.
Item
1
2
3
4
5
6
7
8
One-shot output time
(See note.)
Reset input signal width
NPN/PNP input mode
0.5 s
DIP switch settings en-
able/disable
Counting speed
Input mode
Output mode
OFF
Disabled
30 Hz
ON
Enabled
5 kHz
UP (increment) DOWN (decre-
ment)
Refer to the table on the right.
0.05 s
1 ms
PNP
Pin 4
OFF
ON
OFF
20 ms
NPN
ON
Pin 5
OFF
OFF
ON
ON
N
F
C
K-1
Output mode
Note:
Set to one-shot output 2 time when using as a 2-stage counter
or batch counter.
Easy Confirmation of Switch Settings Using Indicators
The ON/OFF status of the DIP switch pins can be
confirmed using the front display. For details, refer to page 124.
Note: 1.
Be sure to set pin 1 of the DIP switch to ON. If it is set to OFF, the DIP switch settings will not be enabled.
2.
Changes to DIP switch settings are enabled when the power is turned ON.
3.
When setting input modes, output modes, or output times that cannot be set with the DIP switch, all of the settings have to be made using
the operation keys. For details on the setting methods, refer to page 108. When making settings using the operation keys, be sure to set
pin 1 of the DIP switch to OFF.
Switching to Total and Preset Counter, Batch Counter, and Dual Counter Operation (See note.)
The H7CX is factory-set to the 1-stage
counter (2-stage counter for H7CX-AW@/-
A4W@ models) configuration. To change to
a different configuration, use the procedure
shown on the right. For details, refer to
page 39.
Note:
This includes changing to the 2-
stage counter (or 1-stage counter)
configuration.
Power ON
Configuration selection mode
Run mode
Hold down for
1 s min. (See note.)
MODE
+
1
Note:
The
MODE
key must be pressed before the
Select the configuration using the
and
keys (
1
key.
key with 6-digit models).
(1-stage
counter)
(2-stage (Total and
counter) preset counter)
(Batch
counter)
(Dual
counter)
(Tachometer)
Note:
The configurations that can be selected vary with the model.
Advanced-Function Settings
After making DIP switch settings for basic operations, advanced functions (see note) can be added using the operation keys.
For details, refer to page 22.
Note:
Advanced functions consist of the dual count calculating mode, output 1 time (for 2-stage counter), decimal point position,prescale value, display
color, output allocation, and key protect level.
Multifunction Preset Counter
H7CX (Counter Function)
C-107
Counters
Home - IC Supply - Link
Copyright© 2001 - 2014 ICPDF All Rights Reserved ICPDF.COM

粤公网安备 44030402000629号


粤ICP备13051289号-7