S8AS-48008N [OMRON]

Smart Power Supply; 智能电源
S8AS-48008N
型号: S8AS-48008N
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Smart Power Supply
智能电源

文件: 总26页 (文件大小:2300K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Smart Power Supply  
S8AS  
CSM_S8AS_DS_E_4_1  
A New Type of Power Supply That  
Provides Safety and Maintainability  
• 240- and 480-W power supplies with and digital circuit  
protectors in a single package.  
• Each branch output tripping current value can be easily  
set at 0.1-A increments.  
• Startup and shutdown sequence control included.  
• Various monitor displays and alarms (output voltage,  
output current, maintenance forecast monitor,  
temperature).  
• Conforms to UL Class 2  
• Mounts to DIN Rail.  
Refer to Safety Precautions for All Power Supplies and Safety  
Precautions on page 23.  
Model Number Structure  
Model Number Legend  
S8AS-@@@@@@  
1
2
3
1. Capacity  
3. Additional Functions  
Blank: Changeable parameter settings with no communications  
240: 240 W  
480: 480 W  
N:  
R:  
Unchangeable parameter settings with no communications  
Changeable parameter settings with communications (RS-485)  
2. Number of Output Branches  
06: 6 branch outputs  
08: 8 branch outputs  
Ordering Information  
S8AS  
Maximumcutoff  
output current  
(per branch)  
Total  
Number  
Output  
Capacity Input voltage  
voltage  
Communications  
functions  
Parameter  
settings  
output  
of output  
Model  
current branches  
None  
Changeable  
S8AS-24006  
6 branch  
outputs  
240 W  
10 A  
None  
Not changeable S8AS-24006N  
RS-485  
None  
Changeable  
Changeable  
S8AS-24006R  
S8AS-48008  
100 to  
24 V  
3.8 A  
240 VAC  
8 branch  
outputs  
480 W  
20 A  
None  
Not changeable S8AS-48008N  
Changeable S8AS-48008R  
RS-485  
Be sure to read and fully understand the content of the S8AS User's Manual (Cat. No. Z269) before changing settings on the S8AS.  
1
S8AS  
Specifications  
S8AS-24006@  
Item  
Model  
S8AS-24006  
S8AS-24006N  
S8AS-24006R  
Efficiency (Typ.)  
Voltage range *1  
Frequency *1  
80% min.  
100 to 240 VAC (85 to 264 VAC)  
50/60 Hz (47 to 63 Hz)  
100-V input  
Current  
3.8 A max.  
200-V input  
2.0 A max.  
Input  
condi-  
tions  
Power factor  
0.95 min.  
Harmonic current  
EN61000-3-2  
100-V input  
0.5 mA max.  
Leakage  
current  
200-V input  
100-V input  
200-V input  
1.0 mA max.  
25 A max. (for a cold start at 25°C)  
Inrush current  
*2  
50 A max. (for a cold start at 25°C)  
Number of branches  
6
Maximum cutoff output current (per branch)  
Total output current  
3.8 A  
10 A  
Allowable voltage range *3  
Ripple noise voltage  
10% (with V.ADJ)  
2.0% [P-P] max. (for rated input and output voltage) *4  
10 mA max.  
Output  
condi- Output leakage current  
tions  
Input fluctuation  
0.5% max. (Input: 85 to 264 VAC, 100% load) *5  
4.0% max. (rated input, 0% to 100% load) *5  
0.05%/°C max.  
Load fluctuation (rated input voltage)  
Temperature fluctuation  
Startup time *2  
3,000 ms max. (for rated input and output voltage) *4  
20 ms max. (for rated input and output voltage) *4  
28.8 V (Cannot be changed.)  
Output hold time *2  
Abnormal voltage tripping  
Setting range: 0.5 to 3.8 A  
(in 0.1-A increments)  
Setting range: 0.5 to 3.8 A  
(in 0.1-A increments)  
Abnormal current tripping *2  
3.8 A (Cannot be changed.)  
Tripping  
functions  
Abnormal total current tripping  
Tripping alarm output  
Branch outputs are cut off when the total output current is more than 17 A for 2 s, 15 A for 5 s, 13 A for 10 s, or 12 A for 20 s.  
Photoswitch output  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Setting range: 18.0 to 26.4 V  
(in 0.1-V increments)  
Setting range: 18.0 to 26.4 V  
(in 0.1-V increments)  
Undervoltage detection  
20.0 V (Cannot be changed.)  
Undervoltage  
detection  
functions  
Photoswitch output  
Undervoltage detection output  
Maintenance forecast monitor  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Setting range: 0.0 to 5.0 yr  
(in 0.5-yr increments)  
Setting range: 0.0 to 5.0 yr  
(in 0.5-yr increments)  
Maintenance  
forecast  
0.5 yr (Cannot be changed.)  
monitor  
function  
Maintenance forecast monitor  
output  
Photoswitch output  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Setting range: 25 to 90°C  
(in 1°C increments)  
Setting range: 25 to 90°C  
(in 1°C increments)  
Over-  
Over-temperature  
90°C (Cannot be changed.)  
temperature  
detection  
function  
Photoswitch output  
Over-temperature output  
Output voltage display  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Display range:17.0 to 30.0 V  
Display accuracy: 2% rdg 1 digit max.  
Branch output display range: 0.0 to 4.0 A  
Peak output current display range: 0.0 to 20.0 A  
Total current display range: 0.0 to 40.0 A  
Display accuracy: 5% FS (4 A) 1 digit max.  
Output current display  
Display  
functions  
Func-  
tions  
Maintenance forecast monitor  
display  
Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr  
Display range: 20 to 100°C  
Display accuracy: 2°C 1 digit max.  
Temperature display  
The input can be enabled or disabled for All branch outputs: Enabled  
The input can be enabled or disabled for  
each branch output.  
(Cannot be changed.)  
each branch output.  
19.2 to 30.0 VDC, minimum signal  
width: 10 ms, tripping after input within width: 10 ms, tripping after input within width: 10 ms, tripping after input within  
19.2 to 30.0 VDC, minimum signal  
19.2 to 30.0 VDC, minimum signal  
External Tripping Input  
20 ms + the shutdown sequence set  
time  
20 ms + the shutdown sequence set  
time  
20 ms + the shutdown sequence set  
time  
Branch output 1: 0.0 s  
(Cannot be changed.)  
Branch output 2: 0.4 s  
(Cannot be changed.)  
Branch output 3: 0.8 s  
(Cannot be changed.)  
Branch output 4: 1.2 s  
(Cannot be changed.)  
Branch output 5: 1.6 s  
(Cannot be changed.)  
Branch output 6: 2.0 s  
(Cannot be changed.)  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
Startup sequence  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
All branch outputs: 0.0 s  
(Cannot be changed.)  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
Shutdown sequence  
Communications  
Sampling period  
Parallel connection  
Series connection  
Not supported  
1 ms  
Supported (RS-485)  
Not supported  
Not supported  
Note: Refer to the next page for information on *1 to *5.  
2
S8AS  
Item  
Model  
S8AS-24006  
S8AS-24006N  
S8AS-24006R  
Ambient operating temperature  
Storage temperature  
Refer to the derating curve (no icing or condensation). *2  
25 to 65°C  
Ambient operating humidity  
25% to 85% (storage: 25% to 90%)  
3.0 kVAC for 1 min between all input terminals collectively and all branch output, all I/O signal, and all communications  
terminals collectively (Detection current: 20 mA)  
2.0 kVAC for 1 min between all inputs and protective earth (Detection current: 20 mA)  
1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal, and all communications terminals  
collectively (Detection current: 20 mA)  
Withstand voltage  
500 VAC for 1 min between all branch output and all I/O signal/communications terminals collectively  
(Detection current: 20 mA)  
500 VAC for 1 min between all I/O signal terminals collectively and communications terminals collectively  
(Detection current: 20 mA)  
500 VAC for 1 min between all I/O signal terminals collectively and all output signal terminals collectively  
(detection current: 20 mA)  
Others  
100 MΩ min. at 500 VDC between the protective earth terminal or all input terminals collectively and all branch output,  
all I/O signal, and all communications terminals collectively  
Insulation resistance  
Vibration resistance  
Shock resistance  
Output indicator  
Conducted EMI  
Radiated EMI  
No abnormality after 10 to 55 Hz at 0.375-mm single amplitude for 2 h each in 3 directions.  
No abnormality after 150 m/s2 3 times each in 6 directions.  
Provided (Color: green)  
Conforms to EN 61204-3 Class A and FCC Class A.  
Conforms to EN 61204-3 Class A.  
cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per CSA C22.2 No.22.3)  
cURus: UL60950-1, CSA C22.2 No.60950-1  
EN: EN50178, EN60950-1  
Safety standards  
Weight  
VDE: VDE0160, VDE0805 Teil1  
1,600 g max.  
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal  
temperature of the Power Supply may result in ignition or burning.  
*2. Refer to Engineering Data on page 8 for details.  
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 10% of the voltage adjustment range. When adjusting  
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. If the output voltage  
exceeds 28.8 V, all branch outputs will be cut off.  
*4. Rated input and output conditions: Rated input voltage, rated frequency, rated output voltage, rated total output current, and maximum cutoff  
output current.  
*5. 100% load conditions: Rated output voltage, rated total output current, and maximum cutoff output current.  
3
S8AS  
S8AS-48008@  
Item  
Model  
S8AS-48008  
S8AS-48008N  
S8AS-48008R  
Efficiency (Typ.)  
80% min.  
Voltage range *1  
100 to 240 VAC (85 to 264 VAC)  
Frequency *1  
50/60 Hz (47 to 63 Hz)  
100-V input  
200-V input  
7.4 A max.  
Current  
3.9 A max.  
Input  
condi-  
tions  
Power factor  
0.95 min.  
Harmonic current  
EN61000-3-2  
100-V input  
0.5 mA max.  
Leakage  
current  
200-V input  
100-V input  
200-V input  
1.0 mA max.  
25 A max. (for a cold start at 25°C)  
50 A max. (for a cold start at 25°C)  
8
Inrush current  
*2  
Number of branches  
Maximum cutoff output current (per branch)  
Total output current  
3.8 A  
20 A  
Allowable voltage range *3  
Ripple noise voltage  
10% (with V.ADJ)  
2.0%[P-P] max. (for rated input and output voltage) *4  
10 mA max.  
Output  
condi- Output leakage current  
tions  
Input fluctuation  
0.5% max. (Input: 85 to 264 VAC, 100% load) *5  
4.0% max. (rated input, 0% to 100% load) *5  
0.05%/°C max.  
Load fluctuation (rated input voltage)  
Temperature fluctuation  
Startup time *2  
3,000 ms max. (for rated input and output voltage) *4  
20 ms min. (for rated input and output voltage) *4  
28.8 V (Cannot be changed.)  
Setting range: 0.5 to 3.8 A  
Output hold time *2  
Abnormal voltage tripping  
Setting range: 0.5 to 3.8 A  
(in 0.1-A increments)  
Abnormal current tripping *2  
3.8 A (Cannot be changed.)  
(in 0.1-A increments)  
Tripping  
functions  
Abnormal total current tripping  
Tripping alarm output  
Branch outputs are cut off when the total output current is more than 27 A for 1 s, 25 A for 2 s, or 22.5 A for 5 s.  
Photoswitch output  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Setting range: 18.0 to 26.4 V  
(in 0.1-V increments)  
Setting range: 18.0 to 26.4 V  
(in 0.1-V increments)  
Undervoltage detection  
20.0 V (Cannot be changed.)  
Undervoltage  
detection  
functions  
Photoswitch output  
Undervoltage detection output  
Maintenance forecast monitor  
Maintenance forecast monitor output  
Over-temperature  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Setting range: 0.0 to 5.0 yr  
(in 0.5-yr increments)  
Setting range: 0.0 to 5.0 yr  
(in 0.5-yr increments)  
Maintenance  
forecast  
monitor  
0.5 yr (Cannot be changed.)  
Photoswitch output  
function  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Setting range: 25 to 90°C  
(in 1°C increments)  
Setting range: 25 to 90°C  
(in 1°C increments)  
Over-  
90°C (Cannot be changed.)  
temperature  
detection  
function  
Photoswitch output  
Over-temperature output  
Output voltage display  
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max.  
Display range:17.0 to 30.0 V  
Display accuracy: 2% rdg 1 digit max.  
Branch output display range: 0.0 to 4.0 A  
Peak output current display range: 0.0 to 20.0 A  
Total current display range: 0.0 to 40.0 A  
Display accuracy: 5% FS (4 A) 1 digit max.  
Output current display  
Display  
functions  
Maintenance forecast monitor display Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr  
Func-  
tions  
Display range: 20 to 100°C  
Temperature display  
Display accuracy: 2°C 1 digit max.  
The input can be enabled or disabled  
for each branch output.  
All branch outputs: Enabled  
(Cannot be changed.)  
The input can be enabled or disabled  
for each branch output.  
External Tripping Input  
19.2 to 30 VDC, minimum signal width: 19.2 to 30 VDC, minimum signal width: 19.2 to 30 VDC, minimum signal width:  
10 ms, tripping after input within 20 ms 10 ms, tripping after input within 20 ms 10 ms, tripping after input within 20 ms  
+ the shutdown sequence set time  
+ the shutdown sequence set time  
+ the shutdown sequence set time  
Branch output 1: 0.0 s  
(Cannot be changed.)  
Branch output 2: 0.4 s  
(Cannot be changed.)  
Branch output 3: 0.8 s  
(Cannot be changed.)  
Branch output 4: 1.2 s  
(Cannot be changed.)  
Branch output 5: 1.6 s  
(Cannot be changed.)  
Branch output 6: 2.0 s  
(Cannot be changed.)  
Branch output 7: 2.4 s  
(Cannot be changed.)  
Branch output 8: 2.8 s  
(Cannot be changed.)  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
Startup sequence  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
All branch outputs: 0.0 s  
(Cannot be changed.)  
Setting range: 0.0 to 99.9 s in 0.1-s  
increments  
Shutdown sequence  
Communications  
Sampling period  
Parallel connection  
Series connection  
Not supported  
1 ms  
Supported (RS-485)  
Not supported  
Not supported  
Note: Refer to the next page for information on *1 to *5.  
4
S8AS  
Item  
Model  
S8AS-48008  
S8AS-48008N  
S8AS-48008R  
Ambient operating temperature  
Storage temperature  
Refer to the derating curve (no icing or condensation). *2  
25 to 65°C  
Ambient operating humidity  
25% to 85% (storage: 25% to 90%)  
3.0 kVAC for 1 min between all input terminals collectively and all branch output, all I/O signal, and all communications  
terminals collectively (Detection current: 20 mA)  
2.0 kVAC for 1 min between all inputs and protective earth (Detection current: 20 mA)  
1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal, and all communications terminals  
collectively (Detection current: 30 mA)  
Withstand voltage  
500 VAC for 1 min between all branch output and all I/O signal/communications terminals collectively  
(Detection current: 20 mA)  
500 VAC for 1 min between all I/O signal terminals collectively and communications terminals collectively  
(Detection current: 20 mA)  
500 VAC for 1 min between all I/O signal terminals collectively and all output signal terminals collectively  
(detection current: 20 mA)  
Others  
100 MΩ min. at 500 VDC between the protective earth terminal or all input terminals collectively and all branch output, all I/  
O signal, and all communications terminals collectively  
Insulation resistance  
Vibration resistance  
Shock resistance  
Output indicator  
Conducted EMI  
Radiated EMI  
No abnormality after 10 to 55 Hz at 0.375-mm single amplitude for 2 h each in 3 directions.  
No abnormality after 150 m/s2 3 times each in 6 directions.  
Provided (Color: green)  
Conforms to EN 61204-3 Class A and FCC Class A.  
Conforms to EN 61204-3 Class A.  
cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per CSA C22.2 No.22.3)  
cURus: UL60950-1, CSA C22.2 No.60950-1  
EN: EN50178, EN60950-1  
Safety standards (pending)  
Weight  
VDE: VDE0160, VDE0805 Teil1  
2,400 g max.  
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal  
temperature of the Power Supply may result in ignition or burning.  
*2. Refer to Engineering Data on page 8 for details.  
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 10% of the voltage adjustment range. When adjusting  
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. If the output voltage  
exceeds 28.8 V, all branch outputs will be cut off.  
*4. Rated input and output conditions: Rated input voltage, rated frequency, rated output voltage, rated total output current, and maximum cutoff  
output current.  
*5. 100% load conditions: Rated output voltage, rated total output current, and maximum cutoff output current.  
5
S8AS  
Connections  
Block Diagrams  
S8AS-24006@  
(S8AS-24006R only)  
RS-485  
A ()  
B (+)  
Communications  
circuit  
TRP  
LOW  
Voltage Temperature  
detection detection  
Display  
circuit  
Switches  
LFE  
Processing circuit  
(main processing)  
TMP  
COM  
Communications between  
processing circuits (RS-232C)  
TRG+  
TRG−  
Branch output 6  
Branch output 5  
Branch output 4  
Branch output 3  
Rectification  
and smoothing  
Branch output 2  
Branch output 1  
Current  
limiting  
circuit  
Current-  
Cutoff  
circuit  
Current  
fuse  
detection  
Processing circuit  
(replacement time)  
resistor  
Cutoff circuit  
+V  
SCREW (M3.5)  
DC OUTPUT  
AC (L)  
Current-  
detection  
resistor  
Thermal  
fuse  
Fuse:  
Noise  
8 A  
INPUT  
AC (N)  
V  
V  
filter  
SCREW (M4)  
Harmonic Smooth-  
Rectifi- Inrush  
Rectification  
and smoothing  
current  
ing  
current  
cation  
control  
limit  
Drive control  
circuit  
Power supply  
detection  
Voltage-ON  
detection  
Photocoupler  
(S8AS-48008R only)  
S8AS-48008@  
RS-485  
A ()  
B (+)  
Communications  
circuit  
TRP  
LOW  
Temperature  
detection  
Display  
circuit  
Voltage  
detection  
Switches  
LFE  
Processing circuit  
(main processing)  
TMP  
Communications between  
processing circuits (RS-232C)  
COM  
TRG+  
TRG−  
Branch output 8  
Branch output 7  
Branch output 6  
Branch output 5  
Branch output 4  
Branch output 3  
Branch output 2  
Branch output 1  
Current  
limiting  
circuit  
SCREW (M3.5)  
Current-  
detection  
circuit resistor  
Cutoff  
AC (L)  
Current fuse  
+V  
Cutoff circuit  
Fuse:  
12 A  
Noise  
filter  
INPUT  
AC (N)  
DC OUTPUT  
Current-  
detection  
resistor  
Thermal  
fuse  
Harmonic Smooth-  
Rectifi- Inrush  
Rectification  
and smoothing  
V  
V  
current  
ing  
current  
cation  
SCREW (M4)  
control  
limit  
Voltage-ON  
detection  
Control  
circuits  
Drive  
circuit  
Process-  
Voltage detection  
ing  
Current detection  
Current-ON detection  
circuit  
Rectification  
and smoothing  
Auxiliary power  
supply circuit  
6
S8AS  
Constructions and Nomenclature  
Nomenclature  
S8AS-24006@  
No.  
Name  
Functions  
1
2
9
13  
Connects the input power supply  
(100 to 240 VAC, 50/60 Hz)  
(commercial power supply). *1  
1
AC Input Terminals (L and N)  
Protective Earth (PE) Terminal (  
S8AS-24006  
POWER SUPPLY  
2
3
)
Connects to the ground wire. *2  
8
A(-)  
B(+)  
Screwless terminals with 2-pole  
terminals for each branch output.  
RS485  
1
2
3
4
5
6
V
A
Yrs°C s  
Positive Branch Output Terminals (+)  
L
N
10  
11  
INPUT  
50/60Hz AC100-240V 3.8A  
1
2
3
4
5
6
Screwless terminals with 2-pole  
terminals for each branch output  
and screw terminal shared by the  
negative branch output terminals.  
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
12  
4
Negative Branch Output Terminals ()  
-V  
3
+
1
+
2
+
3
+
4
+
5
+ 6  
Turns ON to indicate when an  
abnormal voltage or current was  
detected and the output was cut  
off. (The photoswitch output will  
turn OFF.)  
DC ON  
V.ADJ  
Tripping Alarm  
(A)  
Output (TRP) *3  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
- 6  
+
-
Turns ON to indicate when the 24-  
VDC output voltage of the S8AS falls  
below the threshold due to decrease  
in input voltage or other factors. (The  
photoswitch output will turn OFF.)  
Undervoltage  
(B) Detection Output  
(LOW)  
6
5
7
4
S8AS-48008@  
Turns OFF to indicate when the  
number of years to the set  
replacement time has been  
reached. (The photoswitch output  
will turn OFF.)  
1
2
9
13  
Maintenance  
(C) Forecast Monitor  
Output (LFE)  
I/O  
Signal  
Terminals  
5
S8AS-48008  
POWER SUPPLY  
8
A(-)  
B(+)  
Turns ON to indicate that the  
L
N
RS485  
INPUT  
1
2
3
4
5
6
7
8
V
A
Yrs°C  
7
s
50/60Hz AC100-240V 7.4A  
10  
11  
Over-temperature  
Output (TMP)  
temperature exceeded the over-  
temperature output threshold. (The  
photoswitch output will turn OFF.)  
1
2
3
4
5
6
8
(D)  
+V  
-V  
12  
Class2  
OUTPUT  
DC 24V 3.8A  
Negative Common  
(E) Terminal (COM)  
(no polarity)  
-V  
Negative common shared by the  
four alarm outputs ((A) to (D)) above.  
3
+
1
+
2
+
3
+
4
+
5
+
6
+
7
+ 8  
DC ON V.ADJ  
Positive External  
(F)  
Can be used to send an input  
signal from an external device to  
cut off a branch output. *4  
Tripping Input (TRG+)  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
-
6
-
7
- 8  
+
-
Negative External  
(G)  
Tripping Input (TRG)  
Indicates whether there is output  
voltage supplied.  
6
Output Indicator (DC ON (Green))  
5
6
7
4
7
8
Output Voltage Adjuster (V.ADJ)  
Seven-segment Display (Red)  
Adjusts the output voltage.  
5. I/O Signal Terminal Internal  
Circuit Configuration  
Displays measured values or set values.  
Light or flash when there is a  
Photoswitch  
9
Branch Output Indicators (Orange) display related to branch output  
(outputs 1 to 6 and 8). *5  
Light or flash when there is a unit (e.g.,  
10 Unit Indicators (Orange)  
11 Status indicators (Red/Green)  
Reset (RST) Key  
V, A, Yrs, °C, s) related to the value  
shown on the 7-segment display.  
Indicate the status of the branch outputs:  
Cutoff: red, Connected: green.  
*6  
Used to clear the error status when  
a branch output was cut off by an  
error or there was an alarm output.  
Used to switch the display item,  
enter or execute settings, etc.  
Enter (ENT) Key  
TRG  
TRP LOW LFE TMP COM  
+
-
Operation  
12  
Used to change the display item  
forward or to increase a set value.  
Keys  
Up (SEL) Key  
(A) (B) (C) (D) (E) (F) (G)  
Used to switch the branch output  
or to decrease a set value.The  
branch output number that is set  
remains the same in other modes.  
Down (CH) Key  
Communications Terminals (A (),  
B (+))  
Used to connect to the RS-485  
communications line.  
13  
(Only for Models That Support  
Communications)  
Note: The noise value depends on the wiring method and other factors. Insert  
a clamp filter (recommended: E04SR301334 manufactured by SEIWA)  
on the communications wiring as a countermeasure against noise.  
*1. The fuse is located on the (L) side.  
*2. This is the protective earth terminal specified in the safety  
standards. Always ground this terminal.  
*3. In Test Mode, the tripping alarm output (TRP) will operate even if  
one or more of the branch outputs is set to OFF. This error output,  
however, will not be held when operation moves to another  
operating mode.  
*4. Wire the polarity of the external tripping input correctly. After  
completing wiring, confirm that the input operates correctly.  
*5. The branch output indicators are OFF when current is not used.  
*6. 6.Information on procedures for detailed displays is given in  
Status Indicators on page 16.  
7
S8AS  
Engineering Data  
Extended Detection  
Derating Curve  
Time  
(ms)  
120  
Setting  
range  
Tripping region  
Current-  
limiting by  
internal  
circuits  
100  
80  
1
1,000  
60  
60  
20  
40  
0.5  
3.8  
11 16 19  
Branch output (A)  
20  
0
20 10  
0
10 20 30 40 50 60 70 80  
Ambient temperature (°C)  
Tripping Performance  
The S8AS detects the current of branch outputs as digital values and  
numeric processing is performed to execute cutoff operations.  
Refer to Abnormal Current Tripping for the tripping performance. The  
following cutoff functions are also provided.  
Note: 1. Internal parts may occasionally be deteriorated or  
damaged. Do not use the S8AS in areas outside the  
derating curve (i.e., in the area shown by shading A in the  
above graph).  
2. Use forced cooling if necessary to satisfy the derating curve.  
3. For 480-W models, reduce the load to 80% or less for long-  
term use at an input voltage of 95 VAC or less.  
Judgment Type Selection  
Standard, instantaneous, or extended can be set as the method for  
detecting the tripping current. With the S8AS-24006N/48008N, only  
the extended detection is supported. Refer to the S8AS User's  
Manual (Cat. No. Z269) for the setting method.  
Abnormal Current Tripping  
Standard Detection  
Current Limit  
Time  
(ms)  
This function is provided to limit excessive short currents, such as  
those that can flow for equipment short faults.  
Setting  
range  
Current-  
limiting by  
internal  
circuits  
Tripping region  
Startup Delay  
This function is provided to disable cutoff operations for 40 ms after  
the branch outputs turn ON so that cutoff operations will not occur for  
large inrush currents.  
100  
Safety Circuits  
60  
20  
Temperature fuses and current fuses are provided for each branch  
output to ensure safety even in the unusual event of an internal  
failure.  
0.5  
3.8  
11 16 19  
Branch output (A)  
Mounting  
Instantaneous Detection  
Standard Mounting  
Face-up Mounting  
Time  
(ms)  
S8AS-24006  
POWER SUPPL  
Y
A(-)  
B(+)  
RS485  
1
2
3
4
5
6
V
A
Yrs°C  
5
s
L
N
INPUT  
50/60Hz AC100-240V 3.8A  
Setting  
range  
1
2
3
4
6
Current-  
limiting by  
internal  
circuits  
Class2  
OUTPUT  
DC 24V 3.8A  
+V  
-V  
-V  
+
1
+
2
+
3
+
4
+
5
+ 6  
DC ON  
V.ADJ  
Tripping region  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
- 6  
+
-
Note: 1. The above illustration shows a 240-W model.  
2. Poor heat dissipation resulting from improper installation  
conditions may occasionally deteriorate or damage internal  
parts and also cause the maintenance forecast monitor  
function to not operate properly. Do not use any mounting  
orientation other than a standard one.  
20  
0.5  
3.8  
19  
Branch output (A)  
Inrush Current, Startup Time, Output Hold Time  
Input ON  
Input OFF  
AC input  
voltage  
Inrush current on input application  
AC input  
current  
96.5%  
90%  
Output  
voltage  
Startup time (3,000 ms max.)  
Hold time (20 ms min.)  
8
S8AS  
Functions  
Functions  
Alarm  
Alarm output  
Output status  
Alarm display  
A10  
Abnormal voltage tripping  
Abnormal current tripping  
Abnormal total current tripping (240-W models only)  
Undervoltage detection  
TRP output: OFF (normally ON)  
TRP output: OFF (normally ON)  
TRP output: OFF (normally ON)  
LOW output: OFF (normally ON)  
LFE output: OFF (normally ON)  
LFE output: OFF (normally ON)  
TMP output: OFF (normally ON)  
All branch outputs cut off.  
Relevant branch output cut off.  
A11  
All branch outputs cut off.  
A12  
ON  
ON  
ON  
ON  
A21  
Maintenance forecast monitor  
Overheating alarm  
A23  
A23/HOT  
A30  
Over-temperature  
Tripping Functions  
Function  
Operation  
Abnormal  
voltage tripping  
The output voltage is monitored and all branch outputs are cut off if the detection voltage is reached. Notification of the status  
is provided using the alarm display and the tripping alarm output (TRP).  
Refer to Chart 1. The alarm display will alternate between the voltage and the alarm code (A10).  
*1, *2, *3  
Detection voltage: 28.8 V (fixed)  
The output current is monitored and the branch output that is abnormal is cut off if the preset current is reached.  
Notification of the status is provided using the alarm display and the tripping alarm output (TRP).  
The alarm display will alternate between the current and the alarm code (A11).  
Setting range: 0.5 to 3.8 A (in 0.1-A increments). The S8AS-24006N and S8AS-48008N are set to 3.8 A. (Cannot be changed.)  
One of the following three abnormal current tripping types can be set. With the S8AS-24006N/48008N, only the standard  
detection is supported.  
Abnormal  
current tripping  
Refer to Chart 2. Standard Detection: Tripping within 100 ms. (Abnormal current will be detected and the output will be cut off within 20 ms if  
*1,  
*2  
current continuously exceeds the set value for more than 80 ms.)  
Instantaneous Detection: Tripping within 20 ms. (Abnormal current will be detected and the output will be cut off within 10 ms  
if current continuously exceeds the set value for more than 10 ms.)  
Extended Detection: Tripping within 1,000 ms. (Abnormal current will be detected and the output will be cut off within 20 ms  
if current continuously exceeds the set value for more than 980 ms.)  
Using the abnormal total current tripping function, the S8AS monitors the total output current and when the total output current  
exceeds the set value, all branch outputs are cut off. Notification of the status is provided using the alarm display and the  
tripping alarm output (TRP). The error code A12 will be shown on the display. There are a number of conditions for the tripping  
current and time. If even one of these conditions is detected, the abnormal total current tripping function will be activated.  
240 W: Branch outputs are cut off when the total output current is more than 17 A for 2 s, 15 A for 5 s, 13 A for 10 s, or 12 A  
for 20 s.  
Abnormal total  
current tripping  
*1, *2  
480 W: Branch outputs are cut off when the total output current is more than 27 A for 1 s, 25 A for 2 s, or 22.5 A for 5 s.  
The output can be cut off by inputting a voltage to the external tripping input (TRG terminal). If a shutdown sequence has been  
set, outputs will be cut off according to the shutdown sequence.  
Each branch output can be enabled or disabled individually. On the S8AS-24006N/S8AS-48008N, all branch outputs are  
enabled. (Cannot be changed.)  
External input signal width: 10 ms min.  
Input signal levels  
High level: 19.2 to 30 VDC  
External tripping  
input  
*1  
Low level: 0 to 2.5 VDC  
Tripping can also be performed by using communications (S8AS-24006R/S8AS-48008R only).  
Refer to the S8AS User's Manual (Cat. No. Z269) for information on tripping using communications.  
Note: Three abnormal current tripping types with different tripping current characteristics are supported: standard detection, instantaneous  
detection, and extended detection. Select the required tripping type.  
*1. Outputs are cut off using semiconductor relays and electrical insulation is not provided.  
*2. With the default settings, the alarm display and alarm output can be cleared using one of the following methods.  
Clear using the reset operation.  
Clear by turning the supply power OFF and ON again.  
*3. The voltage detection is performed on the voltage after AC/DC conversion in the internal circuits. The displayed voltage will be somewhat  
different from the value at the output terminals of the power source due to internal voltage drop. To confirm correct output voltages, measure  
the voltages at the branch output terminals.  
9
S8AS  
Chart 1: Operation Timing  
Chart 2: Operation Timing  
(Fixed)  
28.8 V (Abnormal voltage tripping)  
(Settable)  
3.8 A (Abnormal current tripping)  
24 V (Rated)  
3.0 A (Normal current)  
20 V (undervoltage detection)  
(Settable)  
0
0
t
t
100 ms  
A21  
A10  
Alarm display  
Alarm display  
A11  
Within 20 ms for instantaneous detection  
and 100 ms for standard detection, or  
within 1000 ms for extended  
detection (depends on tripping type).  
Tripping alarm output *  
Undervoltage detection output  
*
20 ms  
* The tripping alarm output is a photoswitch output.  
The output is normally ON and turns OFF when  
an alarm is detected.  
Tripping alarm output *  
Reset  
* The undervoltage detection output and tripping alarm  
output are both photoswitch outputs. The output is  
normally ON and turns OFF when an alarm is detected.  
Alarm Functions  
Function  
Operation  
The voltage is monitored and notification is provided using the alarm display and output (LOW) if the preset voltage is  
exceeded for more than 80 ms. The alarm display will alternate between the voltage and the alarm code (A21). The primary  
voltage is measured at the input terminals.  
Undervoltage detection threshold setting range: 18.0 to 26.4 V in 0.1-V increments.The S8AS-24006N and S8AS-48008N are  
set to 20.0 V. (Cannot be changed.)  
Undervoltage  
detection output  
(Refer to Chart 1.)  
*1, *2  
The time that the power is ON is calculated as the S8AS run time and notification is provided using the alarm display and  
maintenance forecast monitor output (LFE) if the preset time is reached. The alarm display will alternate between the run time  
and the alarm code (A23).  
Maintenance  
forecast monitor  
*1  
Display range: FUL (Full), HLF (Half), or 0.0 to 5.0 years.  
The internal temperature of the S8AS is monitored using a built-in temperature sensor and notification is provided using the  
alarm display and over-temperature output (TMP) if the preset temperature is exceeded for more than 1 s. The alarm display  
will alternate between the temperature and the alarm code (A30). The over-temperature output is convenient for control  
operations, such as operating a cooling fan to suppress temperature increased in the control panel.  
Note: The alarm display and over-temperature output are automatically cleared if the temperature falls below the set  
temperature.  
Over-temperature  
(Refer to Chart 3.)  
*1  
Display range: 20 to 100°C in 1°C increments.  
Temperature setting range: 25 to 90°C in 1°C increments.  
Note: 1. Branch outputs are not cut off for the alarm functions  
2. The voltage detection is performed on the voltage after AC/DC conversion in the interval circuits. The displayed voltage will be somewhat  
different from the value at the output terminals of the power source due to internal voltage drop. To confirm correct output voltages,  
measure the voltages at the branch output terminals.  
Chart 3: Operation Timing  
Temperature  
50°C  
(Settable)  
0
t
A30  
A30  
A30  
Alarm display  
Temperature *  
* The alarm display and over-temperature output are automatically  
cleared (with hysteresis). The over-temperature output is a  
photoswitch output. It is normally ON and turns OFF when an  
alarm is detected.  
10  
S8AS  
Maintenance Forecast Monitor Function  
Indication and Output  
Example: Display When the Time Remaining to the  
Maintenance Time Is Less Than 0.5 yr  
When the Product is purchased, “ful” will be displayed. As the  
electrolytic capacitors deteriorate, the display will change to “hlf”  
(Refer to Maintenance Forecast Monitor Function). “ful” will be  
displayed for the maintenance forecast display for approximately one  
month after the Power Supply is first turned ON. The accumulated  
value will then be displayed depending on the ambient conditions.  
(However, the “hlf” display may not appear, depending on the  
application environment and the set value for maintenance forecast.)  
If the maintenance forecast setting L (which can be set to 0.0 to 5.0  
years in 0.5-year increments) is set to a value larger than two years,  
the display automatically changes to a value (L - 0.5) after the  
remaining time to maintenance is reduced to the set number of years,  
and an alarm (A23) and the remaining time will be displayed  
alternately.  
If the setting is less than 2.0 years, the display changes to a value  
(1.5) after the remaining time becomes less than two years, and after  
the remaining time becomes less than the set time, an alarm (A23)  
and the remaining time (L - 0.5) will be displayed alternately.  
If the alarm (A23) and a numeric value are displayed alternately, the  
transistor (maintenance forecast output terminal (Yrs)) will turn OFF  
to indicate the need for maintenance., i.e., there will be no continuity  
at the maintenance forecast output terminals.  
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V A Yrs°C s  
Note: 1. The time remaining to maintenance is based on continuous  
operation, not including the time when the power supply is  
turned OFF.  
2. ful” will be displayed until approximately one month of  
time has passed to enable estimating the speed of  
deterioration. The output will remain ON (i.e., there will be  
continuity at the maintenance forecast output terminal  
(Yrs)).  
3. For details on the display, refer to Relationship between  
Displayed Values and Output of Set Values.  
(The LEF output will turn OFF when the maintenance time has been  
reached.)  
Maintenance Forecast Monitor Function  
The Power Supply is equipped with electrolytic capacitors.  
The electrolyte inside the electrolytic capacitors penetrates the  
sealing rubber and evaporates as time passes after it is  
manufactured. This causes deterioration of characteristics, such as  
decreasing the capacitance.  
Due to this deterioration of the characteristics of the electrolytic  
capacitor, the Power Supply decreases its performance as time  
passes.  
The maintenance forecast monitor function shows an approximate  
period left for maintenance of the Power Supply due to deterioration  
of electrolytic capacitors. When the period left for maintenance that  
the power supply forecasts reaches the set value, an alarm is  
indicated and an output signal is triggered. Use this function to know  
the approximate replacement timing of the Power Supply.  
Note: The maintenance forecast monitor function indicates an  
approximate period left for maintenance, based on  
deterioration of the electrolytic capacitors. It does not predict  
failures resulting from other causes.  
Relationship between Displayed Values and Output of Set Values  
L: Maintenance forecast set value  
When L is set to between 2.5 and 5 years.  
0.0 to 5.0, 0.5 steps  
Initial capacity  
(L 0.5)  
"1.0" is displayed on the main display for the duration  
that the maintenance forecast up to replacement  
satisfies the condition 1.0 T < 1.5.  
Capacity at  
replacement  
time  
5.0  
2.5  
2.0  
1.5  
1.0  
0.5  
0
Electrolytic capacitor capacity  
Main display  
T: Maintenance time until replacement  
L = 2.5  
L = 0.5  
Maintenance forecast  
monitor output  
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V A Yrs°C s  
The numeric value  
decreases with time.  
11  
S8AS  
Principle of Operation  
Difference between Expected Life and Replacement Time  
OMRON calculates the expected life based on the following  
conditions.  
1. Rated input voltage  
2. Load rate: 50%  
The deterioration speed of the electrolytic capacitors varies  
considerably with the ambient temperature. (Generally the speed  
follows the Arrhenius Law, i.e., for every 10°C increase in the  
temperature, the rate of degradation doubles.) The S8AS monitors  
the temperature inside the Power Supply, and calculates the amount  
of deterioration according to the operating hours and internal  
temperature.  
3. Ambient temperature: 40°C  
4. Standard Mounting  
Note: The expected life is calculated by performing a temperature rise  
test using an aluminum electrolytic capacitor, and therefore is  
not a guaranteed value.  
Based on this amount of deterioration, the Power Supply will provide  
an alarm indication and output when the period left for maintenance  
reaches the set value.  
Note: 1. Due to degradation of internal electronic parts, replace the  
Power Supply approximately 15 years after purchase even  
if the maintenance forecast monitor indication and output do  
not appear.  
The expected life span of the S8AS is 10 years.  
The maintenance forecast is the service life (the Power Supply's  
internal temperature is monitored at all times) of the internal  
electrolytic capacitors in actual operating conditions, and depends on  
the customer's operating conditions. The maximum period of the  
maintenance forecast is taken as 15 years.  
2. The maintenance forecast is accelerated or decelerated  
according to operating conditions. Periodically check the  
display.  
3. Acceleration or deceleration of the maintenance forecast  
may cause the output to repeatedly go ON and OFF.  
4. The accuracy of the maintenance forecast function may be  
adversely affected by applications in which the AC input is  
frequently turned ON and OFF.  
Other Functions  
Function  
Operation  
The connection timing for branch outputs 1 to 6 and 8 can be set individually to offset the connection timing to the load  
devices. Creating time delays between starting loads enables safer load operation. It also reduces total inrush current so  
that power supply capacity can be optimized.  
Startup sequence  
(Refer to Chart 5.)  
Setting range:  
0.0 to 99.9 s in 0.1-s increments.  
For the S8AS-24006N and S8AS-48008N, the settings are 0.0 s for branch output 1, 0.4 s for branch  
output 2, 0.8 s for branch output 3, 1.2 s for branch output 4, 1.6 s for branch output 5, 2.0 for branch  
output 6, 2.4 s for branch output 7, and 2.8 s for branch output 8. (Cannot be changed.) *  
The cutoff timing for branch outputs 1 to 6 and 8 can be set individually to offset the cutoff timing of load devices for the  
external tipping input or to enable an emergency stop.  
Setting range: 0.0 to 99.0 s in 0.1-s increments. For the S8AS-24006N and S8AS-48008N, all branch outputs have a setting  
Shutdown  
sequence  
(Refer to Chart 6.)  
of 0.0 s. (Cannot be changed.) *  
A delay function is provided so that the abnormal current tripping function  
or overcurrent alarm function will not be triggered by large initial inrush  
Current  
Alarm function disabled  
for large inrush  
currents at startup.  
currents, e.g., for capacitive loads or lamp loads. The abnormal current  
tripping function will function once the set time has elapsed.  
(Note: The delay is 40 ms and cannot be changed.)  
Startup Delay  
0
t
40 ms: Delay  
* The sequencing functions are designed for the six branch outputs of one S8AS. There is no synchronization processing between S8AS Power  
Supplies when more than one S8AS is used. Sequencing functions for branch outputs 7 and 8 are available only with the S8AS-48008N.  
12  
S8AS  
Chart 5: Operation Timing  
Chart 6: Operation Timing  
External tripping input  
Power supply voltage  
Branch output 1 voltage  
Branch output 2 voltage  
Branch output 3 voltage  
Branch output 1 voltage  
Branch output 2 voltage  
Branch output 3 voltage  
Startup sequence time  
Startup sequence time  
Startup sequence time  
Shutdown sequence time  
Shutdown sequence time  
Shutdown sequence time  
Branch output 6 or  
branch output 8 voltage  
Branch output 6 or  
branch output 8 voltage  
Startup sequence time  
Shutdown sequence time  
20 ms max.  
Self-diagnostics  
(0.5 s min.)  
Note: 1. Cut off simultaneously for tripping for abnormal voltages  
(28.8 V or higher).  
Note: For the S8AS-24006N and S8AS-48008N, the settings are  
0.0 s for branch output 1, 0.4 s for branch output 2, 0.8 s for  
branch output 3, 1.2 s for branch output 4, 1.6 s for branch  
output 5, 2.0 for branch output 6, 2.4 s for branch output 7, and  
2.8 s for branch output 8. (Cannot be changed.)  
(Branch outputs 7 and 8 are available only with the S8AS-  
48008N.)  
2. For the S8AS-24006N and S8AS-48008N, all branch  
outputs have a setting of 0.0 s. (Cannot be changed.)  
13  
S8AS  
Key Operations and Displays in Each Mode  
Power ON  
First startup after purchase.  
When power was turned  
OFF in any mode except  
Test Mode.  
When power was turned  
OFF in Test Mode  
*3  
Run Mode  
Setting Mode  
Test Mode  
*2  
Output voltage  
Current tripping  
Value Setting  
Individual branch outputs  
*1, *2  
display  
threshold  
No key operation for more than 3 s.  
Connected  
Cut off  
Selection of Standard,  
Instantaneous, or  
Total Current  
Display  
Current tripping  
type  
Extended Detection  
No key operation for more than 3 s.  
*1  
Output Current  
Undervoltage  
detection threshold  
Value Setting  
Display  
Cut off all branch outputs  
(Shutdown Sequence)  
No key operation for more than 3 s.  
*1  
Peak Output  
Current Display  
Clearing selected  
peak output current.  
Over-temperature  
output threshold  
Execute  
Value Setting  
No key operation for more than 3 s.  
or no key operation for  
more than 3 s.  
Maintenance Forecast  
Monitor Output Display  
Startup Sequence  
Time Setting *2  
Time Setting  
Connect all branch outputs  
(Startup Sequence)  
No key operation for more than 3 s.  
Temperature  
Display  
Shutdown Sequence  
Time Setting *2  
Execute  
Time Setting  
No key operation for more than 3 s.  
External Tripping  
Input Setting *2  
Enable/Disable  
Setting  
No key operation for more than 3 s.  
Selection of Tripping  
Trigger Type: EGE/LVL  
External Tripping  
Trigger Type  
No key operation for more than 3 s.  
Communications Settings  
(Models with  
communications only)  
Settings  
No key operation for more than 3 s.  
Press for 3 s.  
Select reset  
method  
Selection of  
Method  
No key operation for more than 3 s.  
Mode Selection Menu  
Press for 3 s.  
Press for 3 s.  
*3  
*3  
*3  
Select Run Mode  
Select Setting Mode  
Select Test Mode  
Select Protection level  
Initialize Parameters  
Press for 3 s.  
Press for 3 s.  
Level Selection  
Yes, initialize.  
*1. Branch outputs can be changed using the Down (  
) Key. The changes to the branch outputs will be retained in other displays as well.  
*2. Settings are displayed in order for branch outputs. Specific branch output settings have been omitted.  
*3. Not displayed for the S8AS-24006N/48008N.  
14  
S8AS  
Mode Descriptions  
The S8AS supports a Run Mode, Setting Mode, and Test Mode.  
Mode Selection Menu  
(1) Run Mode (RUN)  
Used for normal operation.  
(1) In Run Mode, the current for each branch output, the total output  
The measurements for the output voltage, output  
current, the output voltage, the replacement time, the internal  
temperature, and other values can be displayed.  
Use this mode for operation once initial settings and system  
adjustments have been completed.  
Run Mode  
current, replacement time, and internal  
temperature can be read on the seven-segment  
display.  
(2) Setting Mode (SET)  
Setting Mode * Used to set or change S8AS parameters.  
(2) Setting Mode is used to set parameters.  
Used to test operation for devices connected to  
Test Mode  
the S8AS.  
Note: Refer to the S8AS User's Manual (Cat. No. Z269) for details.  
* The S8AS-24006N and S8AS-48008N do not have a Setting Mode.  
(3) Test Mode (TST)  
(3) Test Mode enables forcing branch outputs ON and OFF.  
Connections and cutoffs can be manipulated for all outputs for each  
branch output. By default, all outputs will be ON (connected).  
Use this mode to set unused branch outputs to OFF (not connected).  
Initial Setting Procedure after Purchase  
The following diagram illustrates mode transitions for the S8AS.  
When the S8AS is turned ON for the first time, it will enter Setting  
Mode. After changing to Setting Mode, set the initial setting for each  
parameter, and then switch to Test Mode or Run Mode.  
(4) Protection Level  
(PRT)  
(4) Protection Level can be used to set restrictions for setting  
parameters.  
Three levels, levels 0, 1, and 2, are available. The default is level 1.  
Refer to the User's Manual for the parameters that are protected in  
each level.  
When newly  
purchased.  
S8AS was not in  
Test Mode when  
power went OFF.  
Power ON  
S8AS was in  
Test Mode  
when power  
went OFF.  
Mode Selection Menu  
Run Mode  
(5) Initialize Parameters  
*
3
(INI)  
(5) Parameters can be initialized to return all parameters to their default  
Select Run Mode run (RUN)  
settings.  
Press for 3 s.  
The Initialize Parameters is not displayed in the default protection  
level (level 1).  
*1  
Select Setting Mode set (SET)  
((1) Switches to  
RUN Mode display.)  
Setting Mode  
Select Test Mode tst (TST)  
*1  
Test Mode  
Go to Setting Mode to change any of the default parameter settings.  
Operation may be restricted by the protection level, preventing  
changes to some parameters. If necessary, change the protection  
level.  
Press for 3 s.  
Press for 3 s.  
Select Protection Level prt (PRT)  
Refer to the User's Manual for details on parameters and restrictions  
for the protection levels.  
*1, *2  
Initialize Parameters ini (INI)  
*
*
*
1. Not displayed for the S8AS-24006N/48008N.  
2. Initialize Parameters is displayed only in protection level 0.  
3. If the Mode Selection Menu is entered in Test Mode and then the power is  
turned OFF before entering another operating mode, the S8AS will start in  
Test Mode the next time it is started.  
15  
S8AS  
Status Indicators  
The status indicators light according to the branch output status as  
described below.  
Run Mode  
Run Mode is used for normal operation. When the power is turned ON  
and the mode was Run Mode or Setting Mode the last time the input  
power was turned OFF, the S8AS will start in Run Mode and  
Lit green  
Normal connection status  
connecting the branch outputs will be started. Monitoring of voltages,  
currents, replacement time, and temperature can be confirmed using  
the Up Key and Down Key (  
Flashing  
green  
Connection standby status during the startup  
sequence  
/
).  
Lit red  
Cutoff status for an abnormality  
(1) Output Voltage  
(1) When Run Mode is entered, the parameter  
that was displayed the last time Run Mode  
was used will be displayed.  
The voltage output display is shown at the  
left as an example.  
Flashing red  
Not lit  
Cutoff status for an internal abnormality  
Forced cutoff or operation stopped  
1
2
3
4
5
6
V
V
V
A Yrs°C  
A Yrs°C  
A Yrs°C  
s
s
s
S8AS-24006  
POWER SUPPLY  
A(-)  
B(+)  
RS485  
1
2
3
4
5
6
V
A
Yrs°C  
5
s
L
N
(2) Total Output  
Current  
INPUT  
50/60Hz AC100-240V 3.8A  
(2) The total current for all outputs is displayed.  
1
2
3
4
6
Status Indicators  
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
1
2
3
4
5
6
-V  
+
1
+
2
+
3
+
4
+
5
+ 6  
DC ON  
V.ADJ  
(3) The output current of the last branch output  
that was set will be displayed regardless of  
the operating mode.  
The current output of the branch output 1 is  
shown at the left.  
The current output of the branch output 2 is  
shown by pressing the Down (CH) Key.  
*The branch output number set with the Down  
(CH) Key is stored in memory even when the  
operating mode or parameters are changed.  
The branch output displayed when Test Mode is  
entered will not necessarily be branch output 1.  
(3) Present Output  
Current for  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
- 6  
+
-
Branch Output 1  
*1  
1
2 3 4 5 6  
Clearing the Peak Output Currents  
(Select the branch output with the  
Down (CH) Key.))  
The peak output currents can be cleared. Select the peak output  
current to be cleared in Run Mode and then use the following  
operation.  
(4) Press the Up (SEL) Key to display the peak  
current for the branch output displayed in step 2  
(e.g., branch output 2). The “A” unit indicator will  
flash while the peak current is being displayed.  
The peak current can be cleared by performing  
the following procedure while the peak current is  
being displayed.  
1. Press the ENT Key.  
2. Change the “NO” display to the “YES”  
display using the Up (SEL) Key.  
Peak Output Current  
Display  
(4) Peak Current for  
Branch Output 2  
Waiting display, 1 s  
1
2
3
4
5
6
V
A Yrs°C  
s
Flashing  
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V A Yrs°C s  
(Select the branch output with the  
Down (CH) Key.))  
or 3 s with  
no key  
operations  
Clearing completed.  
3. Press the ENT Key again.  
(5) Replacement  
Time  
(5) Displays the estimated number of years  
until the replacement time.  
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V A Yrs°C s  
1
2
3
4
5
6
V A Yrs°C s  
After flashing for 3 s  
Set value saved  
(flashes for 3 s)  
(6) Internal  
Temperature  
(6) Displays the internal temperature.  
1
2
3
4
5
6
V A Yrs°C s  
1
2
3
4
5
6
V A Yrs°C s  
Press the Up (SEL) Key again to return to the  
output voltage display and start the display  
cycle again.  
Indicator Status Notation  
Lit Flashing  
((1) Switches to output voltage display.)  
Note: 1. The S8AS will start in Run Mode when power is turned ON  
for the first time after shipping from the factory.  
2. Settings cannot be changed in Run Mode. Use Setting  
Mode to change settings. (The setting for the S8AS-24006N  
and S8AS-48008N can not be changed.)  
3. If a startup sequence has been set, connections will be  
started according to the set delays.  
4. When moving to Run Mode, the branch output ON/OFF  
status from before entering Run Mode will be maintained.  
After testing branch output operation in Test Mode, always  
turn ON the required branch outputs before moving to Run  
Mode.  
5. The voltage detection function monitors the voltage at the  
power input terminals. Measure the voltage at the branch  
output terminals to confirm that the output voltage is correct.  
16  
S8AS  
Setting Mode  
Setting Mode is used to set S8AS parameters. Settings can be read or changed while operation continues.  
The various parameters can be selected as shown below.  
Abnormal Current Tripping Value  
The current at which a branch output is cut off  
Setting range: 0.5 to 3.8 A.  
The branch output will be cut off if the value set here is  
exceeded.  
C-V  
Communications Settings (*1, *5)  
Unit No.  
Unit number setting (0 to 31)  
Branch output selection  
UNO  
BPS  
LEN  
BIT  
Abnormal Current Tripping Type (*1)  
Detection settings for currents to cut off branch outputs  
Standard detection/instantaneous detection (*2)  
C-T  
Baud Rate  
Bit Length  
Stop Bits  
Baud rate setting  
48: 4,800 bps, 96: 9,600 bps  
Branch output selection  
Undervoltage alarm  
The undervoltage alarm will be output if the voltage drops  
below this threshold value.  
Setting range: 18.0 to 26.4 V  
V-U  
LFE  
An alarm will be output if the value set here is exceeded.  
Bit length setting (7 or 8)  
Stop bit setting (1 or 2)  
Maintenance forecast monitor  
Over-temperature Output  
The replacement time for the S8AS is calculated from the  
operating time and internal temperature. The maintenance  
forecast monitor output will operate when the replacement  
time falls below the value set here.  
Setting range: 0.0 to 5.0 years  
The temperature at which an signal is output.  
Setting range: 25 to 90°C  
An over-temperature signal will be output if the value set  
here is exceeded.  
TMP  
Parity  
Parity setting  
non: None, evn: Even, odd: Odd  
PTY  
SWT  
Startup Sequence (*1)  
Enable/disable the startup sequence and set the time for  
each branch output.  
UPS  
Send Wait Time  
Time setting range: 0.0 to 99.9 s (*3)  
Send wait time setting  
0 to 999 ms  
Branch output selection  
Shutdown Sequence (*1)  
Enable/disable the shutdown sequence and set the time  
for each branch output.  
DWS  
Reset method *1  
Time setting range: 0.0 to 99.9 s (*4)  
Reset method setting  
KEY: Clear errors using the Reset Key (RST)  
ALL: Clear errors using the Reset Key (RST) or  
by turning the power OFF and ON again.  
RST  
Branch output selection  
External tripping (*1)  
Enables (ON) or disables (OFF) the external  
tripping input function.  
Note: 1. Parameters cannot be changed in protection level 2, or  
when using the S8AS-24006N or S8AS-48008N.  
2. The S8AS will start in Run Mode when power is turned  
ON for the first time after shipping from the factory.  
3. Refer to the S8AS User's Manual (Cat. No. Z269),  
when having further settings.  
*1. Not displayed in protection level 1 or 2.  
*2. The S8AS-24006N and S8AS-48008N use Extended  
Detection. (Cannot be changed.)  
TRG  
TGS  
Branch output selection  
Tripping trigger type selection (*1)  
External tripping  
Tripping trigger type setting: EGE/LVL  
*3. The S8AS-24006N and S8AS-48008N use a startup  
sequence using an offset of 0.4 s starting with the first  
branch output. (Cannot be changed.)  
*4. The shutdown sequence shutdown delay on the S8AS-  
24006N and S8AS-48008N is set at 0.0 s. (Cannot be  
changed.)  
Setting Parameters  
Parameters are set as shown below.  
Example for Setting the Abnormal Current Tripping Value  
*5. Communications settings will not be displayed on models  
that do not have communications functions.  
Use  
and  
to change the set value.  
After no key  
operations  
for 3 s  
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V A Yrs°C s  
When finished, press  
to save the set value.  
Set value saved (flashes for 3 s).  
After flashing  
for 3 s  
1
2
3
4
5
6
V A Yrs°C s  
Indicator Status Notation  
Lit Flashing  
17  
S8AS  
Test Mode  
Protection Level Setting  
A protection level can be set to prevent operating errors during normal  
operation. Reading or changing parameter settings and other  
operations can be restricted in three levels.  
Device startup operation can be tested by turning ON/OFF branch  
outputs either individually or together. The branch outputs that are to  
be used are set to be connected in Test Mode. The operation to turn  
all branch outputs ON/OFF together can be used to check startup and  
shutdown sequences.  
Protection  
Level  
Intended for  
Possible operations  
Test Mode (TST) Selected  
Facility designers  
and manufacturers changed.  
All settings can be read and  
0
1
2
Facility  
maintenance  
personnel  
Some settings can be read and  
changed.  
Press for 3 s.  
(5)  
Settings can be read but not  
changed.  
On-site operators  
(1)  
(3)  
Select PRT (protection level) from the Mode Selection Menu and then  
perform the following procedure. (The following example shows  
changing to protection level 0.)  
1
2
3
4
5
6
V
A Yrs°C  
5
s
1
2
3
4
5
6
V
A Yrs°C  
5 6  
s
1
2
3
4
6
1
2
3
4
Setting Protection Level  
After no key  
operations  
for 3 s  
(2)  
(4)  
Mode Selection Menu  
(Protection Level)  
1
2
3
4
5
6
V
A Yrs°C  
5
s
1
2
3
4
5
6
V
A Yrs°C  
5 6  
s
1
2
3
4
6
1
2
3
4
After no key operations for 3 s  
Select TST (Test Mode) from the Mode Selection Menu and press the ENT Key.  
Test Mode will be entered.  
(1) When Test Mode is entered, the branch output number 1 indicator (see note) will flash and  
“OFF” or “ONwill flash on the 7-segment display.  
OFF flashing: Press the ENT Key to turn OFF branch output 1.  
ON flashing: Press the ENT Key to turn ON branch output 1.  
(2) The branch output can be selected at display (1) by using the Down (CH) Key.  
Press the ENT Key to turn the output ON and OFF.  
(3) If the Up (SEL) Key is pressed at display (1), all branch output number indicators will flash  
and “OFF” will flash on the 7-segment display. All branch outputs can be turned OFF in this  
condition.  
Parameter Initialization  
All S8AS parameters can be restored to their default settings.  
Set protection level 0 and then go to the Mode Selection Menu. INI  
(parameter initialization) will be added to the menu. Select INI and  
then perform the following procedure.  
Press the ENT Key to turn all branch outputs OFF.  
(4) If the Up (SEL) Key is pressed at display (3), all branch output number indicators will flash  
and “ONwill flash on the 7-segment display. All branch outputs can be turned ON in this  
condition.  
Mode Selection Menu  
Parameter Initialization  
(Parameter Initialization)  
Press the ENT Key to turn all branch outputs ON.  
(5) After completing ON/OFF testing and setting the branch outputs, press the Up (SEL) and  
Down (CH) Keys simultaneously for 3 s to go to the Mode Select Menu, and then enter Run  
Mode.  
After no key  
operations  
for 3 s  
* The branch output number set with the Down (CH) Key will not change even when the  
operating mode or parameters are changed. The branch output displayed when Test Mode is  
entered will not necessarily be branch output 1.  
Note: 1. In Test Mode, the branch output number indicators and 7-  
segment display will continue to flash.  
2. In Test Mode, the abnormal tripping output (TRP) will  
operate if one or more of the branch outputs are not  
connected. The TRP output will not operate if the operating  
mode is changed.  
Setting Confirmation  
(Flashes for 3 s.)  
Run Mode  
3. If power is turned OFF in Test Mode, Test Mode will be  
entered the next time power is turned ON.  
Note: 1. The Mode Selection Menu is not displayed in protection  
level 1 or 2. The default setting is for protection level 1.  
2. Default Settings  
Indicator Status Notation  
Lit  
Flashing  
The operating mode will change to Run Mode.  
The parameters will change to their default settings.  
All branch outputs will be changed so they are connected.  
The protection level will change to level 1.  
18  
S8AS  
List of Alarms  
Alarm  
display  
Power  
outputs  
Name  
Alarm outputs  
Recovery/reset method  
Remove the cause of the abnormality and then press the Reset Key( ) on the  
front panel or use communications reset function (S8AS-24006R and S8AS-  
Abnormal  
voltage  
tripping  
TRP output: OFF Total current 48008R only). *  
A10  
(normally ON)  
tripping  
Cut off  
Power supply will be restarted after recovery.  
Note: Once an error has been reset, another reset operation cannot be  
performed for at least 15 seconds.  
Remove the cause of the abnormality and then press the Reset Key( ) on the  
front panel or use communications reset function (S8AS-24006R and S8AS-  
48008R only). *  
Abnormal  
current  
tripping  
TRP output: OFF  
(normally ON)  
A11  
A12  
Power supply will be restarted after recovery.  
Note: Once an error has been reset, another reset operation cannot be  
performed for at least 15 seconds.  
Remove the cause of the abnormality and then press the Reset Key( ) on the  
front panel or use communications reset function (S8AS-24006R and S8AS-  
48008R only). *  
Note: Once an error has been reset, another reset operation cannot be  
performed for at least 15 seconds.  
Abnormal  
total current  
tripping  
TRP output: OFF Total current  
(normally ON)  
tripping  
Remove the cause of the abnormality and then press the Reset Key( ) on the  
front panel or use communications reset function (S8AS-24006R and S8AS-  
48008R only). *  
Note: 1. Once an error has been reset, another reset operation cannot be  
performed for at least 15 seconds.  
Undervoltage ALM output: OFF  
A21  
ON  
alarm  
(normally ON)  
2. The alarm status will be reset if the cause of the alarm has been  
removed when the power supply is reset.  
Maintenance  
forecast  
monitor output  
The replacement time specified for the S8AS has become less than the value set  
for the maintenance forecast monitor function. Either replace the S8AS or change  
the set value.  
LEF output: OFF  
(normally ON)  
A23  
ON  
ON  
ON  
Take steps to reduce the internal temperature of the S8AS. The error will  
automatically be cleared when the temperature becomes stable. However, if the  
overheating alarm stays ON for more than 3 hours, it can no longer be cleared.  
Be sure to clear the error within 3 hours.  
Overheating  
alarm  
LFE output: OFF  
(normally ON)  
A23/HOT  
Over-  
temperature  
output  
TMP output: OFF  
(normally ON)  
The alarm display and over-temperature output will automatically be reset if the  
temperature remains below the set value minus 3°C for at least 5 s.  
A30  
Note: Alarms will be displayed in order of priority if more than one alarm occurs at the same time.  
Order of priority: A10, A12, A11, A23/HOT, A21, A23, A30.  
* Enabling or disabling the functionality to reset errors by turning the power supply OFF and then ON can be set using the Reset Method Setting  
(RST) parameter. However, the settings for the S8AS-24006N and S8AS-48008N cannot be changed.  
(Initial setting: Errors can be reset by turning the power supply OFF and ON again.)  
19  
S8AS  
Alarm Display  
The S8AS displays alarms according to the parameters set in Setting  
Mode. The alarm number and detected value are alternated on the  
display for each alarm.  
Communications (S8AS-24006R/48008R)  
The built-in RS-485 port can be used to connect special Support Tool  
to set parameters, monitor, perform tripping operations for branch  
outputs, and perform other remote monitoring and control operations  
from a network.  
Example: Abnormal Current Tripping Alarm at Branch Output 4  
Type  
RS-485  
0.5 s  
Communications  
method  
Half-duplex  
Sync method  
Baud rate  
Start-stop  
0.5 s  
1
2
3
4
5
6
V
A Yrs°C  
s
1
2
3
4
5
6
V
A Yrs°C  
s
4,800 or 9,600 bps  
ASCII  
0.5 s  
Current when  
0.5 s  
Transmitted code  
Data bit length  
Stop bit length  
Error detection  
Parity check  
Protocol  
alarm occurred  
7 or 8 bits  
1 or 2 bits  
Note: Indicator Status Notation  
Lit Flashing  
Vertical parity and BCC  
None, even, or odd  
CompoWay/F  
1
2
3
4
5
6
V A Yrs°C s  
Note: Alarms will be displayed in order of priority if more than one  
alarm occurs at the same time.  
Order of priority: A10, A12, A11, A23/HOT, A21, A23, A30.  
Support Tool (S8AS-24006R/48008R)  
The Support Tool is used to set and monitor models that support  
communications. Parameters can be set, operation can be monitored,  
and parameter files can be managed.  
Resetting Alarms  
When an alarm is displayed, remove the cause of the alarm and then  
press the Reset Key (  
) for at least 3 s.  
The following display will appear and the alarm will be reset.  
For information on resetting alarms, refer to List of Alarms on the  
previous page.  
Support Tool Functions  
Reading and writing parameter settings  
Monitoring present values  
Monitoring status (cutoff status, normal/error status)  
Applicable OS: Windows 2000 or XP  
Visit OMRON's website for downloading the Support Tool.  
20  
S8AS  
Dimensions  
(Unit: mm)  
S8AS Smart Power Supplies  
124.7  
122  
160  
10  
S8AS-24006  
Three, M3.5 square washers  
S8AS-24006N  
S8AS-24006  
POWER SUPPLY  
1
2
3
4
5
6
V
A
Yrs°C  
5
s
L
N
INPUT  
50/60Hz AC100-240V 3.8A  
1
2
3
4
6
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
34.9  
115  
-V  
+
1
+
2
+
3
+
4
+
5
+ 6  
DC ON  
V.ADJ  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
- 6  
+
-
M4 square washers  
(sliding: 15 max.)  
131.8  
5.08  
4.5  
142.4  
S8AS-24006R  
124.7  
122  
160  
10  
Three, M3.5 square washers  
S8AS-24006  
POWER SUPPLY  
A(-)  
B(+)  
RS485  
1
2
3
4
5
6
V
A
Yrs°C  
5
s
L
N
INPUT  
50/60Hz AC100-240V 3.8A  
1
2
3
4
6
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
34.9  
115  
-V  
+
1
+
2
+
3
+
4
+
5
+ 6  
DC ON  
V.ADJ  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
- 6  
+
-
M4 square washers  
(sliding: 15 max.)  
131.8  
5.08  
4.5  
124.7  
122  
S8AS-48008  
S8AS-48008N  
230  
10  
Three, M3.5 square washers  
S8AS-48008  
POWER SUPPLY  
L
N
INPUT  
50/60Hz AC100-240V 7.4A  
1
2
3
2
4
5
6
7
8
V
A Yrs°C s  
1
3
4
5
6
7
8
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
34.9  
115  
-V  
+
1
+
2
+
3
+
4
+
5
+
6
+
7
+ 8  
DC ON V.ADJ  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
-
6
-
7
- 8  
+
-
M4 square washers  
(sliding: 15 max.)  
5.08  
131.8  
4.5  
142.4  
S8AS-48008R  
230  
124.7  
122  
10  
Three, M3.5 square washers  
S8AS-48008  
POWER SUPPLY  
A(-)  
B(+)  
L
N
RS485  
INPUT  
50/60Hz AC100-240V 7.4A  
1
2
3
4
5
6
7
8
V
A Yrs°C s  
1
2
3
4
5
6
7
8
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
115  
34.9  
-V  
+
1
+
2
+
3
+
4
+
5
+
6
+
7
+ 8  
DC ON V.ADJ  
TRG  
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
-
6
-
7
- 8  
+
-
M4 square washers  
(sliding: 15 max.)  
5.08  
4.5  
131.9  
21  
S8AS  
Mounting Rail (Material: Aluminum)  
PFP-100N  
0.15  
7.3  
PFP-50N  
4.5  
Model  
PFP-100N  
PFP-50N  
0.3  
0.15  
27  
35  
15 25  
25  
25  
25  
1
15(5) *  
10  
10  
1,000 (500) *  
*Values in parentheses  
are for the PFP-50N.  
Mounting Rail (Material: Aluminum)  
16  
PFP-100N2  
4.5  
Model  
0.3  
35  
27 24  
29.2  
PFP-100N2  
15 25  
25  
25  
25 15  
1
1.5  
10  
10  
1,000  
Mounting Rail (Order Separately)  
10  
End Plate  
6.2  
1
1.8  
PFP-M  
Model  
M4 × 8  
pan-head  
PFP-M  
screw  
35.5  
50  
35.5  
1.8  
11.5  
1.3  
4.8  
10  
M4 spring  
washer  
22  
S8AS  
Safety Precautions  
Refer to Safety Precautions for All Power Supplies.  
!CAUTION  
Attachment to the DIN Rail  
To mount the block on a DIN Rail, until  
it makes a clicking sound, pull down  
the Rail stopper hook portion (A) of the  
Block onto the Rail, and press the  
Block in direction (B) to lock it in place.  
A
Minor electric shock, fire, or Product failure may  
occasionally occur. Do not disassemble, modify, or repair  
the Product or touch interior of the Product.  
Minor burns may occasionally occur. Do not touch the  
Product during power is being supplied or immediately  
after power is turned OFF.  
B
To dismount the Block, pull down  
portion (C) with a flat-blade  
screwdriver and pull out the Block.  
Minor injury may occasionally occur due to electrical  
shock. Do not touch the terminals while power is being  
supplied. Also, be sure to close the terminal cover after  
wiring the terminals.  
Fire may occasionally occur. Tighten terminal screws to  
the specified torque.  
30 mm min.  
C
Rail stopper  
Wiring  
Connect the ground completely. The ground is a protective earth  
(PE) terminal specified in safety standards. If the ground is not  
connected completely, electric shock or malfunction may occur.  
Minor fire may possibly occur. Ensure that input and output  
terminals are wired correctly.  
Precautions for Safe Use  
Mounting  
The long-term reliability of the S8AS can be increased by installing  
it properly and providing sufficient heat dissipation. Use the S8AS  
within the derating curve. The S8AS is designed to radiate heat by  
means of natural air circulation. Provide appropriate space as  
shown below to allow air flow around the Power Supplies.  
Poor heat dissipation resulting from improper installation  
conditions may occasionally deteriorate or damage internal parts  
and also cause the maintenance forecast monitor function to not  
operate properly. Do not use any mounting orientation other than  
a standard one.  
Heat generated by wiring materials may cause the temperature of  
internal parts to increase, which may result in deterioration of or  
damage to the internal parts. Select the wiring materials according  
to the current that is being used. Using the wiring materials, torque,  
and wire stripping lengths in the following table is recommended to  
prevent smoke or fire of the wire material due to an abnormal load.  
Recommended Wire Diameter  
Poor heat dissipation may deteriorate or damage internal parts. Do  
not loosen the screws on the side of the Product.  
Do not allow any pieces of metal or conductors, or any clippings or  
cuttings resulting from installation work to enter the Product.  
Wire  
stripping  
length  
Recommended  
wire diameter  
Wire  
type  
Terminals  
Name  
AC input  
terminals and  
protective  
earth (PE)  
terminal  
Torque  
AWG14 to 16  
(cross-sectional Solid or 9.6 in.lb.  
8 to  
area of 0.823 to stranded (1.08 N·m) 10 mm  
75 mm  
min.  
2.081 mm2)  
Air flow  
AWG12 to 14  
(cross-sectional Solid or 12 in.lb.  
S8AS-24006  
POWER SUPPL  
S8AS-24006  
POWER SUPPL  
Screw  
terminals terminals (),  
Branch output  
Y
Y
8 to  
1
2
3
4
5
6
V
4
A
Yrs°C  
5
s
1
2
3
4
5
6
V
4
A
Yrs°C  
5
s
L
N
L
N
INPUT  
50/60Hz AC100-240V 3.8A  
INPUT  
50/60Hz AC100-240V 3.8A  
area of 2.081 to stranded (1.36 N·m) 10 mm  
1
2
3
6
1
2
3
6
UL Standard  
3.309 mm2)  
+V  
-V  
+V  
-V  
Class2  
OUTPUT  
DC 24V 3.8A  
Class2  
OUTPUT  
DC 24V 3.8A  
-V  
+
-V  
+
AWG12 to 20  
(cross-sectional Solid or 8.8 in.lb.  
Branch output  
terminals (),  
CSA Standard  
+
1
+
2
+
3
4
+
5
+
6
+
1
+
2
+
3
4
+
5
+ 6  
8 to  
DC ON  
V.ADJ  
DC ON  
V.ADJ  
area of 0.517 to stranded (1.0 N·m) 10 mm  
TRG  
TRG  
-
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
-
6
TRP LOW LFE TMP COM  
-
1
-
2
-
3
-
4
-
5
- 6  
3.309 mm2)  
+
-
+
Branch output  
positive  
terminals,branch  
75 mm  
min.  
20 mm min.  
AWG12 to 24  
(cross-sectional Solid or  
output negative  
terminals, I/O  
signal terminals,  
and  
Screwless  
terminals  
---  
10 mm  
area of 0.2 to  
stranded  
2.5 mm2)  
communications  
terminals  
23  
S8AS  
Do not push more than 100 N of force to the terminal block when  
tightening screws.  
Be sure to tighten the lock screws on the sides of the screwless  
connector after connecting it to the S8AS. When removing a  
screwless connector, be sure the lock screws are completely loose  
before pulling on the connector.  
Maintenance Forecast Monitor Function  
The accuracy of the maintenance forecast monitor function will be  
reduced in applications where the AC input turns ON and OFF  
frequently.  
Total Peak Output Current  
The S8AS is designed to provide a temporary peak current to provide  
the overcurrent required to start load devices.  
Be sure to remove the sheet covering the Product during  
installation before turning ON the power.  
The total peak output current for all branch outputs combined is given  
below. However, if even one of the following conditions is not satisfied  
by the total current, all branch outputs will be cut off to ensure safety  
based on the amount of peak current and the usage time.  
Installation Environment  
Do not use the Product where it would be subjected to shock or  
vibration. A device such as a contact breaker may be a vibration  
source. Set the Product as far as possible from possible sources of  
shock or vibration. Additionally, install a PFP-M End Plate on each  
end of the Product after mounting it to a DIN Rail.  
240-W Models  
Input voltage range: 200 to 240 VAC  
Total peak current/Peak current pulse width:  
If the Product is used in an area with excessive electronic noise, be  
sure to separate the Product as far as possible from the noise  
sources.  
17 A max./2 s max.  
13 A max./10 s max.  
15 A max./5 s max.  
12 A max./20 s max.  
480-W Models  
Input voltage range: 200 to 240 VAC  
Ambient Operating and Storage Environment  
Total peak current/Peak current pulse width:  
27 A max./1 s max.  
22.5 A max./5 s max.  
25 A max./2 s max.  
Store the Product at an ambient temperature of 25 to 65°C and  
relative humidity of 25% to 90%.  
Note: 1. If the input voltage range is outside of the range given  
above, or if the total output current exceeds the maximum  
peak current, the S8AS may be cut off due to unstable  
internal operation.  
Internal parts may occasionally be deteriorated or damaged. Do  
not use the Product in conditions exceeding the derating curve (in  
portion (1) of the Derating Curve on page 8).  
Use the Product where the relative humidity is 25% to 85%.  
Do not use the Product where it would be subjected to direct  
sunlight.  
Do not use the Product where it would be subjected to the  
possibility of penetration of liquid, foreign substance, or corrosive  
gas.  
To maintain performance of the maintenance forecast monitor,  
make sure the following conditions are satisfied for long-term  
storage. For storage exceeding three months, keep the Product at  
a temperature of 20°C to 30°C and a humidity of 25% to 70%.  
2. After the load device has been started, ensure that the total  
current in steady state remains within the rated values.  
3. When the peak current has exceeded the rated current, do  
not allow the peak current to flow again for the next 60  
seconds.  
Startup Sequence and Shutdown Sequence  
The sequencing functions are designed for the branch outputs of one  
S8AS. There is no synchronizing processing between S8AS when  
more than one S8AS is used.  
Startup Delay  
Output Voltage Adjustment  
The startup delay will not operate when a relay or other device is used  
for ON/OFF control on the output side of the S8AS, so a cutoff  
operation may occasionally occur.  
The output voltage adjuster (V.ADJ.) may possibly become  
damaged. Do not apply more than the required force.  
Do not exceed the rated output capacity and rated total output  
current after adjusting the output voltage.  
Dielectric Strength Test  
The S8AS is designed to withstand 3,000 VAC for 1 minute  
between the AC input terminals collectively and the branch output,  
I/O signal, or communications terminals collectively. When testing,  
set the cutoff current for the withstand voltage test device to 20 mA.  
The S8AS may possibly be damaged from the impulse voltage if a  
testing device switch is used to abruptly apply or cut off 3000 VAC.  
Increase the applied voltage gradually using the voltage  
adjustment on the testing device.  
Periodic Inspections  
Under normal operating conditions, the Product will require several  
years or even more than ten years until the maintenance forecast  
monitor function operates. When using the Product for an extended  
period of time, perform the following procedure periodically to confirm  
that the output for the maintenance forecast monitor function (LFE) is  
operating correctly.  
a) Change to Run Mode.  
When testing terminals together, always short the specified  
terminals so that the voltage is applied to all of the terminals at the  
same time.  
b) Confirm that the (LFE) output is ON (i.e., that there is electrical  
continuity between (LEF) and (COM)).  
Precautions for Correct Use  
Tripping Performance  
When the tripping alarm output operates, always remove the cause  
of the output first and then reset the alarm.  
When using a load with a fixed-power operation, the S8AS may  
cause a cutoff when the power supply is turned OFF.  
Outputs may be cut off by the abnormal voltage protection with  
loads that generate reverse peak electromotive force.  
Tripping performance is depends on the ambient operating  
temperature. Use the Product within the derating range. Refer to  
the Derating Curve on page 8.  
It is conceivable that internal parts may be deteriorated or  
damaged. Do not repeatedly perform cutoff or recovery operations  
more than necessary.  
24  
S8AS  
Insulation Resistance Test  
Prohibition of Parallel Connection  
Do not connect branch outputs from the S8AS in parallel. Also, do not  
connect the branch outputs in parallel with branch outputs of other  
S8AS Power Supplies.  
When testing the insulation resistance, use a DC resistance meter  
at 500 VDC.  
To prevent damage, always short branch output terminals (+/), all  
I/O terminals, and communications terminals before testing.  
S8AS  
S8AS  
Output Voltage Adjustment  
If the output voltage is set to less than 20 V (default setting), the  
undervoltage alarm may be activated.  
Do not exceed the rated output capacity and rated total output  
current after adjusting the output voltage.  
The output voltage may increase beyond the allowable voltage  
range rated voltage +10% when the V.ADJ adjuster is used. When  
adjusting the output voltage, check the output voltage of the power  
supply to make sure that the load is not damaged.  
S8AS  
Connections cannot be made in parallel  
with other branch output circuits.  
Displaying the Output Voltage  
The voltage detection is performed on the voltage after AC/DC  
conversion in the interval circuits. The displayed voltage will be  
somewhat different from the value at the output terminals of the power  
source due to internal voltage drop. To confirm correct output  
voltages, measure the voltages at the branch output terminals.  
Connecting Backup Devices  
Do not connect a battery or other backup power supply to the output  
of the Product.  
Harmonic Current Suppression Circuit  
A harmonic current suppression circuit is built into the Power Supply.  
This circuit can create noise when the input is turned ON, but it will  
last only until the internal circuits stabilize and does not indicate any  
problem in the Product.  
No Output Voltage  
The internal circuit's overcurrent protection or overvoltage protection  
may operate. Alternatively, the latch protection circuit may operate if  
there is a lightning inrush or other large voltage applied to the input.  
Contact your OMRON representative if there is still no output voltage  
after checking the following two points:  
Checking Overcurrent Protection  
Check whether the load is in an overcurrent or short-circuited state.  
Remove the wires to the load before checking.  
Checking Overvoltage Protection and Latching Protection  
Turn the power supply OFF and leave it OFF for at least 3 minutes,  
then turn it ON again.  
Startup Time  
At startup, the S8AS will check hardware and software before starting  
the operation of branch outputs. A time of approximately 3 seconds is  
required for these self-diagnostic functions. Take this time into  
account when designing the system.  
External Tripping Input  
Wire the polarity of the external tripping input correctly.  
After completing wiring, confirm that operation is correct.  
Tripping Alarm Output,  
Undervoltage Detection Output, Maintenance  
Forecast Monitor Output,  
and Over-temperature Output  
Photoswitch outputs: 30 VDC max., 50 mA max., residual voltage  
when ON: 2 V max., leakage current when OFF: 0.1 mA max.  
Wire all output signal circuits correctly.  
Internal current control circuits are not provided internally for output  
signals. Do not allow the output current to exceed 50 mA.  
After completing wiring, confirm that the circuits operate correctly.  
25  
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)  
from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS  
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT  
LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the products.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,  
safety equipment, and installations subject to separate industry or government regulations.  
·
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or  
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the  
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
2010.6  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2010 All Right Reserved.  

相关型号:

S8AS-48008R

Smart Power Supply
OMRON

S8A_08

8 Amp Silicon Rectifier 50 to 1000 Volts
MCC

S8B

8 Amp Silicon Rectifier 50 to 1000 Volts
MCC

S8B

8.0A patch rectifier diode 100V SMC series
SUNMATE

S8B-EH

Disconnectable Crimp style connectors
ETC

S8B-PH-KL

2.0mm pitch/Disconnectable Insulation displacement and Crimp style connectors
JST

S8B-PH-KLC-H

2.0mm pitch/Disconnectable Insulation displacement and Crimp style connectors
JST

S8B-PH-SM4-TB

2.0mm pitch/Disconnectable Insulation displacement and Crimp style connectors
JST

S8B-PH-SM4C-TB

2.0mm pitch/Disconnectable Insulation displacement and Crimp style connectors
JST

S8B-TP

Rectifier Diode, 1 Phase, 1 Element, 8A, 100V V(RRM), Silicon, DO-214AB, ROHS COMPLIANT, PLASTIC, HSMC, 2 PIN
MCC

S8B-XH-A

2.5mm pitch/Disconnectable Crimp style connectors
ETC

S8B-XH-A-1

2.5mm pitch/Disconnectable Crimp style connectors
ETC