Multifunction Preset Counter  
H7CX  
• Highly visible display with backlit negative transmissive LCD.  
• Programmable PV color to visually alert when output status  
changes (screw terminal block models).  
• Intuitive setting enabled using ergonomic up/down digit keys (4-  
digit models) and DIP switch.  
• Configurable as 1-stage counter, 2-stage counter, total and pre-  
set counter, batch counter, dual counter, or tachometer. (Config-  
urability varies with model.)  
• PNP/NPN switchable input.  
• Finger-safe terminals (screw terminal block models).  
• Meets a variety of mounting requirements:  
Screw terminal block models, and pin-style terminal models.  
• NEMA4/IP66 compliance.  
• Six-language instruction manual.  
Contents  
Model Number Structure.............................................................. C-88  
Ordering Information.................................................................... C-88  
Specifications............................................................................... C-89  
Connections................................................................................. C-93  
Nomenclature .............................................................................. C-98  
Dimensions.................................................................................. C-99  
Precautions.................................................................................. C-103  
Operating Procedures.................................................................. C-106  
Setting Procedure Guide....................................................... C-106  
Operating Procedures (Counter Function) ............................ C-107  
Operating Procedures (Tachometer Function) ...................... C-118  
Operation in Configuration Selection Mode........................... C-124  
Additional Information.................................................................. C-125  
Multifunction Preset Counter H7CX  
C-87  
Model Number Structure  
Model Number Legend  
H7CX-A@@@@@@  
1 2 3 4 5  
6
1. External connection  
None: Screw terminals  
11: 11-pin socket  
2. No. of digits  
4. Output type  
None: Contact output or contact and transistor in combination  
S:  
Transistor output  
5. Supply voltage/external power supply  
None: 6 digits  
None: 100 to 240 VAC at 50/60 Hz with 12 VDC power supply  
4:  
4 digits  
D:  
12 to 24 VDC without external power supply  
3. Stage setting  
D1: 12 to 24 VDC or 24 VAC at 50/60 Hz with 12 VDC power  
supply  
None: 1-stage setting  
6. Case color  
U:  
W:  
Factory-set to 1-stage setting  
Factory-set to 2-stage setting  
None: Black  
G:  
Light gray (Munsell 5Y7/1): Produced upon request.  
Ordering Information  
List of Models  
Supported configurations  
1-stage counter  
1-stage counter with total counter  
1-stage counter  
2-stage counter  
1-stage counter with total  
counter  
1-stage counter  
2-stage counter  
1-stage counter  
with total counter  
1-stage counter  
with batch counter  
1-stage counter with batch  
counter  
Dual counter (addition/subtrac- Dual counter (addi-  
tion)  
Tachometer  
tion only)  
Sensor  
power  
supply  
Output type  
Supply voltage  
11-pin socket  
Screw terminal  
1-stage  
1-stage  
(See note.)  
2-stage  
6 digits  
H7CX-A11@  
H7CX-A11  
4 digits  
6 digits  
H7CX-A@  
H7CX-A  
---  
4 digits  
H7CX-A4@  
H7CX-A4  
---  
6 digits  
6 digits  
H7CX-AW@  
H7CX-AW  
4 digits  
H7CX-A4W@  
H7CX-A4W  
H7CX-A114@  
H7CX-A114  
H7CX-AU@  
12 VDC Contact output  
100 to 240 VAC  
---  
---  
12 to 24 VDC/  
24 VAC  
H7CX-A11D1  
H7CX-A114D1  
H7CX-AWD1  
---  
Contact and  
transistor output  
100 to 240 VAC  
---  
---  
---  
---  
---  
---  
---  
---  
H7CX-AU  
---  
---  
---  
---  
12 to 24 VDC/  
24 VAC  
H7CX-AUD1  
Transistor output 100 to 240 VAC  
H7CX-A11S  
H7CX-A114S  
H7CX-AS  
---  
H7CX-A4S  
---  
---  
H7CX-AWS  
---  
12 to 24 VDC/  
24 VAC  
H7CX-A11SD1 ---  
H7CX-AUSD1 H7CX-AWSD1 ---  
None  
Contact output  
12 to 24 VDC  
---  
---  
---  
---  
H7CX-AD  
H7CX-A4D  
---  
---  
---  
Transistor output  
H7CX-ASD  
H7CX-A4SD ---  
H7CX-AWSD  
H7CX-A4WSD  
Note: Can be used as a 2-stage counter. In this case, each output can be flexibly allocated to either stage 1 or 2.  
Accessories (Order Separately)  
Name  
Models  
Flush Mounting Adapter (See note 1.)  
Y92F-30  
Waterproof Packing (See note 1.)  
Y92S-29  
Track Mounting/Front Connecting 11-pin  
Socket  
P2CF-11  
11-pin, finger-safe type  
11-pin  
P2CF-11-E  
Back Connecting Socket  
P3GA-11  
11-pin, finger-safe type  
P3GA-11 with Y92A-48G (See note 2.)  
Hard Cover  
Soft Cover  
Y92A-48  
Y92A-48F1  
PFP-50N  
PFP-100N  
PFP-100N2  
PFP-M  
Mounting Track  
50 cm (l) × 7.3 mm (t)  
1 m (l) × 7.3 mm (t)  
1 m (l) × 16 mm (t)  
End Plate  
Spacer  
PFP-S  
Note: 1. Supplied with screw-terminal models (i.e., excluding H7CX-A11@/-A114@ models).  
2. Y92A-48G is a finger-safe terminal cover attached to the P3GA-11 Socket.  
C-88  
Multifunction Preset Counter H7CX  
Specifications  
Ratings  
Item  
H7CX-A4@  
Preset counter  
H7CX-A@  
H7CX-A114@  
H7CX-A11@  
Classification  
Supported  
configurations  
1-stage counter, 1-stage counter with total counter (selectable)  
Rated supply voltage  
(See note 1.)  
100 to 240 VAC (50/60 Hz), 12 to 24 VDC  
100 to 240 VAC (50/60 Hz)  
24 VAC (50/60 Hz)/12 to 24 VDC  
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC)  
Power consumption  
Approx. 9.2 VA at 264 VAC  
Approx. 7.2 VA at 26.4 VAC  
Approx. 3.7 W at 12 VDC  
Mounting method  
Flush mounting  
Screw terminals  
0.5 N·m max.  
Flush mounting, surface mounting, or DIN track mounting  
External connections  
11-pin socket  
---  
Terminal screw  
tightening torque  
Display  
PV  
7-segment, negative transmissive LCD;  
11.5-mm-high characters, red or 9-mm-high characters, red or  
11.5-mm-high characters, red  
9-mm-high characters, red  
green (programmable)  
green (programmable)  
SV  
6-mm-high characters, green  
Digits  
4 digits (999 to 9,999)  
6 digits (99,999 to 999,999)  
SV range: 99,999 to 999,999  
(See note 2.) or 0 to 999,999  
4 digits (999 to 9,999)  
6 digits (99,999 to 999,999)  
SV range: 99,999 to 999,999  
(See note 2.) or 0 to 999,999  
SV range: 0 to 9,999  
SV range: 0 to 9,999  
Max. counting speed  
Input modes  
30 Hz or 5 kHz (selectable, ON/OFF ratio 1:1), common setting for CP1 and CP2  
Increment, decrement, command, individual, and quadrature  
CP1, CP2, reset, and total reset  
Input signals  
Input method  
No-voltage input/voltage input (switchable)  
No-voltage input  
ON impedance: 1 kmax. (Leakage current: 5 to 20 mA at 0 )  
ON residual voltage: 3 V max.  
OFF impedance: 100 kmin.  
Voltage input  
High (logic) level: 4.5 to 30 VDC  
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 k)  
Reset input  
Minimum reset input signal width: 1 or 20 ms (selectable), common setting for all inputs  
External, manual, and automatic reset (internal according to C, R, P, and Q mode operation)  
Reset system  
Output modes  
N, F, C, R, K-1, P, Q, A  
N, F, C, R, K-1, P, Q, A,  
K-2, D, L  
N, F, C, R, K-1, P, Q, A  
N, F, C, R, K-1, P, Q, A,  
K-2, D, L  
One-shot output time  
Output type  
0.01 to 99.99 s  
Contact type: SPDT  
Transistor type: 1 transistor  
Control output  
Contact output:  
3 A at 250 VAC/30 VDC, resistive load (cosφ=1)  
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)  
Transistor output:  
NPN open collector, 100 mA at 30 VDC  
Residual voltage: 1.5 VDC max. (approx. 1 V)  
Leakage current: 0.1 mA max.  
NEMA B300 Pilot Duty, 1/4 HP 3-A resistive load at 120 VAC, 1/3 HP 3-A resistive load at 240 VAC  
External power supply  
12 VDC ( 10%), 100 mA (except for H7CX-A@D models)  
Refer to Precautions for details.  
Key protection  
Yes  
Prescaling function  
Yes (0.001 to 9.999)  
Yes (0.001 to 99.999)  
Yes (0.001 to 9.999)  
Yes (0.001 to 99.999)  
Decimal point  
adjustment  
Yes (rightmost 3 digits)  
Sensor waiting time  
Memory backup  
250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)  
EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.  
Ambient temperature  
Operating: 10 to 55°C (10 to 50°C if counters are mounted side by side) (with no icing or condensation)  
Storage:  
25 to 65°C (with no icing or condensation)  
Ambient humidity  
Case color  
25% to 85%  
Black (N1.5), light gray (Munsell 5Y7/1, produced upon request)  
Waterproof packing, flush mounting adapter  
Attachments  
None  
Note: 1. Permissible ripple: 20% (p-p) max.  
2. Only when the following modes are selected.  
Input mode: command, individual, or quadrature; output mode: K-2, D, or L  
Multifunction Preset Counter H7CX  
C-89  
Ratings (contd.)  
Item  
H7CX-A4W@  
Preset counter  
H7CX-AW@  
H7CX-AU@  
Classification  
Preset counter/tachometer  
Supported configurations  
1-stage counter, 2-stage counter, 1-stage 1-stage counter, 2-stage counter, 1-stage counter with total counter, 1-stage counter with batch  
counter with total counter, 1-stage counter counter, dual counter (addition/subtraction), tachometer (selectable)  
with batch counter, dual counter (addition  
only) (selectable)  
Rated supply voltage (See note 1.)  
100 to 240 VAC (50/60 Hz),  
12 to 24 VDC  
100 to 240 VAC (50/60 Hz),  
24 VAC (50/60 Hz)/12 to 24 VDC,  
12 to 24 VDC  
100 to 240 VAC (50/60 Hz),  
24 VAC (50/60 Hz)/12 to 24 VDC  
Operating voltage range  
Power consumption  
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)  
Approx. 9.2 VA at 264 VAC  
Approx. 7.2 VA at 26.4 VAC  
Approx. 3.7 W at 12 VDC  
Mounting method  
External connections  
Terminal screw tightening torque  
Display  
Flush mounting  
Screw terminals  
0.5 N·m max.  
7-segment, negative transmissive LCD  
PV  
11.5-mm-high characters, red or green  
(programmable)  
9-mm-high characters, red or green (programmable)  
SV  
6-mm-high characters, green  
Digits  
4 digits (999 to 9,999)  
6 digits (99,999 to 999,999 or 0 to 999,999 when using as Tachometer)  
SV range: 99,999 to 999,999 (See note 2.) or 0 to 999,999  
SV range: 0 to 9,999  
Input signals  
Input method  
CP1, CP2, reset 1, and reset 2  
No-voltage input/voltage input (switchable)  
No-voltage input  
ON impedance: 1 kmax. (Leakage current: 5 to 20 mA at 0 )  
ON residual voltage: 3 V max.  
OFF impedance: 100 kmin.  
Voltage input  
High (logic) level: 4.5 to 30 VDC  
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 k)  
Counter  
Max. counting speed  
Input mode  
30 Hz or 5 kHz (selectable, ON/OFF ratio 1:1), common setting for CP1 and CP2  
Increment, decrement, command, individual, and quadrature  
Reset input  
Minimum reset input signal width: 1 or 20 ms (selectable), common setting for all inputs  
External, manual, and automatic reset (internal according to C, R, P, and Q mode operation)  
Reset system  
Output modes  
One-shot output time  
N, F, C, R, K-1, P, Q, A  
0.01 to 99.99 s  
---  
N, F, C, R, K-1, P, Q, A, K-2, D, L, H  
Tachometer  
Pulse measurement  
method  
Periodic measurement (Sampling period: 200 ms)  
30 Hz or 10 kHz (selectable)  
Max. counting speed  
Measuring ranges  
---  
---  
30 Hz: 0.01 to 30.00 Hz  
10 kHz: 0.01 Hz to 10 kHz  
Measuring accuracy  
Output modes  
---  
---  
---  
---  
---  
0.1% FS 1 digit max. (at 23 5°C)  
HI-LO, AREA, HI-HI, LO-LO  
0.1 to 99.9 s  
Auto-zero time  
Startup time  
0.0 to 99.9 s  
Average processing  
OFF/2/4/8 times  
Output type  
H7CX-A4W/-AW/-AWD1: SPDT (OUT2) and SPST-NO (OUT1)  
H7CX-A4WSD/-AWS/-AWSD/-AWSD1: 2 transistors  
H7CX-AU/-AUD1: SPDT and 1 transistor  
H7CX-AUSD1: 2 transistors  
(Output allocation possible)  
Control output  
Contact output:  
3 A at 250 VAC/30 VDC, resistive load (cosφ=1)  
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)  
Transistor output:  
NPN open collector, 100 mA at 30 VDC  
Residual voltage: 1.5 VDC max. (approx. 1 V)  
Leakage current: 0.1 mA max.  
NEMA B300 Pilot Duty, 1/4 HP 3-A resistive load at 120 VAC, 1/3 HP 3-A resistive load at 240 VAC  
External power supply  
12 VDC ( 10%) 100 mA (except for H7CX-A@D models)  
Refer to Precautions for details.  
Key protection  
Yes  
Prescaling function  
Decimal point adjustment  
Sensor waiting time  
Memory backup  
Yes (0.001 to 9.999)  
Yes (0.001 to 99.999)  
Yes (rightmost 3 digits)  
250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)  
EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.  
Ambient temperature  
Operating: 10 to 55°C (10 to 50°C if counters are mounted side by side) (with no icing or condensation)  
Storage:  
25 to 65°C (with no icing or condensation)  
Ambient humidity  
Case color  
25% to 85%  
Black (N1.5), light gray (Munsell 5Y7/1, produced upon request)  
Attachments  
Waterproof packing, flush mounting adapt- Waterproof packing, flush mounting adapter, labels for counter/tachometer DIP switch settings  
er  
Note: 1. Permissible ripple: 20% (p-p) max.  
2. Only when the following modes are selected.  
- Input mode: command, individual, or quadrature; output mode: K-2, D, L, or H  
- Dual count calculating mode: SUB; output mode: K-2, D, L, or H in dual counter operation  
C-90  
Multifunction Preset Counter H7CX  
Characteristics  
item  
H7CX  
Insulation resistance  
100 Mmin. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and be-  
tween non-continuous contacts  
Dielectric strength  
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts  
2,000 VAC (for 100 to 240 VAC), 50/60 Hz for 1 min between power supply and input circuit (1,000 VAC for 24 VAC/  
12 to 24 VDC)  
1,000 VAC (for H7CX-@SD/-@SD1), 50/60 Hz for 1 min between control output, power supply, and input circuit  
(2,000 VAC for models other than H7CX-@SD/-@SD1)  
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts  
Impulse withstand  
voltage  
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC and 12 to 24 VDC  
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC,  
1.5 kV for 24 VAC/12 to 24 VDC and 12 to 24 VDC  
Noise immunity  
1.5 kV (between power terminals) for 100 to 240 VAC and 24 VAC/12 to 24 VDC, 480 V for 12 to 24 VDC  
600 V (between input terminals)  
Square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)  
Static immunity  
Destruction: 15 kV  
Malfunction: 8 kV  
Vibration resistance  
Shock resistance  
Destruction: 10 to 55 Hz with 0.75-mm single amplitude, four cycles each in three directions (8 minutes per cycle)  
Malfunction: 10 to 55 Hz with 0.35-mm single amplitude, four cycles each in three directions (8 minutes per cycle)  
Destruction: 294 m/s2 each in three directions  
Malfunction: 98 m/s2 each in three directions  
Life expectancy  
Mechanical: 10,000,000 operations min.  
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load)  
See Life-test Curve on page 92.  
Approved safety  
standards  
(See note 1.)  
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)  
Conforms to VDE0106/P100 (finger protection).  
EMC  
(EMI)  
Emission Enclosure:  
Emission AC mains:  
EN61326  
EN55011 Group 1 class A  
EN55011 Group 1 class A  
(EMS)  
Immunity ESD:  
EN61326  
EN61000-4-2:  
4 kV contact discharge (level 2)  
8 kV air discharge (level 3)  
Immunity RF-interference:  
EN61000-4-3:  
10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);  
10 V/m (Pulse-modulated, 900 MHz 5 MHz) (level 3)  
10 V (0.15 to 80 MHz) (level 3)  
Immunity Conducted Disturbance: EN61000-4-6:  
Immunity Burst:  
EN61000-4-4:  
2 kV power-line (level 3);  
1 kV I/O signal-line (level 4)  
Immunity Surge:  
EN61000-4-5:  
1 kV line to lines (power and output lines) (level 2);  
2 kV line to ground (power and output lines) (level 3)  
Immunity Voltage Dip/Interruption EN61000-4-11: 0.5 cycle, 100% (rated voltage)  
Panel surface: IP66 and NEMA Type 4 (indoors) (See note 2.)  
Approx. 140 g  
Degree of protection  
Weight  
Note: 1. To meet UL listing requirements with the H7CX-A11@ models, an OMRON P2CF-11-@ or P3GA-11 Socket must be mounted on the  
H7CX. Otherwise, H7CX-A11@ models are considered to meet UL508 recognition requirements.  
2. A waterproof packing is necessary to ensure IP66 waterproofing between the H7CX and installation panel.  
Multifunction Preset Counter H7CX  
C-91  
Life-test Curve (Reference Values)  
Resistive Load  
Inductive Load  
1,000  
1,000  
700  
500  
700  
500  
300  
300  
30 VDC (cosφ=1)  
30 VDC (L/R=7 ms)  
250 VAC (cosφ=1)  
100  
100  
250 VAC cosφ=0.4  
70  
50  
70  
50  
0
1
2
3
4
0
1
2
3
4
Load current (A)  
Load current (A)  
Reference: A current of 0.15 A max. can be switched at 125 VDC (cosφ=1) and current of 0.1 A max. can be switched if L/R=7 ms. In both cases,  
a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P).  
Inrush Current (Reference Values)  
Model  
Voltage  
Applied voltage Inrush current (peak value) Time  
H7CX-A11/-AW  
100 to 240 VAC  
264 VAC  
5.8 A  
10.4 A  
6.0 A  
0.7 ms  
1.2 ms  
1.2 ms  
H7CX-A11D1/-AWD1 24 VAC/12 to 24 VDC 26.4 VAC  
H7CX-AD  
12 to 24 VDC  
26.4 VDC  
C-92  
Multifunction Preset Counter H7CX  
Connections  
Block Diagram  
(Basic  
insulation) Power supply  
circuit  
Output circuit  
(Basic  
insulation)  
(See note.)  
Display circuit  
Internal control  
circuit  
Input circuit  
Key switch  
circuit  
Note: All models except for H7CX-@D (models with 12 to 24-VDC power supplies) have basic insulation.  
I/O Functions  
Using as a Counter  
Inputs  
CP1, CP2  
In general (except for dual counter mode)  
Reads counting signals  
Increment, decrement, command, individual, and quadrature inputs accepted.  
When used as a dual counter  
Reads CP1 count signals with CP1 input and CP2 count signals with CP2 input.  
Increment signals can be input.  
Reset or Reset 1  
In general (except for dual counter mode)  
Resets present value and outputs (OUT2 when using the batch counter). (See note 1.)  
Counting cannot be performed during reset/reset 1 input.  
The reset indicator is lit during reset input.  
When used as a dual counter  
Resets the CP1 present value (to 0).  
Counting for CP1 input cannot be performed during reset 1 input.  
The reset indicator is lit during reset 1 input.  
Total Reset or  
Reset 2  
(See note 2.)  
When used as a 1-stage/2-stage counter  
Does not operate (Not used).  
When used as a total and preset counter  
Resets the total count value.  
Holds the total count value at 0 during total reset input.  
When used as a batch counter  
Resets the batch count value and batch output (OUT1).  
Holds the batch count value at 0 during reset 2 input.  
When used as a dual counter  
Resets the CP2 present value.  
Counting for CP2 input cannot be performed during reset 2 input.  
Outputs  
OUT1, OUT2  
Outputs take place according to designated output mode when corresponding preset is reached.  
Note: 1. In increment mode or increment/decrement mode, the present value returns to 0; in decrement mode, the present value returns to the  
set value with 1-stage models, and returns to set value 2 with 2-stage models.  
2. The reset indicator will not be lit when the total reset or reset 2 input is ON.  
Using as a Tachometer  
Inputs  
CP1, CP2  
Reads counting signals. (CP2 input is not used.)  
Reset 1, Reset 2  
Holds the measurement value and outputs. (Reset 2 input is not used.)  
The reset indicator is lit during hold.  
Outputs  
OUT1, OUT2  
Outputs signals according to the specified output mode when a set value is reached.  
Multifunction Preset Counter H7CX  
C-93  
Terminal Arrangement  
Confirm that the power supply meets specifications before use.  
H7CX-A/-A4  
1-stage Contact Output  
H7CX-AD/-A4D  
1-stage Contact Output  
0 V  
0 V  
6
7
2
8
9
10  
6
11  
1
7
2
8
9
10  
()  
Sensor, etc.  
Unused Unused  
Unused  
11  
Unused  
12  
Unused  
13  
(+)  
12 VDC  
12  
3
13  
5
External power  
supply  
1
3
4
5
4
OUT  
OUT  
()  
(+)  
Note: Terminals 1 and 6 are connected internally.  
H7CX-AS/-A4S  
1-stage Transistor Output  
H7CX-ASD/-A4SD  
1-stage Transistor Output  
0 V  
0 V  
6
11  
1
7
2
8
9
10  
6
7
8
9
10  
()  
Sensor, etc.  
Unused  
12  
Unused  
13  
Unused  
11  
Unused  
12  
Unused  
13  
(+)  
12 VDC  
External power  
supply  
3
4
5
1
2
3
4
5
OUT  
OUT  
()  
(+)  
Note: Terminals 1 and 6 are connected internally.  
H7CX-A11/-A114/-A11D1/-A114D1  
1-stage Contact Output  
H7CX-A11S/-A114S/-A11SD1  
1-stage Transistor Output  
Reset  
CP1  
Reset  
CP1  
Internal circuit  
CP2  
CP2  
Internal circuit  
6
6
5
7
5
7
Total reset  
Total reset  
4
8
4
8
0 V  
0 V  
3
9
3
9
()  
Sensor, etc.  
()  
Sensor, etc.  
2
10  
2
10  
1
11  
1
11  
12 VDC  
12 VDC  
(+)  
(+)  
External power supply  
External power supply  
OUT  
OUT  
(+)  
(+)  
()  
()  
Note: Do not connect unused terminals as relay terminals.  
C-94  
Multifunction Preset Counter H7CX  
H7CX-AW/-A4W/-AWD1  
2-stage Contact Output  
H7CX-AWS/-AWSD1  
2-stage Transistor Output  
0 V  
0 V  
6
11  
1
7
2
8
12  
3
9
10  
6
11  
1
7
2
8
12  
3
9
10  
()  
Sensor, etc.  
()  
Sensor, etc.  
(+)  
(+)  
12 VDC  
12 VDC  
13 OUT1  
13 OUT1  
External power  
supply  
External power  
supply  
4
5
4
5
OUT2  
OUT2  
()  
()  
(+)  
(+)  
H7CX-AWSD/-A4WSD  
2-stage Transistor Output  
H7CX-AUSD1  
1 or 2-stage Transistor Output  
0 V  
0 V  
6
7
8
12  
3
9
10  
6
11  
1
7
2
8
12  
3
9
10  
()  
Sensor, etc.  
Unused  
11  
(+)  
12 VDC  
13 OUT1  
13 OUT1 or 2  
External power  
supply  
1
2
4
5
4
5
OUT2  
OUT 1 or 2  
()  
(+)  
Note: 1. Terminals 1 and 6 are connected internally.  
2. Do not connect unused terminals as relay terminals.  
()  
(+)  
Note: Each output can be flexibly allocated to  
either stage 1 or 2 in function selection  
mode.  
H7CX-AU/-AUD1  
1-stage Contact, 1-stage Transistor Output  
0 V  
6
11  
1
7
2
8
12  
3
9
10  
()  
Sensor, etc.  
(+)  
12 VDC  
13 OUT1 or 2  
External power  
supply  
4
5
OUT 1 or 2  
()  
(+)  
Note: Each output can be flexibly allocated to either  
stage 1 or 2 by setting in function selection mode.  
Multifunction Preset Counter H7CX  
C-95  
Input Circuits  
CP1, CP2, Reset/Reset 1, and Total Reset/Reset 2 Input  
+14 V  
1 kΩ  
Internal  
circuit  
IN  
Note: The circuit shown above is for no-voltage input (NPN input).  
Input Connections  
The inputs of the H7CX are no-voltage (short-circuit or open) inputs or voltage inputs.  
No-voltage Inputs (NPN Inputs)  
Open Collector  
Voltage Output  
Contact Input  
PLC or  
sensor  
Sensor  
0 V  
0 V  
0 V  
6
3
7
7
8
5
9
6
10  
6
3
7
7
8
5
9
6
10  
6
3
7
7
8
5
9
6
10  
H7CX-A@  
H7CX-A11@  
H7CX-A@  
H7CX-A11@  
H7CX-A@  
H7CX-A11@  
4
4
4
Operates when the transistor turns ON.  
Operates when the transistor turns ON.  
Operates when the contact turns ON.  
No-voltage Input Signal Levels  
No-contact input  
Short-circuit level  
Transistor ON  
Residual voltage: 3 V max.  
Impedance when ON: 1 Kmax.  
(The leakage current is 5 to 20 mA when the  
impedance is 0 .)  
Open level  
Transistor OFF  
Impedance when OFF: 100 Kmin.  
Contact input  
Use contact which can adequately switch  
5 mA at 10 V.  
Maximum applicable voltage: 30 VDC max.  
DC Two-wire Sensor  
0 V  
6
3
7
7
8
5
9
6
10  
H7CX-A@  
H7CX-A11@  
4
Operates when the transistor turns ON.  
Applicable Two-wire Sensor  
Leakage current:1.5 mA max.  
Switching capacity:5 mA min.  
Residual voltage:3 VDC max.  
Operating voltage:10 VDC  
C-96  
Multifunction Preset Counter H7CX  
Voltage Inputs (PNP Inputs)  
Contact Input  
No-contact Input  
(NPN Transistor)  
No-contact Input  
(PNP Transistor)  
Sensor  
Sensor  
0 V  
0 V  
0 V  
6
3
7
7
8
5
9
6
10  
6
3
7
7
8
5
9
6
10  
6
3
7
7
8
5
9
6
10  
H7CX-A@  
H7CX-A11@  
H7CX-A@  
H7CX-A11@  
H7CX-A@  
H7CX-A11@  
4
4
4
Operates when the transistor turns OFF.  
Operates when the transistor turns ON.  
Operates when the contact turns ON.  
Voltage Input Signal Levels  
High level (Input ON):  
Low level (Input OFF):  
4.5 to 30 VDC  
0 to 2 VDC  
Maximum applicable voltage: 30 VDC max.  
Input resistance: Approx. 4.7 kΩ  
Multifunction Preset Counter H7CX  
C-97  
Nomenclature  
Indicators  
Operation Keys  
1
A
I
J
Reset Indicator (Orange)  
Lit when the reset input (1) or reset key  
Mode Key  
2
3
7
8
Used to switch mode and setting items.  
is ON.  
Reset Key  
4
5
6
9
B
C
The operation of the reset function  
depends on the configuration selected  
as shown in the table below.  
Up Keys: 1 to 4  
(6-digit models: 1 to 6)  
Key Protection Indicator (Orange)  
Control Output Indicator (Orange)  
One stage  
OUT1, OUT2: Two stages  
11  
12  
OUT:  
K
L
10  
D
E
Total Count Indicator  
Lit when the total count value is  
displayed.  
Down Keys: 1 to 4  
Front view of 4-digit model  
Batch Indicator  
Switches  
Lit when the batch count value is  
displayed.  
M
Key Protect Switch  
F
G
Set Value 1, 2 Stage Indicator  
1
(Factory setting) OFF  
ON  
Present Value (Main Display)  
Character height: 11.5 mm (6-digit: 9mm)  
2
3
7
8
4
5
6
H
Set Value (Sub-display)  
Character height: 6 mm  
DIP Switch  
N
9
11  
10  
Front view of 6-digit model  
13  
14  
Reset Operation by Reset Key  
Configuration  
Reset operation  
1-stage/2-stage Resets the present value and outputs.  
counter  
Total and preset Resets the present value and outputs.  
counter  
When the total count value is displayed, resets  
the present value, the total count value, and  
outputs.  
Batch counter  
Resets the present value and OUT2.  
When the batch count value is displayed,  
resets the present value, the batch count  
value, and outputs.  
Dual counter  
Tachometer  
Resets the CP1 present value, CP2 present val-  
ue, dual count value, and outputs.  
Maintains the measured value and outputs (hold  
function).  
C-98  
Multifunction Preset Counter H7CX  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
Counter (without Flush Mounting Adapter)  
Screw-terminal Models with External Power Supplies (Flush Mounting)  
H7CX-A  
H7CX-AS  
H7CX-A4  
H7CX-AW  
H7CX-AWS  
H7CX-A4W  
H7CX-AU  
H7CX-AUD1  
H7CX-AUSD1  
H7CX-A4S H7CX-AWD1  
H7CX-AWSD1  
48×48  
6
100  
44.8×44.8  
Note: M3.5 terminal screw (effective length: 6 mm)  
Screw-terminal Models without External Power Supplies (Flush Mounting)  
H7CX-AD  
H7CX-AWSD  
H7CX-AWSD  
H7CX-ASD  
H7CX-A4D  
H7CX-A4SD  
48×48  
6
64  
44.8×44.8  
Note: M3.5 terminal screw (effective length: 6 mm)  
11-pin Socket Models (Flush Mounting/Surface Mounting)  
H7CX-A11  
H7CX-A114  
H7CX-A114S  
H7CX-A114D1  
H7CX-A11S  
H7CX-A11D1  
H7CX-A11SD1  
14.4  
6
48×48  
72.5  
44.8×44.8  
Multifunction Preset Counter H7CX  
C-99  
Dimensions with Flush Mounting Adapter  
Screw-terminal Models with External Power Supplies  
Panel Cutouts  
(Provided with Adapter and Waterproof Packing)  
Panel cutouts are as  
shown below.  
(according to DIN43700).  
H7CX-A  
H7CX-AW  
H7CX-AU  
H7CX-AUD1  
H7CX-AUSD1  
H7CX-AS  
H7CX-A4  
H7CX-A4S  
H7CX-AWS  
H7CX-A4W  
H7CX-AWD1  
H7CX-AWSD1  
Y92S-29 (provided)  
Waterproof Packing  
Panel  
60 min.  
Y92F-30 (provided)  
Flush Mounting Adapter  
+0.6  
0  
45  
+0.6  
0  
45  
60 min.  
15 min.  
58  
(51)  
7.5  
48  
98.5  
Note: 1. The mounting panel thickness  
should be 1 to 5 mm.  
2. To allow easier operability, it is  
recommended that Adapters are  
mounted so that the gap between  
sides with hooks is at least 15 mm  
(i.e., so that the panel cutout interval  
is at least 60 mm).  
Screw-terminal Models without External Power Supplies  
(Provided with Adapter and Waterproof Packing)  
H7CX-AD  
H7CX-AWSD  
H7CX-A4WSD  
H7CX-ASD  
H7CX-A4D  
H7CX-A4SD  
Y92S-29 (provided)  
Waterproof Packing  
3. It is possible to mount counters  
side by side, but only in the  
direction without the hooks.  
If they are mounted side-by-side,  
water-resistant specifications  
cannot be ensured.  
Panel  
Flush Mounting Adapter  
58  
(51)  
n side by side mounting  
A
A = (48n 2.5)+1  
48  
7.5  
62.5  
0
11-pin Socket Models  
With Y92A-48F1 attached.  
A = {48n2.5 + (n1) x 4}+1  
(Adapter and Waterproof Packing Ordered Separately)  
0
With Y92A-48 attached.  
H7CX-A11  
H7CX-A114  
H7CX-A114S  
H7CX-A114D1  
A = (51n5.5)+1  
H7CX-A11S  
H7CX-A11D1  
H7CX-A11SD1  
0
Y92F-30 (order separately)  
Flush Mounting Adapter  
Y92S-29 (order separately)  
Waterproof Packing  
Panel  
P3GA-11  
(order separately)  
Back Connecting  
Socket  
58  
(51)  
48  
7.5  
98.7  
Dimensions with Front Connecting Socket  
H7CX  
-A11@  
109.7  
112  
P2CF-11  
Note: These dimensions vary with the kind of DIN track (reference value).  
C-100  
Multifunction Preset Counter H7CX  
Accessories (Order Separately)  
Note: All units are in millimeters unless otherwise indicated.  
Track Mounting/Front Connecting Socket  
P2CF-11  
Eleven,  
M3.5 x 7.5 sems  
3
4.5  
7.8  
Terminal Arrangement/  
Internal Connections  
(Top View)  
70 max.  
35.4  
Surface Mounting Holes  
Two, 4.5-dia.  
holes  
Two, 4.5 dia. or two, M4  
4
50 max.  
31.2 max.  
40 0.2  
Note: Track mounting is also possible.  
P2CF-11-E (Finger Safe Terminal Type)  
Conforming to VDE0106/P100  
Eleven,  
M3.5 x 7.5 sems  
5
4.5  
7.8  
3
1.2  
70 max.  
35.4  
Two, 4.5-dia.  
holes  
4
40 0.2  
30  
31.2 max.  
50 max.  
Back Connecting Socket  
P3GA-11  
Terminal Arrangement/  
Internal Connections  
(Bottom View)  
27 dia.  
45  
25.6  
4.5  
6.2  
45  
16.3  
Note: Finger protection can be ensured by using in combination with the Y92A-48G Terminal Cover.  
Finger Safe Terminal Cover  
Conforming to VDE0106/P100  
Y92A-48G  
Twelve, 6.4-dia. holes  
(Attachment for P3GA-11  
Socket)  
48 x 48  
34  
47.7 x 47.7  
16.5  
24.6  
27.6  
47.4  
Multifunction Preset Counter H7CX  
C-101  
Note: 1. Depending on the operating environment, the condition of  
the Soft Cover may deteriorate, and it may shrink or become  
harder. Therefore, it is recommended that the Soft Cover is  
replaced regularly.  
Hard Cover  
Y92A-48  
Soft Cover  
Y92A-48F1  
2. The H7CXs panel surface is water-resistive (conforming to  
IP66) and so even if drops of water penetrate the gaps be-  
tween the keys, there will be no adverse effect on internal  
circuits. If, however, there is a possibility of oil being present  
on the operators hands, use the Soft Cover. The Soft Cover  
ensures protection equivalent to IP54F against oil. Do not,  
however, use the H7CX in locations where it would come in  
direct contact with oil.  
Flush Mounting Adapter  
(provided with screw-terminal models)  
Waterproof Packing  
(provided with screw-terminal models)  
Y92F-30  
Y92S-29  
Mounting Track  
PFP-100N2  
PFP-100N, PFP-50N  
16  
7.3 0.15  
35 0.3  
4.5  
4.5  
29.2  
1.5  
24  
1
27  
35 0.3  
27 0.15  
1
15  
25  
25  
15 25  
25  
25  
25  
15 25  
25  
*
10  
10  
10  
10  
1,000 (500)  
(see note)  
1,000  
Note: The values shown in parentheses are for the PFP-50N.  
End Plate  
PFP-M  
Spacer  
PFP-S  
16  
12  
10  
6.2  
5
1.8  
1
35.5 35.3  
34.8  
50  
44.3  
1.8  
11.5  
1.3  
4.8  
M4 x 8  
pan head  
screw  
10  
16.5  
C-102  
Multifunction Preset Counter H7CX  
Precautions  
Transistor Output  
The transistor output of the H7CX is isolated from the internal cir-  
cuitry by a photocoupler, so the transistor output can be used as both  
NPN and PNP output.  
!Caution  
Do not use the product in locations subject to flammable or explo-  
sive gases. Doing so may result in explosion.  
The service life of the output relays depends on the switching  
capacity and switching conditions. Consider the actual application  
conditions and use the product within the rated load and electrical  
service life. Using the product beyond its service life may result in  
contact deposition or burning.  
NPN output  
PNP output  
Do not disassemble, repair, or modify the product. Doing so may  
result in electric shock, fire, or malfunction.  
Load  
Load  
+
Do not allow metal objects or conductive wires to enter the product.  
Doing so may result in electric shock, fire, or malfunction.  
+
Power for load  
Power for load  
The diode connected to the collector of the output transistor is used  
to absorb inverted voltage that is generated when an inductive load is  
connected to the H7CX.  
External Power Supply  
The capacity of the external power supply is 100 mA at 12 V. When  
using a 24 VAC/12 to 24 VDC power supply, reduce the load with the  
power supply voltage, as shown in the following diagram (DC power  
supplies only).  
Counter  
Inductive load  
(DC v ltage ppl only)  
+
Power for load  
100  
Changing the Set Values  
When changing the set value during operation, because the H7CX  
uses a constant read-in system, output will turn ON if the set value is  
equal to the present value.  
Operation with a Set Value and  
Present Value of 0  
20  
If the set value and present value are both 0, output will turn ON.  
Output will turn OFF during reset.  
15  
10.8  
Power pply vol age  
C)  
Using the Prescaling Function  
Observe the following points when setting a prescale value.  
Power Supplies  
When turning the power ON and OFF, input signal reception is possi-  
ble, unstable, or impossible as shown in the diagram below.  
Set the set value to a value less than {Maximum countable value −  
Prescale value}.  
Power  
supply  
ON  
OFF  
Example: If the prescale value is 1.25 and the counting range is  
0.000 to 999.999, set the set value to a value less than  
998.749 (= 999.999 1.25).  
200 ms  
5 ms  
0 to 90 ms  
0 to 1 s  
If the set value is set to a value greater than this, output will not turn  
ON.  
Input  
Impossible  
Possible  
Unstable  
Impossible  
Unstable  
Note: Output will turn ON, however, if a present value overflow occurs  
Turn the power ON and OFF using a relay with a rated capacity of 10  
A minimum to prevent contact deterioration due to inrush current  
caused by turning the power ON and OFF.  
(FFFFFF or FFFF).  
Setting the prescale value incorrectly may result in incorrect count-  
ing operation. Be sure to set the prescale value correctly.  
Apply the power supply voltage through a relay or switch in such a  
way that the voltage reaches a fixed value immediately, otherwise  
they may not be reset or a counter error may result.  
DIP Switch Setting  
Ensure that the power is turned OFF before changing DIP switch set-  
tings. Changing DIP switch settings with the power turned ON may  
result in electric shock due to contact with terminals subject to high  
voltages.  
Be sure that the capacity of the power supply is large enough, other-  
wise the counter may not start due to inrush current (reference value:  
approx. 10 A, 1.2 ms at 26.4 VAC) that may flow for an instant when  
the counter is turned ON.  
Make sure that the fluctuation of the supply voltage is within the per-  
missible range.  
Power Failure Backup  
All data is stored in the EEPROM when there is power failure. The  
EEPROM can be overwritten more than 100,000 times. EEPROM is  
overwritten when the power is turned OFF or when settings are  
changed.  
Make sure that the voltage applied is within the specified range, oth-  
erwise the internal elements of the counter may be damaged.  
Multifunction Preset Counter H7CX  
C-103  
Self-diagnostic Function  
The following displays will appear if an error occurs.  
Main display  
Sub-display  
Error  
Output status  
Correction method  
Set value after  
reset  
------  
No change  
Present value underflow  
(See note 3.)  
No change  
Either press the reset key or turn ON No change  
reset input.  
(----)  
(See notes 1 and  
2.)  
ffffff  
No change  
Not lit  
Present value overflow  
(See note 4.)  
No change  
OFF  
Either press the reset key or turn ON No change  
reset input. (See note 5.)  
(ffff)  
(See notes 1 and  
2.)  
e1  
CPU  
Either press the reset key or reset the No change  
power supply.  
e2  
e2  
Not lit  
Memory error (RAM)  
OFF  
OFF  
Reset the power supply.  
No change  
0
sum  
Memory error (EEP)  
(See note 6.)  
Reset to the factory settings using the  
reset key.  
Note: 1. The display for 4-digit models is given in parentheses.  
2. Display flashes (1-second cycles).  
3. Occurs when the present value or the total count value goes below 99,999 (999 with 4-digit models).  
4. Occurs when the present value (or measurement value) reaches 999,999 (9,999 with 4-digit models) under the following conditions:  
The output mode is K-2, D, L, or H.  
The H7CX is set for dual counter or tachometer operation.  
5. Except when the H7CX is set for tachometer operation.  
6. Includes the case where the EEPROM has reached its overwrite lifetime.  
Response Delay Time When  
Resetting (Transistor Output)  
The following table shows the delay from when the reset signal is  
input until the output is turned OFF.  
Wiring  
Wiring input lines in the same conduit as power lines or other high-  
voltage lines may result in malfunction due to noise. Wire the input  
lines separately, away from lines carrying high-voltages. In addition,  
make the input wiring as short as possible and use shield lines or  
metal wiring conduits.  
(Reference values)  
Pay attention to terminal polarity to ensure correct wiring.  
Minimum reset signal width  
Output delay time  
0.8 to 1.2 ms  
15 to 25 ms  
1 ms  
Mounting  
20 ms  
Tighten the two mounting screws on the Adaptor. Tighten them alter-  
nately, a little at a time, so as to keep them at an equal tightness.  
Output Delay Time  
The following table shows the delay from when the present value  
passes the set value until the output is produced.  
The H7CXs panel surface is water-resistive (conforming to NEMA 4  
and IP66). In order to prevent the internal circuit from water penetra-  
tion through the space between the timer and operating panel, attach  
a waterproof packing between the timer and installation panel and  
secure the waterproof packing with the Y92F-30 Flush-mounting  
Adapter.  
Actual measurements in N and K-2 modes.  
(Reference values)  
Control output type Maximum counting Output delay time  
speed  
Contact output  
30 Hz  
5 kHz  
30 Hz  
5 kHz  
16.5 to 24.0 ms  
3.7 to 5.6 ms  
0.5 to 1 mm  
It is recommended that the space between  
the screw head and the adapter should be  
0.5 to 1 mm.  
Transistor output  
12.0 to 20.0 ms  
0.2 to 0.55 ms  
Note: The above times may vary slightly depending on the mode or  
operating conditions.  
Maximum Counting Speed for  
Batch Counter  
The maximum counting speed for batch counter operation is 5 kHz.  
The batch counter counts the number of times the count reaches the  
set value.  
C-104  
Multifunction Preset Counter H7CX  
Operating Environment  
Use the product within the ratings specified for submerging in water  
and exposure to oil.  
Do not use the product in locations subject to vibrations or shocks.  
Using the product in such locations over a long period may result in  
damage due to stress.  
Do not use the product in locations subject to dust, corrosive  
gases, or direct sunlight.  
Separate the input signal devices, input signal cables, and the  
product from the source of noise or high-tension cables producing  
noise.  
Separate the product from the source of static electricity when  
using the product in an environment where a large amount of static  
electricity is produced (e.g., forming compounds, powders, or fluid  
materials being transported by pipe).  
Organic solvents (such as paint thinner), as well as very acidic or  
basic solutions might damage the outer casing of the H7CX.  
Use the product within the ratings specified for temperature and  
humidity.  
Do not use the product in locations where condensation may occur  
due to high humidity or where temperature changes are severe.  
Store at the specified temperature. If the H7CX has been stored at  
a temperature of less than -10°C, allow the H7CX to stand at room  
temperature for at least 3 hours before use.  
Leaving the H7CX with outputs ON at a high temperature for a long  
time may hasten the degradation of internal parts (such as electro-  
lytic capacitors). Therefore, use the product in combination with  
relays and avoid leaving the product as long as more than 1 month  
with the output turned ON.  
X2/b  
T/a  
X1/a  
X1/a  
T
X1  
X2  
Auxiliary relay  
X
(e.g., MY Relay)  
The load current must be within the rated current.  
Insulation  
Specifications call for basic insulation between the power supply  
and input terminals, between the power supply and output termi-  
nals, and between the input and output terminals. (The H7CX-A@D  
is not insulated between the power supply and input terminals.)  
Input and output terminals are connected to devices without  
exposed charged parts.  
Input and output terminals are connected to devices with basic  
insulation that is suitable for the maximum operating voltage.  
Multifunction Preset Counter H7CX  
C-105  
Operating Procedures  
Setting Procedure Guide  
Setting for Counter Operation  
(1-stage/2-stage Counter, Total and Preset Counter, Batch Counter, Dual Counter)  
When Using Basic Settings Only  
Basic Settings  
The settings can be performed easily with the DIP switch.  
For details on the setting methods, refer to page 21.  
Counting speed (30 Hz, 5 kHz)  
Input mode (UP, DOWN)  
1
2
3
4
5
6
7
8
Output mode (N, F, C, K-1)  
ON  
One-shot output time (0.5 s, 0.05 s)(See note 2.)  
Reset input signal width (20 ms, 1 ms)  
NPN/PNP input mode (NPN, PNP)  
OFF  
When Using Settings Other than the Above  
When Using Advanced Functions  
All the functions can be set with the operation keys.  
For details on the setting methods, refer to page 22.  
Settings for advanced functions other than the basic  
settings above can be performed with the operation keys.  
For details on the setting methods, refer to page 22.  
Other Settings  
Advanced Functions  
Dual count calculating mode  
Input mode (UP/DOWN A, UP/DOWN B, UP/DOWN C)  
Output mode (R, P, Q, A, K-2, D, L, H)  
One-shot output time (except for 0.5 s and 0.05 s) (See note 2.)  
Output 1 time (for 2-stage counter)  
Decimal point position  
Prescale value  
Display color  
Output allocation  
Key protect level  
Note: 1. At the time of delivery, the H7CX is set to the 1-stage counter (2-stage counter for H7CX-AW@/-A4W@ models) configuration.  
2. Set to output 2 time when using as a 2-stage counter or batch counter.  
Setting for Tachometer Operation  
When Using Basic Settings Only  
Basic Settings  
The settings can be performed easily with the DIP switch.  
For details on the setting methods, refer to page 33.  
Counting speed (30 Hz, 10 kHz)  
1
2
3
4
5
6
7
8
Output mode (HI-LO, AREA, HI-HI, LO-LO)  
Average processing (OFF, 2, 4, 8 times)  
NPN/PNP input mode (NPN, PNP)  
ON  
OFF  
When Using Advanced Functions  
Settings for advanced functions other than the basic  
settings above can be performed with the operation keys.  
For details on the setting methods, refer to page 34.  
Advanced Functions  
Decimal point position  
Prescale value  
Auto-zero time  
Startup time  
Display color  
Output allocation  
Key protect level  
Note: At the time of delivery, the H7CX is set to the 2-stage counter (1-stage counter for H7CX-AU@ models) configuration.  
C-106  
Multifunction Preset Counter H7CX  
Operating Procedures (Counter Function)  
Settings for Basic Operations  
Settings for basic functions can be performed with just the DIP switch.  
Be sure to set pin 1 to ON.  
1
2
3
4
5
6
7
8
ON  
OFF  
Note: All of the pins are factory-set to OFF.  
Item  
OFF  
ON  
1
DIP switch settings en- Disabled  
able/disable  
Enabled  
2
3
Counting speed  
Input mode  
30 Hz  
5 kHz  
UP (increment) DOWN (decre-  
ment)  
Pin 4  
OFF  
Pin 5  
OFF  
Output mode  
4
5
6
Output mode  
Refer to the table on the right.  
N
F
ON  
OFF  
ON  
One-shot output time  
(See note.)  
0.5 s  
0.05 s  
OFF  
ON  
C
7
8
Reset input signal width 20 ms  
NPN/PNP input mode NPN  
1 ms  
PNP  
ON  
K-1  
Note: Set to one-shot output 2 time when using as a 2-stage counter  
or batch counter.  
Easy Confirmation of Switch Settings Using Indicators  
The ON/OFF status of the DIP switch pins can be  
confirmed using the front display. For details, refer to page 124.  
Note: 1. Be sure to set pin 1 of the DIP switch to ON. If it is set to OFF, the DIP switch settings will not be enabled.  
2. Changes to DIP switch settings are enabled when the power is turned ON.  
3. When setting input modes, output modes, or output times that cannot be set with the DIP switch, all of the settings have to be made using  
the operation keys. For details on the setting methods, refer to page 108. When making settings using the operation keys, be sure to set  
pin 1 of the DIP switch to OFF.  
Switching to Total and Preset Counter, Batch Counter, and Dual Counter Operation (See note.)  
The H7CX is factory-set to the 1-stage  
Power ON  
counter (2-stage counter for H7CX-AW@/-  
A4W@ models) configuration. To change to  
a different configuration, use the procedure  
shown on the right. For details, refer to  
Configuration selection mode  
Run mode  
page 39.  
Note: This includes changing to the 2-  
stage counter (or 1-stage counter)  
configuration.  
Hold down for  
1 s min. (See note.)  
1
MODE  
+
MODE  
1
Note: The  
key must be pressed before the  
key.  
Select the configuration using the  
and  
keys ( key with 6-digit models).  
(1-stage  
counter)  
(2-stage (Total and  
counter) preset counter) counter)  
(Batch  
(Dual  
counter)  
(Tachometer)  
Note: The configurations that can be selected vary with the model.  
Advanced-Function Settings  
After making DIP switch settings for basic operations, advanced functions (see note) can be added using the operation keys.  
For details, refer to page 22.  
Note: Advanced functions consist of the dual count calculating mode, output 1 time (for 2-stage counter), decimal point position,prescale value, display  
color, output allocation, and key protect level.  
Multifunction Preset Counter H7CX (Counter Function)  
C-107  
Settings for All Functions  
Note: At the time of delivery, the H7CX is set to the 1-stage counter (2-stage counter for H7CX-AW@/-A4W@ models) configuration. When using  
as a 2-stage (or 1-stage) counter, total and preset counter, batch counter, or dual counter, switch to the configuration using the procedure  
given on page 124.  
Settings that cannot be performed with the DIP switch are performed with the operation keys.  
Power ON  
For details on operations in run mode, refer to page 25.  
Note: 1. If the mode is switched to the function setting mode during operation, operation will con-  
tinue.  
2. Changes made to settings in function setting mode are enabled for the first time when the  
mode is changed to run mode. Also, when settings are changed, the counter is reset  
(present value initialized and output turned OFF) on returning to run mode.  
See note 1.  
3 s min.  
See note 2.  
3 s min.  
The characters displayed in reverse video are the default settings.  
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).  
If pin 1 of the DIP switch is set to ON, the setting items indicated by  
will not be displayed.  
r
r
Set each setting item using the  
r
keys. (  
key only for 6-digit models)  
Note 3:  
See note 3.  
When using as a dual counter:  
Dual count  
calculating mode  
Input mode  
See note 4. See note 4.  
(UP)  
(DOWN) (UP/DOWN A) (UP/DOWN B) (UP/DOWN C)  
See note.  
Note 4: Displayed for output modes other than K-2, D, L, and H only.  
(Addition) (Subtraction)  
Note: Displayed for output modes  
other than K-2, D, L, and H  
only.  
Output mode  
See note 6.  
See note 5.See note 5.See note 5.See note 5.  
(N)  
(F)  
(C)  
(R)  
(K-1)  
(P)  
(Q)  
(A)  
(K-2)  
(D)  
(L)  
(H)  
Note 6:  
Note: 5. Display only when the input mode is UP/DOWN A, B,  
or C with 6-digit models (with H7CX-AU@/-AW@  
models only for H).  
When using as a 2-stage counter:  
One-shot  
output  
time  
One-  
shot  
output  
2 time  
(0.01s) (0.50s) (99.99s)  
Note: Displayed only when the  
output mode is C, R, K-1,  
P, Q, A, or K-2.  
(0.01s) (0.50s) (99.99s)  
Note: Displayed only when the output mode is C, R, K-1, P,  
Q, A, or K-2.  
One-  
shot  
output  
1 time  
Counting  
speed  
(Outputs held) (0.01s) (99.99s)  
If the output time is 0.00, hold is  
displayed.  
(30Hz)  
(5kHz)  
Note 1: Displayed for output modes  
other than D, L, and H.  
Note 2: HOLD cannot be set when the  
output mode is K-2.  
When using as a  
batch counter:  
Reset input  
signal  
width  
One-  
shot  
output  
2 time  
(0.01s) (0.50s) (99.99s)  
Note: Displayed only when the output  
mode is C, R, K-1, P, Q, A, or K-2.  
(20ms)  
(1ms)  
Decimal  
point  
See note 7.  
position  
No decimal  
point  
One digit after  
decimal point  
Two digits after  
decimal point  
Three digits after  
decimal point  
Prescale  
value  
See note 7.  
Note 7: The displays for 4-digit models are shown inside  
parentheses.  
(0.001)  
(1.000)  
(99.999) [9.999]  
NPN/PNP  
input mode  
(NPN  
input)  
(PNP  
input)  
Display color  
(Red)  
(Green) (Red-green) (Green-red)  
Note: Displayed for terminal-block models (except H7CX-A11@) only.  
Output  
allocation  
Note: Displayed for H7CX-AU@ models only.  
Key protect  
level  
(KP-1)  
(KP-2)  
(KP-3)  
(KP-4)  
(KP-5)  
C-108  
Multifunction Preset Counter H7CX (Counter Function)  
Explanation of Functions  
Input Mode (cntm) (Setting possible using DIP switch.)  
Prescale Value (pscl)  
Set increment mode (UP), decrement mode (DOWN), or one of the  
increment/decrement modes (UP/DOWN A, UP/DOWN B, or UP/  
DOWN C) as the input mode. Input modes other than UP or DOWN  
modes cannot be set using the DIP switch and so use the operation  
keys if other modes are required. (For details on the operation of the  
input modes, refer to Input Modes and Present Value on page 112.)  
Pulses input to the counter are converted according to the specified  
prescale value. (Setting range: 0.001 to 99.999 for 6-digit models  
and 0.001 to 9.999 for 4-digit models.)  
Example: To display the feed distance for systems that output  
25 pulses for a feed length of 0.5 m in the form @@.@@ m:  
1. Set the decimal point position to 2 decimal places.  
Dual Count Calculating Mode (calm)  
2. Set the prescale value to 0.02 (0.5÷25).  
When using as a dual counter, select either ADD (addition) or SUB  
(subtraction) as the calculation method for the dual count value. SUB  
mode can be used only when K-2, D, L, or H is selected as the output  
mode with 6-digit models.  
0.5 m  
ADD: Dual count value = CP1 PV + CP2 PV  
SUB: Dual count value = CP1 PV CP2 PV  
Output Mode (outm) (Setting possible using DIP switch.)  
25 pulses  
Set the way that control output for the present value is output. The  
possible settings are N, F, C, R, K-1, P, Q, A, K-2, D, L, and H. Output  
modes other than N, F, C, or K-1 cannot be set using the DIP switch  
and so use the operation keys if other modes are required. The out-  
put modes that can be set vary with the model. (For details on the  
operation of the output modes, refer to Input/Output Mode Settings  
on page 113.)  
Encoder  
NPN/PNP Input Mode (imod)  
Select either NPN input (no-voltage input) or PNP input (voltage  
input) as the input format. The same setting is used for all external  
inputs. For details on input connections, refer to Input Connection on  
page 96.  
One-shot Output Time (otim) (Setting possible using DIP  
switch.)  
Set the one-shot output time (0.01 to 99.99 s) for control output.  
One-shot output can be used only when C, R, K-1, P, Q, A, or K-2 is  
selected as the output mode. Output times other than 0.5 s or 0.05 s  
cannot be set with the DIP switch and so use the operation keys if  
other settings are required.  
Display Color (colr)  
Set the color used for the present value.  
Output OFF (See note.)  
Red (fixed)  
Output ON (See note.)  
red  
grn  
r-g  
g-r  
One-shot Output 2 Time (otm2) (Setting possible using  
DIP switch.)  
Green (fixed)  
Red  
Green  
Red  
When using as a 2-stage counter or batch counter, set the one-shot  
output time (0.01 to 99.99 s) for control output (OUT2). One-shot out-  
put can be used only when C, R, K-1, P, Q, A, or K-2 is selected as  
the output mode. Output times other than 0.5 s or 0.05 s cannot be  
set with the DIP switch and so use the operation keys if other settings  
are required.  
Green  
Note: When using as a 2-stage counter, this is the status of output 2.  
Output Allocation (otst)  
When using H7CX-AU@ models as a 2-stage counter, the output can  
be flexibly allocated to either stage 1 or 2.  
Transistor output can be allocated to SV1 and contact output for SV2  
or vice verse, as in the following table.  
One-shot Output 1 Time (otm1)  
When using as a 2-stage counter, set the one-shot output time (0.01  
to 99.99 s) for control output (OUT1). One-shot output can be used  
only when D, L, or H is selected as the output mode. If the output  
time is set to 0.00, hold is displayed, and outputs are held. HOLD  
cannot be set when the output mode is K-2.  
H7CX-AU/-AUD1  
OUT1  
Transistor (12-13)  
Contact (3, 4, 5)  
OUT2  
Contact (3, 4, 5)  
Transistor (12-13)  
off  
on  
Counting Speed (cnts) (Setting possible using DIP  
switch.)  
H7CX-AUSD1  
Set the maximum counting speed (30 Hz/5 kHz) for CP1 and CP2  
inputs together. If contacts are used for input signals, set the count-  
ing speed to 30 Hz. Processing to eliminate chattering is performed  
for this setting.  
OUT1  
OUT2  
off  
on  
Transistor (12-13)  
Transistor with diode  
(3, 4, 5)  
Reset Input Signal Width (iflt) (Setting possible using  
DIP switch.)  
Transistor with diode  
(3, 4, 5)  
Transistor (12-13)  
Set the reset input signal width (20 ms/1 ms) for reset/reset 1 and  
total reset/reset 2 inputs together. If contacts are used for input sig-  
nals, set the counting speed to 20 ms. Processing to eliminate chat-  
tering is performed for this setting.  
Decimal Point Position (dp)  
Decide the decimal point position for the present value, CP1/CP2  
present values, set value (SV1, SV2), total count value, and dual  
count set value.  
Multifunction Preset Counter H7CX (Counter Function)  
C-109  
Key Protect Level (kypt)  
Set the key protect level.  
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the  
key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the key-  
protect switch after the H7CX is mounted to the panel.  
OFF ON  
(See note)  
Note: Factory-set to OFF  
Key protect indicator  
Level  
Meaning  
Details  
Switching display in  
run mode  
Changing mode  
(See note.)  
Reset key  
Up/down key (Up key for  
6-digit models)  
KP-1 (default setting)  
No  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
No  
Yes  
No  
No  
Yes  
Yes  
No  
No  
No  
KP-2  
KP-3  
KP-4  
KP-5  
No  
No  
No  
No  
Note: Changing mode to configuration selection mode ( MODE  
+
1 s min.) or function setting mode ( MODE 3 s min.).  
1
C-110  
Multifunction Preset Counter H7CX (Counter Function)  
Operation in Run Mode  
Set values for each digit as required using the  
and  
keys. (  
key only for 6-digit models.)  
1-stage Counter  
2-stage Counter  
Present Value  
Shows the present count value.  
Present value  
Set value  
Set Value (Set Value 1, Set Value 2)  
Set the set value. When the present  
value reaches the set value, signals  
are output according to the specified  
output mode.  
Present value  
Set value 1  
Present value  
Set value 2  
Total and Preset Counter  
Present Value/Set Value  
Present value  
Set value  
Same as 1-stage counter.  
Total Count Value  
Shows the present total count value.  
Total count value  
Batch Counter  
Present Value/Set Value  
Same as 1-stage counter.  
Present value  
Set value  
Batch Count Value  
Shows the number of times the count has  
been completed for the present value.  
Batch Count Set Value  
Batch count value  
Set the batch count set value. When the  
batch count value reaches the batch count  
set value, batch output (OUT1) turns ON.  
Batch count set value  
Dual Counter  
Dual Count Value  
Shows the sum of the CP1 present value and CP2 present value when the  
dual count calculating mode is ADD and shows the value obtained by  
subtracting the CP2 present value from the CP1 present value when the dual  
count calculating mode is SUB.  
Dual count value  
Dual count set value  
Dual Count Set Value  
Set the dual count set value. When the dual count value reaches the dual  
count set value, signals are output according to the specified output mode.  
CP1 present value  
CP2 present value  
CP1/CP2 Present Value  
Show the present count values for CP1 and CP2 present values respectively.  
Multifunction Preset Counter H7CX (Counter Function)  
C-111  
Input Modes and Present Value  
UP (Increment) Mode  
DOWN (Decrement) Mode  
CP1: Count input; CP2: Prohibit (gate) input  
CP1: Count input; CP2: Prohibit (gate) input  
H
CP1  
L
H
CP1  
L
A
A
A
A
Prohibit  
Prohibit  
H
L
H
L
CP2  
CP2  
n
n1  
5
Present  
value  
n2  
4
Present  
value  
n3  
3
n4  
2
n5  
1
0
0
0
a must be greater than the minimum signal width. (See note 2.)  
a must be greater than the minimum signal width. (See note 2.)  
CP1: Prohibit (gate) input; CP2: Present value  
CP1: Prohibit (gate) input; CP2: Count input  
H
CP1  
L
H
CP1  
L
A
A
A
A
Prohibit  
Prohibit  
H
L
H
L
CP2  
CP2  
n
5
n1  
n2  
4
Present  
value  
3
n3  
Present  
value  
2
n4  
1
n5  
0
0
0
a must be greater than the minimum signal width. (See note 2.)  
a must be greater than the minimum signal width. (See note 2.)  
Note: 1. If the configuration selection is set to dual counter, CP1 and  
CP2 input will operate in the same way as the count input  
(CP1) of UP (increment) mode.  
UP/DOWN A  
Command Input Mode  
H
CP1  
2. a must be greater than the minimum signal width and b  
must be at least 1/2 the minimum signal width. If they are  
less, a count error of 1 may occur.  
L
A
A
H
L
CP2  
Minimum signal width:16.7 ms (when maximum counting  
speed = 30 Hz)  
3
3
Present  
value  
100 µs (when maximum counting  
speed = 5 kHz)  
2
2
2
1
1
3. The meaning of the H and L symbols in the tables is ex-  
0
plained below.  
0
a must be greater than the minimum signal width. (See note 2.)  
Input method No-voltage input  
Voltage input  
(PNP input)  
Symbol  
(NPN input)  
Short-circuit  
Open  
UP/DOWN B  
Individual Input Mode  
H
L
4.5 to 30 VDC  
0 to 2 VDC  
H
CP1  
L
H
CP2  
L
3
3
Present  
value  
2
2
2
1
1
1
0
0
UP/DOWN C  
Quadrature Input Mode  
H
L
CP1  
CP2  
B
B B B  
H
L
3
3
Present  
value  
2
2
2
1
1
0
0
b must be at least 1/2 the minimum signal width. (See note 2.)  
C-112  
Multifunction Preset Counter H7CX (Counter Function)  
Input/Output Mode Settings  
Operation for 1-stage models is the same as that for OUT2.  
One-shot output from OUT1  
(The one-shot output time  
can be set in the range 0.01  
to 99.99s.)  
Self-holding output  
Self-holding output  
One-shot output from OUT2  
When using a 2-stage model as a 1-stage counter, total and preset  
counter, or dual counter, OUT1 and OUT2 turn ON and OFF simulta-  
neously.  
Input mode  
DOWN  
Operation after count  
completion  
UP  
UP/DOWN A, B, C  
Reset/  
reset 1  
Output  
mode  
setting  
N
The outputs and  
present value display  
are held until reset/re-  
set 1 is input.  
999999  
Set  
value 2  
Set  
value 1  
0
OUT1  
OUT2  
Reset/  
reset 1  
F
The present value dis-  
play continues to in-  
crease/decrease. The  
outputs are held until  
reset/reset 1 is input.  
999999  
Set  
value 2  
Set  
value 1  
0
OUT1  
OUT2  
Reset/  
reset 1  
C
As soon as the count  
reachesSV, thepresent  
value display returns to  
the reset start status.  
The present value dis-  
play does not show the  
present value upon  
count-up.  
999999  
Set  
value 2  
Set  
value 1  
0
OUT1  
The outputs repeat  
one-shot operation.  
OUT1 self-holding out-  
put turns OFF after the  
OUT2 one-shot output  
time.The OUT1 one-  
shot output time is inde-  
pendent of OUT2.  
OUT2  
Reset/  
reset 1  
R
The present value dis-  
play returns to the reset  
start status after the  
one-shot output time.  
999999  
Set  
value 2  
The outputs repeat  
one-shot operation.  
Set  
value 1  
0
OUT1 self-holding out-  
put turns OFF after the  
OUT2 one-shot output  
time.The OUT1 one-  
shot output time is inde-  
pendent of OUT2.  
OUT1  
OUT2  
Note: 1. The full scale (FS) for H7CX 4-digit models is 9999.  
2. When the present value reaches 999999, it returns to 0.  
3. Counting cannot be performed during reset/reset 1 input.  
4. If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.  
5. If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output  
will turn ON again for the duration of the output time setting once the power supply has recovered.  
6. Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.  
Multifunction Preset Counter H7CX (Counter Function)  
C-113  
Input mode  
DOWN  
Operation after  
count completion  
UP  
UP/DOWN A, B, C  
Reset/  
reset 1  
Output K-1  
mode  
setting  
The present value dis-  
play continues to in-  
crease/decrease.  
OUT1 self-holding  
outputturnsOFFafter  
the OUT2 one-shot  
output time.The  
OUT1 one-shot out-  
put time is indepen-  
dent of OUT2.  
999999  
Set  
value 2  
Set  
value 1  
0
OUT1  
OUT2  
Reset/  
reset 1  
P
The present value dis-  
play does not change  
during the one-shot  
output time period,  
but the actual count  
returns to the reset  
start status.  
999999  
Set  
value 2  
Set  
value 1  
0
The outputs return to  
the one-shot start  
state and repeat one-  
shot operation.  
OUT1  
OUT2  
OUT1 self-holding  
outputturnsOFFafter  
the OUT2 one-shot  
output time. The  
OUT1 one-shot out-  
put time is indepen-  
dent of OUT2.  
Q
The present value  
continues to increase/  
decrease for the one-  
shot output time, but  
returns to the reset  
start status after the  
one-shot output time  
has elapsed.  
Reset/  
reset 1  
999999  
Set  
value 2  
Set  
value 1  
0
OUT1  
The outputs repeat  
one-shot operation.  
OUT1 self-holding  
outputturnsOFFafter  
the OUT2 one-shot  
output time. The  
OUT2  
OUT1 one-shot out-  
put time is indepen-  
dent of OUT2.  
Reset/  
reset 1  
A
The present value dis-  
play and OUT1 self-  
holding output is held  
until reset/reset 1 is  
input. OUT1 and  
OUT2 are indepen-  
dent.  
999999  
Set  
value 2  
Set  
value 1  
0
OUT1  
OUT2  
Note: 1. The full scale (FS) for H7CX 4-digit models is 9999.  
2. When the present value reaches 999999, it returns to 0.  
3. Counting cannot be performed during reset/reset 1 input.  
4. If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.  
5. If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output  
will turn ON again for the duration of the output time setting once the power supply has recovered.  
6. Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.  
C-114  
Multifunction Preset Counter H7CX (Counter Function)  
(The one-shot output time  
can be set in the range 0.01  
to 99.99s.)  
Self-holding Instantaneous One-shot  
output (equals) output output  
Input mode  
Operation after count  
completion  
UP/DOWN A, B, C  
Reset/  
reset 1  
Output K-2  
mode  
setting  
The display continues to in-  
crease/decrease until the over-  
flow or underflow value is  
999999  
Set  
value 2  
reached. One-shot output only.  
Set  
value 1  
0
99999  
OUT1  
OUT2  
Reset/  
reset 1  
D
The display continues to in-  
crease/decrease until the over-  
flow or underflow value is  
reached. The outputs are ON  
while the count is equal.  
999999  
Set  
value 2  
Set  
value 1  
0
99999  
OUT1  
OUT2  
Reset/  
reset 1  
L
The display continues to in-  
crease/decrease until the over-  
flow or underflow value is  
reached.  
999999  
Set  
value 2  
OUT1 is held while the present  
value is less than or equal to set  
value 1. OUT2 is held while the  
present value is greater than or  
equal to set value 2.  
Set  
value 1  
0
99999  
OUT1  
OUT2  
Reset/  
reset 1  
H
The display continues to in-  
crease/decrease until the over-  
flow or underflow value is  
reached.  
999999  
Set  
value 2  
OUT1 is held while the present  
value is greater than or equal to  
set value 1. OUT2 is held while  
the present value is greater than  
or equal to set value 2.  
Set  
value 1  
0
99999  
OUT1  
Note:  
H mode is available only when  
using a 6-digit model as a 2-  
stage counter.  
OUT2  
Note: 1. Counting cannot be performed during reset/reset 1 input.  
2. If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.  
3. If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output  
will turn ON again for the duration of the output time setting once the power supply has recovered.  
4. Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.  
Multifunction Preset Counter H7CX (Counter Function)  
C-115  
Total and Preset Counter Operation  
The H7CX has a total counter, separate from the 1-stage preset counter, for counting the total accumulated value.  
The total counter continues to count the  
Reset/reset 1  
total accumulated value when the present  
value is reset using reset/reset 1 input  
(reset key).  
Total reset/reset 2  
Present value  
The total count value is reset when the  
total reset/reset 2 input is turned ON. If the  
reset key is pressed while the total count  
value is displayed, the total count value is  
reset. The present value is also reset at  
this time.  
0
999999  
Total count value  
The counting range of the total counter is  
99,999 to 999,999 (999 to 9,999). The  
total count value returns to 0 when it  
reaches the full scale limit.  
0
Note: The full scale (FS) for H7CX 4-digit models is 9999.  
Batch Counter Operation  
The H7CX has a batch counter, separate from the 1-stage preset counter, for counting the number of times the count has been completed.  
The batch counter continues after count  
completion.  
Reset 1  
Batch output is held until batch counter  
Reset 2 (batch  
counter reset)  
reset is input.  
When the batch counter reset input is  
turned ON, the batch count value is reset,  
and batch output turns OFF.  
If the reset key is pressed while the batch  
count value is displayed, the batch count  
Set value  
Present value  
0
value is reset and batch output turns OFF.  
The present value is also reset at this time.  
OUT2  
Batch count set value  
Batch count value  
0
OUT1 (batch output)  
Note: The above is for when the output mode is C.  
Note: 1. The batch count value is held at 0 during batch counter reset input.  
2. If the batch count set value is 0, batch count will be performed but there will be no batch output.  
3. The batch count value returns to 0 when it reaches 999,999 (9,999 for 4-digit models).  
4. Once batch input has been turned ON, it will return to the ON state after power interruptions.  
5. If the batch count set value is changed from a value that is greater than the batch count value to one that is less, batch output will turn ON.  
6. After batch output turns ON, the ON state will be held even if the batch count set value is changed to a value greater than the batch count  
value.  
C-116  
Multifunction Preset Counter H7CX (Counter Function)  
Dual Counter Operation  
Using the dual counter allows the count from 2 inputs to be added or subtracted and the result displayed. It is possible to specify a set value for  
which output turns ON when the set value matches the added or subtracted result.  
OUT1 and OUT2 turn ON and OFF simultaneously.  
The operation after count com-  
Dual Count Calculating Mode = ADD  
Dual count value = CP1 PV + CP2 PV  
Dual Count Calculating Mode = SUB  
Dual count value = CP1 PV CP2 PV  
pletion for the dual counter  
value is determined by the out-  
put mode.  
Reset 1  
Reset 1  
The CP1 present value is reset  
when reset 1 input is turned  
ON and the CP2 present value  
is reset when reset 2 input is  
turned ON.  
If the reset key is pressed while  
the dual count value, CP1  
present value, or CP2 present  
value is displayed, all of the  
present values are reset and  
outputs turn OFF. At this time,  
counting is not possible for  
CP1 or CP2 inputs.  
(CP1 reset)  
(CP1 reset)  
Reset 2  
(CP2 reset)  
Reset 2  
(CP2 reset)  
Dual count value  
Dual count set value  
Dual count value  
Dual count set value  
0
0
CP1 present value  
CP1 present value  
CP2 present value  
0
0
0
CP2 present value  
0
OUT1, 2  
OUT1, 2  
Note: The above is for when the output mode is N.  
Note: The above is for when the output mode is  
K-2. SUB mode can be used only when  
K-2, D, L, or H is selected as the output  
mode with 6-digit models.  
Note: 1. Counting is not possible for CP1 during reset 1 input. CP2 will not be affected. The dual count value will be calculated based on a CP1  
present value of 0.  
2. Counting is not possible for CP2 during reset 2 input. CP1 will not be affected. The dual count value will be calculated based on a CP2  
present value of 0.  
3. The counting range for the dual count value is 99,999 to 999,999 (999 to 9,999 for 4-digit models). The counting ranges for the CP1  
present value and CP2 present value are 0 to 999,999 (0 to 9,999 for 4-digit models). If a present value exceeds 999,999 (9,999 for 4-  
digit models), FFFFFF (FFFF for 4-digit models) will be displayed to indicate an overflow, and all counting will stop.  
Reset Function List  
Function  
1-stage/2-stage  
counter  
Total and preset counter  
Batch counter  
Dual counter  
Screen dis-  
played in run  
mode  
Present value/ Present value/  
Total count  
value  
Present value/  
set value  
Batch count  
value/batch  
Dual count  
value/dual  
CP1 present  
value/CP2  
set value (1, 2)  
set value  
count set value count set value present value  
Reset/reset 1  
Present value  
and output reset.  
Present value and output reset.  
Present value and output reset.  
Only the CP1 present value is re-  
set.  
Total reset/re- No effect.  
set 2  
Only the total count value is reset. Batch count value and batch output Only the CP2 present value is re-  
reset.  
set.  
Reset key  
Present value  
Present value  
Present value,  
Present value  
Present value,  
CP1 present value, CP2 present  
and output reset. and output reset. total count value, and output reset. batch count val- value, dual count value, and output  
and output reset.  
ue, output and  
batch output re-  
set.  
reset.  
Multifunction Preset Counter H7CX (Counter Function)  
C-117  
I Operating Procedures (Tachometer Function)  
Switching from Counter to Tachometer  
Power ON  
Run mode  
The H7CX is factory-set to the 2-stage  
counter (1-stage counter for H7CX-AU@  
models) configuration. To switch to the  
tachometer configuration, use the  
procedure shown on the right. For details,  
refer to page 39.  
Configuration selection mode  
Hold down for  
1 s min. (See note.)  
+
MODE  
1
Switch to 2cnt to taco (tachometer operation) using the  
key.  
MODE  
1
key.  
Note: The  
key must be pressed before the  
Settings for Basic Operations  
Settings for basic functions can be performed with just the DIP switch.  
Be sure to set pin 1 to ON.  
1
2
3
4
5
6
7
8
ON  
OFF  
Note: All of the pins are factory-set to OFF.  
Item  
OFF  
ON  
Enabled  
Pin 3  
OFF  
Pin 4  
OFF  
Tachometer output mode  
Upper and lower limit  
Area  
1
DIP switch set- Disabled  
tings enable/  
disable  
ON  
OFF  
ON  
OFF  
ON  
Upper limit  
2
3
4
5
6
7
8
Counting speed 30 Hz  
10 kHz  
ON  
Lower limit  
Tachometer out- Refer to the table on the right.  
put mode  
Average pro-  
cessing  
Refer to the table on the right.  
Pin 5  
Pin 6  
Average processing  
OFF  
ON  
OFF  
OFF  
ON  
OFF (no average processing)  
---  
---  
---  
2 times  
4 times  
8 times  
NPN/PNP input NPN  
mode  
PNP  
OFF  
ON  
ON  
Easy Confirmation of Switch Settings Using Indicators  
The ON/OFF status of the DIP switch pins can be  
confirmed using the front display. For details, refer to page 124.  
Note: 1. Be sure to set pin 1 of the DIP switch to ON. If it is set to OFF, the DIP switch settings will not be enabled.  
2. Changes to DIP switch settings are enabled when the power is turned ON.  
Advanced-Function Settings  
After making DIP switch settings for basic operations, advanced-functions (see note) can be added using the operation keys.  
For details, refer to page 34.  
Note: Advanced functions consist of decimal point position, prescale value, auto-zero time, startup time, display color, output allo-  
cation, and key protect level.  
C-118  
Multifunction Preset Counter H7CX (Tachometer Function)  
Settings for Advanced Functions  
Note: When using as a tachometer, switch to the tachometer configuration using the procedure given on page 124.  
Settings that cannot be performed with the DIP switch are performed with the operation keys.  
Note: 1. If the mode is switched to the function setting mode during operation, operation will  
Power ON  
continue.tion, operation will continue.  
2. Changes made to settings in function setting mode are enabled for the first time when  
the mode is changed to run mode. Also, whensettings are changed, the counter is re-  
set (measured values initial-ized and output turned OFF) on returning to run mode.  
For details on operations in run mode, refer to page 37.  
(See note 1.)  
3s min.  
(See note 2.)  
3s min.  
The characters displayed in reverse video are the initial values.  
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).  
If pin 1 of the DIP switch is set to ON, the setting items indicated by  
will not be displayed.  
Set each setting item using the  
keys.  
Tachometer  
output  
mode  
(HI-LO)  
(AREA)  
(HI-HI)  
(LO-LO)  
Counting  
speed  
(30Hz)  
(10kHz)  
Decimal  
point  
position  
(No decimal  
point)  
(One digit  
after decimal  
point)  
(Two digits  
after decimal  
point)  
(Three digits  
after decimal  
point)  
Prescale  
value  
(0.001)  
(1.000)  
(99.999)  
Average  
processing  
(No aver-  
age pro-  
cessing)  
(Average  
of 2 meas-  
urements)  
(Average  
of 4 meas-  
urements)  
(Average  
of 8 meas-  
urements)  
Auto-zero  
time  
(0.1s)  
(0.0s)  
(99.9s)  
Startup  
time  
(99.9s)  
NPN/PNP  
input mode  
(NPN  
input)  
(PNP  
input)  
Display  
color  
(Red)  
(Green) (Red-green) (Green-red)  
Output  
allocation  
Note: Displayed for H7CX-AU@ models  
Key protect  
level  
(KP-1)  
(KP-2)  
(KP-3)  
(KP-4)  
(KP-5)  
Multifunction Preset Counter H7CX (Tachometer Function)  
C-119  
Explanation of Functions  
Tachometer Output Mode (totm) (Setting possible using  
Auto-zero Time (aut=)  
DIP switch.)  
It is possible to set the H7CX so that if there is no pulse for a certain  
time the display is force-set to 0. This time is called the auto-zero  
time. Set the auto-zero time to a time slightly longer than the esti-  
mated interval between input pulses and within the setting range (0.1  
to 99.9 s). It will not be possible to make accurate measurements if  
the auto-zero time is set to a time shorter than the input pulse cycle.  
Setting a time that is too long may also result in problems, such as a  
time-lag between rotation stopping and the alarm turning ON.  
Set the output method for control output based on the OUT1/OUT2  
set value. Upper and lower limit (HI-LO), area (AREA), upper limit  
(HI-HI), and lower limit (LO-LO) can be set. (For details on the opera-  
tion of the output modes, refer to Output Mode Settings on  
page 123.)  
Counting Speed (cnts) (Setting possible using DIP  
switch.)  
Startup Time (stmr)  
Set the maximum counting speed (30 Hz/10 kHz) for CP1 input. If  
contacts are used for input signals, set the counting speed to 30 Hz.  
Processing to eliminate chattering is performed for this setting.  
In order to prevent undesired output resulting from unstable input  
immediately after the power supply is turned ON, it is possible to pro-  
hibit measurement for a set time (0.0 to 99.9 s), the startup time. It  
can also be used to stop measurement and disable output until the  
rotating body reaches the normal rate of rotation, after the power  
supply to the H7CX and rotating body are turned ON at the same  
time.  
Decimal Point Position (dp)  
Decide the decimal point position for the measurement value, OUT1  
set value, and OUT2 set value.  
Prescale Value (pscl)  
Display  
Startup time  
It is possible to display the rate of rotation or the speed of a device or  
machine to which the H7CX is mounted by converting input pulses to  
a desired unit. If this prescaling function is not used, the input fre-  
quency (Hz) will be displayed.  
Comparison  
value  
(lower limit)  
The relationship between display and input is determined by the fol-  
lowing equation. Set the prescale value according to the unit to be  
displayed.  
Time  
Power supply  
Displayed value = f × a  
f: Input pulse frequency (number of pulses in 1 second)  
a: Prescale value  
Output  
(lower limit)  
1. Displaying Rotation Rate  
NPN/PNP Input Mode (imod)  
Display unit  
Prescale value (a)  
1/N × 60  
1/N  
Select either NPN input (no-voltage input) or PNP input (voltage  
input) as the input format. The same setting is used for all external  
inputs. For details on input connections, refer to The circuit shown  
above is for no-voltage input (NPN input). on page 96.  
rpm  
rps  
N: Number of pulses per revolution  
Display Color (colr)  
Example:In order to display the rate of rotation for a machine that  
Set the color used for the measurement value.  
outputs 5 pulses per revolution in the form @@.@ rpm:  
Setting  
Control output OFF  
Red (fixed)  
Green (fixed)  
Measured value displayed Measured value displayed  
Control output ON  
1. Set the decimal point position to 1 decimal place.  
red  
2. Using the formula, set the prescale value to 1/N × 60 =  
60/5 = 12.  
grn  
r-g  
(See note  
1.)  
2. Displaying Speed  
in red when both control  
outputs 1 and 2 are OFF.  
in green when either control  
output 1 or control output 2  
is ON.  
Display unit  
Prescale value (a)  
πd × 1/N × 60  
πd × 1/N  
m/min  
m/s  
Measured value displayed Measured value displayed  
in green when both control in red when either control  
g-r  
(See note  
2.)  
N: Number of pulses per revolution  
d: Diameter of rotating body (m)  
πd: Circumference (m)  
outputs 1 and 2 are OFF.  
output 1 or control output 2  
is ON.  
Note: 1. If the tachometer output mode is set to AREA, however, the  
measured value is displayed in red when control output 1 is  
OFF and in green when control output 1 is ON.  
d:Diameter of  
rotating body  
2. If the tachometer output mode is set to AREA, however, the  
measured value is displayed in green when control output 1  
is OFF and in red when control output 1 is ON.  
Average Processing (aug) (Setting possible using DIP  
switch.)  
Flickering display and output chattering can be prevented using aver-  
age processing (simple averaging). Average processing can be set to  
one of four levels: no average processing, 2 times (i.e., the average  
of 2 measurement values), 4 times, or 8 times. The measurement  
cycle will be equal to the sampling cycle (200 ms) multiplied by the  
average processing setting (i.e., the number of times). Average pro-  
cessing enables fluctuating input signals to be displayed stably. Set  
the optimum number of times for the application.  
C-120  
Multifunction Preset Counter H7CX (Tachometer Function)  
Output Allocation (otst)  
When using H7CX-AU@ models as 2-stage counter, each output can  
be flexibly allocated to either stage 1 or 2.  
Transistor output placed for SV1 and contact output for SV2 or vice  
verse, as in the following table.  
H7CX-AU/-AUD1  
OUT1  
OUT2  
Transistor (12-13)  
Contact (3, 4, 5)  
off  
on  
Contact (3, 4, 5)  
Transistor (12-13)  
H7CX-AUSD1  
OUT1  
OUT2  
Transistor (12-13)  
Transistor with diode  
(3, 4, 5)  
off  
on  
Transistor with diode  
(3, 4, 5)  
Transistor (12-13)  
Key Protect Level (kypt)  
Set the key protect level.  
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the  
key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the key-  
protect switch after the H7CX is mounted to the panel.  
OFF ON  
(See note)  
Note: Factory-set to OFF  
Key protect indicator  
Level  
Meaning  
Details  
Yes  
No  
Changing mode  
(See note.)  
Switching display  
during operation  
Reset key  
Up/down key (Up key for  
6-digit models)  
KP-1 (default setting)  
No  
Yes  
Yes  
Yes  
No  
No  
No  
KP-2  
KP-3  
KP-4  
KP-5  
No  
No  
No  
No  
Yes  
Yes  
Yes  
No  
Yes  
No  
No  
Note: Changing mode to configuration selection mode ( MODE  
+
1 s min.) or function setting mode ( MODE 3 s min.).  
1
Multifunction Preset Counter H7CX (Tachometer Function)  
C-121  
Operation in Run Mode  
Set values for each digit as required using the  
key.  
Measurement Value  
Displays the currently measured value.  
Measurement value  
OUT1/OUT2 Set Value  
Set OUT1 set value and OUT2 set value. The  
measurement value is compared to OUT1 set value  
and OUT2 set value and output is made according to  
the selected output mode.  
Measurement value  
OUT1 set value  
Measurement value  
OUT2 set value  
C-122  
Multifunction Preset Counter H7CX (Tachometer Function)  
Output Mode Settings  
Output  
mode  
setting  
Upper  
and  
(Upper-limit) OUT2 set value  
Measurement value  
lower  
limit  
(HI-LO)  
(Lower-limit) OUT1 set value  
OUT1  
OUT2  
ON condition for OUT1: measurement value OUT1 set value  
ON condition for OUT2: measurement value OUT2 set value  
Area  
(AREA)  
OUT2 set value  
Measurement value  
OUT1 set value  
OUT1  
OUT2  
Condition  
OUT1 set value OUT2 set value  
OUT1 set value > OUT2 set value  
ON  
condition  
for OUT1  
OUT1 set value measurement value OUT2 set OUT2 set value measurement value OUT1 set  
value  
value  
ON  
condition  
for OUT2  
measurement value < OUT1 set value  
or  
measurement value > OUT2 set value  
measurement value < OUT2 set value  
or  
measurement value > OUT1 set value  
Upper  
limit  
(HI-HI)  
(Upper-limit) OUT2 set value  
Measurement value  
(Upper-limit) OUT1 set value  
OUT1  
OUT2  
ON condition for OUT1: Measurement value OUT1 set value  
ON condition for OUT2: Measurement value OUT2 set value  
Lower  
limit  
(LO-LO)  
(Lower-limit) OUT2 set value  
Measurement value  
(Lower-limit) OUT1 set value  
OUT1  
OUT2  
ON condition for OUT1: Measurement value OUT1 set value  
ON condition for OUT2: Measurement value OUT2 set value  
Multifunction Preset Counter H7CX (Tachometer Function)  
C-123  
I Operation in Configuration Selection Mode  
Select which H7CX configuration is used (i.e., 1-stage counter, 2-stage counter, total and preset counter, batch counter, dual counter, or tachom-  
eter) in configuration selection mode. The H7CX is also equipped with a DIP switch monitor function, a convenient function that enables the settings  
of the DIP switch pins to be confirmed using the front display.  
Counting stopped  
Counting possible  
Power ON  
1
1
To change the mode to configuration selection mode, press  
1
the  
Key for 1 s min. with the  
key held down. The  
mode will not change if the  
1
key is pressed first.  
+
1
(See note 2.)  
(See note 1.)  
Select the configuration using the  
digit models)  
keys. (  
key only for 6-  
1 s min.  
The H7CX is factory-set to the 1-stage counter configuration (2-stage  
counter configuration with H7CX-AW@/-A4W@ models).  
Configuration  
selection  
(1-stage counter) (2-stage counter) (Total and  
preset counter)  
(Batch counter) (Dual counter)  
(Tachometer)  
The configuration that can be selected depend on the model.  
The status of the DIP switch pins (1 to 8) can be confirmed using the  
keys.  
DIP switch  
monitor  
Note: This display is possible only if DIP switch pin 1 (DIP switch set-  
tings) is set to ON (i.e., enabled).  
Example  
1
2
3
4
5
6
7
8
ON  
OFF  
Indicates that DIP switch pin 8 is ON.  
Indicates that DIP switch pin 7 is OFF.  
Indicates that DIP switch pin 6 is ON.  
Indicates that DIP switch pin 5 is OFF.  
Indicates that DIP switch pin 4 is ON.  
Indicates that DIP switch pin 3 is OFF.  
Indicates that DIP switch pin 2 is ON.  
Indicates that DIP switch pin 1 is ON.  
Note: 1. When the mode is changed to configuration selection mode, the present value is reset, outputs turns OFF, and counting (measuring)  
stops.  
2. Setting changes made in configuration selection mode are enabled when the mode is changed to run mode. If the configuration is  
changed, the set value (or set value 1 and set value 2), OUT1 set value or OUT2 set value are initialized.  
C-124  
Multifunction Preset Counter H7CX  
Additional Information  
I Using the Operation Keys  
Counter Operation  
Counting stopped  
Counting possible  
Power ON  
Run mode  
1
+
1 s min.  
3 s min.  
3 s min.  
Configuration selection mode  
Function setting mode  
1
+
1-stage counter  
1 s min.  
Configuration selection  
DIP switch monitor  
Input mode  
Present value, set value  
Dual count calculating mode  
Output mode  
2-stage counter  
Present value, set value 1  
Present value, set value 2  
One-shot output time  
One-shot output 2 time  
One-shot output 1 time  
Counting speed  
Total and preset counter  
Present value, set value  
Total count value  
Reset input signal width  
Decimal point position  
Prescale value  
Batch counter  
Present value, set value  
NPN/PNP input mode  
Display color  
Batch count value,  
batch count set value  
Output allocation  
Key protect level  
Dual counter  
Dual count value,  
dual count set value  
CP1 present value,  
CP2 present value  
Note: 1. Perform settings using the  
and  
keys (  
key only with 6-digit models).  
2. The above flowcharts outline the procedures for all models. For more details on each model, refer to page 107.  
Multifunction Preset Counter H7CX  
C-125  
Tachometer Operation  
Counting stopped  
Counting possible  
Power ON  
1
+
1 s min.  
3 s min.  
3 s min.  
Configuration selection mode  
Run mode  
Function setting mode  
1
+
1 s min.  
Measurement value  
Configuration selection  
DIP switch monitor  
Tachometer output mode  
Measurement value,  
OUT1 set value  
Counting speed  
Decimal point position  
Prescale value  
Measurement value,  
OUT2 set value  
Average processing  
Auto-zero time  
Startup time  
NPN/PNP input mode  
Display color  
Output allocation  
Key protect level  
Note: 1. All setting changes are performed using the  
2. For details, refer to page 118.  
key.  
C-126  
Multifunction Preset Counter H7CX  
I Lists of Settings  
Fill in your set values in the set value column of the following tables and utilize the tables for quick reference.  
Configuration Selection Mode  
Parameter  
name  
Parameter  
func  
dip  
Setting range  
1cnt/2cnt/tcnt/bcnt/dcnt/taco(See note 1.)  
on/off  
Default value  
1cnt  
Unit  
Set value  
Configuration  
selection  
---  
---  
(See note 2.)  
DIP switch  
monitor  
off  
---  
Note: 1. The setting range varies with the model.  
2. The default value for H7CX-AW@/-A4W@ models is 2cnt.  
Settings for Counter Operation  
Run Mode  
1-stage Counter  
Parameter name  
Parameter  
Setting range  
Default value  
Unit  
Set value  
Present value, Present value ---  
set value  
-99999to 999999(-999to 9999)  
0to 999999(0to 9999) (For conditions other  
than those described in note 1.)  
0
--  
---  
Set value  
---  
0
---  
-99999to 999999(-999to 9999)  
(See note 1.)  
2-stage Counter  
Parameter name  
Parameter  
Setting range  
Default value  
Unit  
Set value  
Present value, Present value ---  
set value 1  
-99999to 999999(-999to 9999)  
0to 999999(0to 9999) (For conditions other  
than those described in note 1.)  
0
0
---  
---  
---  
Set value 1  
---  
-99999to 999999(-999to 9999)  
(See note 1.)  
0
Present value, Present value ---  
set value 2  
-99999to 999999(-999to 9999)  
0to 999999(0to 9999) (For conditions other  
than those described in note 1.)  
0
0
---  
---  
---  
Set value 2  
---  
-99999to 999999(-999to 9999)  
(See note 1.)  
0
Total and Preset Counter  
Parameter name  
Parameter  
Setting range  
Default value  
Unit  
Set value  
Present value, Present value ---  
set value  
-99999to 999999(-999to 9999)  
0to 999999(0to 9999) (For conditions other  
than those described in note 1.)  
0
0
---  
---  
---  
Set value  
---  
-99999to 999999(-999to 9999)  
(See note 1.)  
Total count value  
---  
-99999to 999999(-999to 9999)  
0
---  
---  
---  
Batch Counter  
Parameter name  
Parameter  
Setting range  
Default value  
Unit  
Set value  
Present value, Present value  
set value  
---  
---  
-99999to 999999(-999to 9999)  
0to 999999(0to 9999) (For conditions other  
than those described in note 1.)  
0
0
---  
---  
Set value  
-99999to 999999(-999to 9999)  
(See note 1.)  
Batch count  
value, batch  
count set value  
Batch count  
value  
---  
---  
0to 999999(0to 9999)  
0
0
---  
---  
---  
Batch count  
set value  
0to 999999(0to 9999)  
Multifunction Preset Counter H7CX  
C-127  
Dual Counter  
Parameter name  
Parameter  
Dual count value ---  
Setting range  
Default value  
Unit  
Set value  
Dual count  
-99999to 999999(-999to 9999)  
0to 999999(0to 9999) (For conditions other 0  
than those described in note 2.)  
0
---  
---  
---  
value, dualcount  
set value  
Dual count set  
value  
---  
-99999to 999999(-999to 9999)  
(See note 2.)  
CP1 present  
value, CP2  
present value  
CP1 present  
value  
---  
---  
0to 999999(0to 9999)  
0to 999999(0to 9999)  
0
0
---  
---  
---  
---  
CP2 present  
value  
Note: 1. The input mode is increment/decrement mode and the output mode is K-2, D, L, or H.  
2. The dual count calculating mode is subtraction mode and the output mode is K-2, D, L, or H.  
Function Setting Mode  
Parameter name  
Input mode  
Parameter  
cntm  
Setting range  
up/down/ud-a/ud-b/ud-c(See note 1.)  
add/sub(See note 1.)  
Default value  
Unit  
Set value  
up  
---  
---  
Dual count calculating  
mode  
caln  
add  
Output mode  
outm  
otim  
otm2  
otm1  
cnts  
iflt  
dp  
n/f/c/r/k-1/p/q/a/k-2/d/l/h(See note 2.)  
0.01to 99.99  
n
---  
s
One-shot output time  
One-shot output 2 time  
One-shot output 1 time  
Counting speed  
0.50  
0.50  
hold  
30h=  
20ms  
0.01to 99.99  
s
hold/0.01 to 99.99(See note 3.)  
30h=/skh=  
s
---  
---  
Reset input signal width  
Decimal point position  
20ms/1ms  
------/-----.-/----.--/---.---  
(----/---.-/--.--/-.---)  
------  
(----)  
Prescale value  
pscl  
imod  
colr  
otst  
kypt  
0.001to 99.999 (0.001 to 9.999)  
npn/pnp  
1.000  
npn  
---  
---  
---  
---  
---  
NPN/PNP input mode  
Display color  
red/grn/r-g/g-r  
off/on  
red  
Output allocation  
Key protect level  
off  
kp-1/kp-2/kp-3/kp-4/kp-5  
kp-1  
Note: 1. The setting range varies with the output mode.  
2. The setting range varies with the model and the input mode.  
3. HOLD cannot be set when the output mode is K-2.  
C-128  
Multifunction Preset Counter H7CX  
Settings for Tachometer Operation  
Run Mode  
Parameter name  
Measurement value  
Parameter  
Setting range  
0to 999999  
Default value  
Unit  
Set value  
---  
---  
0
0
---  
---  
---  
---  
Measurement  
value, OUT1 set  
value  
Measurement  
value  
0to 999999  
OUT1 set value  
---  
---  
0to 999999  
0to 999999  
0
0
---  
---  
Measurement  
value, OUT2 set  
value  
Measurement  
value  
---  
OUT2 set value  
---  
0to 999999  
0
---  
Function Setting Mode  
Parameter name  
Parameter  
Setting range  
Default value  
hilo  
Unit  
Set value  
Tachometer output  
mode  
totm  
hold/area/hihi/lolo  
---  
Counting speed  
cnts  
30h=/10kh=  
30h=  
------  
1.000  
off  
---  
---  
---  
---  
---  
s
Decimal point position dp  
------/-----.-/----.--/---.---  
0.001to 99.999  
off/2/4/8  
Prescale value  
Average processing  
Auto-zero time  
Startup time  
pscl  
aUg  
aut=  
stmr  
0.1to 99.9  
99.9  
0.0  
0.0to 99.9  
NPN/PNP input mode imod  
npn/pnp  
npn  
s
Display color  
colr  
otst  
kypt  
red/grn/r-g/g-r  
off/on  
red  
---  
---  
---  
Output allocation  
Key protect level  
off  
kp-1/kp-2/kp-3/kp-4/kp-5  
kp-1  
Multifunction Preset Counter H7CX  
C-129  

H7CX-AUDG 相关器件

型号 制造商 描述 价格 文档
H7CX-AUG OMRON Multifunction Preset Counter 获取价格
H7CX-AUS OMRON Multifunction Preset Counter 获取价格
H7CX-AUSD OMRON Multifunction Preset Counter 获取价格
H7CX-AUSD1 OMRON Multifunction Preset Counter 获取价格
H7CX-AUSD1-N OMRON Multifunction Counter/Tachometer 获取价格
H7CX-AUSD1G OMRON Multifunction Preset Counter 获取价格
H7CX-AUSDG OMRON Multifunction Preset Counter 获取价格
H7CX-AUSG OMRON Multifunction Preset Counter 获取价格
H7CX-AW OMRON Multifunction Preset Counter 获取价格
H7CX-AW-N OMRON Multifunction Counter/Tachometer 获取价格

H7CX-AUDG 相关文章

  • Bourns 密封通孔金属陶瓷微调电位计产品选型手册(英文版)
    2024-09-20
    6
  • Bourns 精密环境传感器产品选型手册(英文版)
    2024-09-20
    9
  • Bourns POWrTher 负温度系数(NTC)热敏电阻手册 (英文版)
    2024-09-20
    8
  • Bourns GMOV 混合过压保护组件产品选型手册(英文版)
    2024-09-20
    6