S8JX-G03512C [OMRON]
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W; 输出电压的变化多种多样: 48 V 15至150瓦,以及5或12 V为150瓦型号: | S8JX-G03512C |
厂家: | OMRON ELECTRONICS LLC |
描述: | Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W |
文件: | 总28页 (文件大小:2335K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
New Product
Switch Mode Power Supply
S8JX (15/35/50/100/150/300/600-W Models)
Wide Variety of Output Voltage
Variations: 48 V for 15 to 150 W,
and 5 or 12 V for 150 W
• Easy Mounting:
Mounting Bracket provided as a standard feature.
(except for DIN Rail-mounting models)
Mounts to DIN Rail. (except 600-W model)
Screw-mount at the top. (except 300-/600-W models)
• Safety standards:
UL 508/60950-1
cUL CSA C22.2 No. 107.1
cUR CSA C22.2 No. 60950-1
EN 50178 (= VDE 0160)
EN 60950-1 (= VDE 0805 Teil 1)
• EMC: Conforms to EN 61204-3 Class A.
EMI: EN55011
(
)
EMS: EN61000-4
• Input conditions:
The input voltage range of 15-W, 35-W,
50-W, 100-W, and 150-W models has been
increased to 80 to 370 VDC (EC Directives
and safety standards do not apply.).
Note: Refer to Safety Precautions on page 24.
Model Number Structure
Model Number Legend
Note: 1. Not all combinations are possible. Refer to List of Models in Ordering Information on page 2.
2. Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for
details.
15-/35-/50-/100-/150-W Models
3. Configuration (15/35/50/100/150 W model)
S8JX-G@@@@@@@
None: Open-frame
C: Covered
4. Configuration/mounting
None: Front-mounting
D: DIN Rail-mounting
1
2
3 4
1. Power Ratings
015: 15 W
035: 35 W
050: 50 W
100: 100 W
150: 150 W
2. Output Voltage
05: 5 V
12: 12 V
15: 15 V
24: 24 V
48: 48 V
300-/600-W Models
2. Output Voltage
S8JX-G@@@@@@
24: 24 V
3. Configuration/mounting (covered type)
C: Front-mounting
1
2
3
1. Power Ratings
300: 300 W
600: 600 W
CD: DIN Rail-mounting
Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for
details.
1
S8JX
Ordering Information
List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
Configuration
Input voltage
Power ratings Output voltage (VDC)
Output current
3 A
Model
S8JX-G01505
S8JX-G01512
S8JX-G01515
S8JX-G01524
S8JX-G01548
S8JX-G03505
S8JX-G03512
S8JX-G03515
S8JX-G03524
S8JX-G03548
S8JX-G05005
S8JX-G05012
S8JX-G05024
S8JX-G05048
S8JX-G10005
S8JX-G10012
S8JX-G10024
S8JX-G10048
S8JX-G15005
S8JX-G15012
S8JX-G15024
S8JX-G15048
S8JX-G01505D
S8JX-G01512D
S8JX-G01515D
S8JX-G01524D
S8JX-G01548D
S8JX-G03505D
S8JX-G03512D
S8JX-G03515D
S8JX-G03524D
S8JX-G03548D
S8JX-G05005D
S8JX-G05012D
S8JX-G05024D
S8JX-G05048D
S8JX-G10005D
S8JX-G10012D
S8JX-G10024D
S8JX-G10048D
S8JX-G15005D
S8JX-G15012D
S8JX-G15024D
S8JX-G15048D
5 V
12 V
1.3 A
1 A
15 W
35 W
15 V
24 V
48 V
5 V
0.65 A
0.35 A
7 A
12 V
15 V
24 V
48 V
5 V
3 A
2.4 A
1.5 A
0.75 A
10 A
Front-mounting *1
12 V
24 V
48 V
5 V
4.2 A
2.1 A
1.1 A
20 A
50 W
100 W
150 W
12 V
24 V
48 V
5 V
8.5 A
4.5 A
2.1 A
30 A
100 to 240 VAC
(free)
12 V
24 V
48 V
5 V
13 A
6.5 A
3.3 A
3 A
(80 to 370 VDC *3)
S8JX-G15005@:
Switchable between
100 to 120 VAC and
200 to 240 VAC. (DC
power cannot be
input.)
Open-frame Power
Supplies
12 V
15 V
24 V
48 V
5 V
1.3 A
1 A
15 W
35 W
0.65 A
0.35 A
7 A
12 V
15 V
24 V
48 V
5 V
3 A
2.4 A
1.5 A
0.75 A
10 A
DIN Rail-mounting *2
12 V
24 V
48 V
5 V
4.2 A
2.1 A
1.1 A
20 A
50 W
100 W
150 W
12 V
24 V
48 V
5 V
8.5 A
4.5 A
2.1 A
30 A
12 V
24 V
48 V
13 A
6.5 A
3.3 A
*1. The front-mounting bracket is included as standard with the product.
*2. A front-mounting bracket is not included with the product.
*3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
2
S8JX
Configuration
Input voltage
Power ratings Output voltage (VDC)
Output current
3 A
Model
5 V
S8JX-G01505C
S8JX-G01512C
S8JX-G01515C
S8JX-G01524C
S8JX-G01548C
S8JX-G03505C
S8JX-G03512C
S8JX-G03515C
S8JX-G03524C
S8JX-G03548C
S8JX-G05005C
S8JX-G05012C
S8JX-G05024C
S8JX-G05048C
S8JX-G10005C
S8JX-G10012C
S8JX-G10024C
S8JX-G10048C
S8JX-G15005C
S8JX-G15012C
S8JX-G15024C
S8JX-G15048C
S8JX-G01505CD
S8JX-G01512CD
S8JX-G01515CD
S8JX-G01524CD
S8JX-G01548CD
S8JX-G03505CD
S8JX-G03512CD
S8JX-G03515CD
S8JX-G03524CD
S8JX-G03548CD
S8JX-G05005CD
S8JX-G05012CD
S8JX-G05024CD
S8JX-G05048CD
S8JX-G10005CD
S8JX-G10012CD
S8JX-G10024CD
S8JX-G10048CD
S8JX-G15005CD
S8JX-G15012CD
S8JX-G15024CD
S8JX-G15048CD
S8JX-G30024C
S8JX-G60024C
S8JX-G30024CD
12 V
1.3 A
1 A
15 W
35 W
15 V
24 V
48 V
5 V
0.65 A
0.35 A
7 A
12 V
15 V
24 V
48 V
5 V
3 A
2.4 A
1.5 A
0.75 A
10 A
Front-mounting *1
12 V
24 V
48 V
5 V
4.2 A
2.1 A
1.1 A
20 A
50 W
100 W
150 W
12 V
24 V
48 V
5 V
8.5 A
4.5 A
2.1 A
30 A
100 to 240 VAC
(free)
12 V
24 V
48 V
5 V
13 A
6.5 A
3.3 A
3 A
(80 to 370 VDC *3)
S8JX-G15005@@:
Switchable between
100 to 120 VAC and
200 to 240 VAC. (DC
power cannot be
input.)
Covered Power
Supplies
12 V
15 V
24 V
48 V
5 V
1.3 A
1 A
15 W
35 W
0.65 A
0.35 A
7 A
12 V
15 V
24 V
48 V
5 V
3 A
2.4 A
1.5 A
0.75 A
10 A
DIN Rail-mounting *2
12 V
24 V
48 V
5 V
4.2 A
2.1 A
1.1 A
20 A
50 W
100 W
150 W
12 V
24 V
48 V
5 V
8.5 A
4.5 A
2.1 A
30 A
12 V
24 V
48 V
13 A
6.5 A
3.3 A
14 A
300 W
600 W
300 W
100 to 120 VAC
200 to 240 VAC
(Swichable)
Front-mounting *1
24 V
27 A
DIN Rail-mounting *2
14 A
*1. The front-mounting bracket is included as standard with the product.
*2. A front-mounting bracket is not included with the product.
*3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
3
S8JX
Ratings, Characteristics, and Functions
Input specification
100 to 240 V input
Item
Power ratings *1
15 W
35 W
Efficiency
68% min.
73% min.
100 to 240 VAC (allowable range: 85 to 264 VAC)
Voltage *2
80 to 370 VDC *9
Note: This range is not applicable for the safety standards.
Frequency *2
Current *3
50/60 Hz (47 to 450 Hz)
100 V input
200 V input
0.4 A max.
1 A max.
0.25 A max.
0.6 A max.
Power factor
---
---
Input
Harmonic current emissions
100 V input
0.5 mA max.
1 mA max.
20 A max.
40 A max.
Yes
Leakage current *3
200 V input
100 V input
200 V input
Inrush current (for a
cold start at 25°C) *3
Noise filter
Voltage adjustment range *5
Ripple *3
−10% to 15% (with V. ADJ) (48-V models: 10%)
2% (p-p) max.
Input variation influence
0.4% max. with AC input voltage
Output *4 Load variation influence
Temperature variation influence
Startup time
0.8% max. (0 to 100% load, rated input voltage)
0.05%/°C max. (at rated input and output)
500 ms max. (up to 90% of output voltage at rated input and output)
Hold time *3
20 ms min.
Overload protection *6
Overvoltage protection *7
105% to 175% of rated load current, voltage drop, intermittent, automatic reset
Yes
Overheat protection
No
Additional
functions
Parallel operation
No
Series operation
Yes (For up to two Power Supplies; external diodes required.)
No
Protective circuit operation indicator
Refer to the derating curve in Engineering Data on page 13 (with no icing or
condensation).
Ambient operating temperature
Storage temperature
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in X, Y, Z directions
Yes (Color: Green)
Conducted Emissions
Radiated Emissions
Electrostatic Discharge
Conforms to EN 55011 Group 1 Class A and based on FCC Class A
Conforms to EN 55011 Group 1 Class A
EMI
Other
Confirms to EN61000-4-2
Radiated Electromagnetic Field Confirms to EN61000-4-3
Electrical Fast Transient/Burst
Surge
Confirms to EN61000-4-4
Confirms to EN61000-4-5
Confirms to EN61000-4-6
EMS
Conducted Disturbance
Voltage Dips/Short Interruptions Confirms to EN61000-4-11
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
Approved standards *9
EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI
SEMI F47-0200 (200-VAC input)
250 g max.
Weight *8
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 15.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 15.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is a for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
4
S8JX
Input specification
100 to 240 V input
Item
Power ratings *1
50 W
100 W
Efficiency
76% min.
100 to 240 VAC (allowable range: 85 to 264 VAC)
Voltage *2
80 to 370 VDC *9
Note: This range is not applicable for the safety standards.
Frequency *2
Current *3
50/60 Hz (47 to 450 Hz)
100 V input
200 V input
1.4 A max.
0.8 A max.
2.5 A max.
1.5 A max.
Power factor
---
---
Input
Harmonic current emissions
100 V input
0.5 mA max.
1 mA max.
20 A max.
40 A max.
Yes
Leakage current *3
200 V input
100 V input
200 V input
Inrush current (for a
cold start at 25°C) *3
Noise filter
Voltage adjustment range *5
Ripple *3
−10% to 15% (with V. ADJ) (48-V models: 10%)
2% (p-p) max.
Input variation influence
0.4% max. (with AC input voltage)
0.8% max. (0 to 100% load, rated input voltage)
0.05%/°C max. (at rated input and output)
Output *4 Load variation influence
Temperature variation influence
Startup time
500 ms max. (up to 90% of output voltage at rated input and output)
Hold time *3
20 ms min.
Overload protection *6
Overvoltage protection *7
105% to 175% of rated load current, voltage drop, intermittent, automatic reset
Yes
Overheat protection
No
Additional
functions
Parallel operation
No
Series operation
Yes (For up to two Power Supplies; external diodes required.)
No
Protective circuit operation indicator
Refer to the derating curve in Engineering Data on page 13 (with no icing or
condensation).
Ambient operating temperature
Storage temperature
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in X, Y, Z directions
Yes (Color: Green)
Conducted Emissions
Radiated Emissions
Electrostatic Discharge
Conforms to EN 55011 Group 1 Class A and based on FCC Class A
Conforms to EN 55011 Group 1 Class A
EMI
Other
Confirms to EN61000-4-2
Radiated Electromagnetic Field Confirms to EN61000-4-3
Electrical Fast Transient/Burst
Surge
Confirms to EN61000-4-4
Confirms to EN61000-4-5
Confirms to EN61000-4-6
EMS
Conducted Disturbance
Voltage Dips/Short Interruptions Confirms to EN61000-4-11
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
Approved standards *9
EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI
SEMI F47-0200 (200-VAC input)
Weight *8
300 g max.
550 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 15.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 15.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is a for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
5
S8JX
Input specification
100/200 V switchable
150 W at 5 V
100 to 240 V input
150 W at 12 V 150 W at 24 or 48 V
79% min. 85% min.
Item
Power ratings *1
Efficiency
78% min.
Switchable between 100 to 100 to 240 VAC (allowable range: 85 to 264 VAC)
120 VAC (allowable range:
Voltage *2
85 to 132 VAC) and 200 to
240 VAC (allowable range:
80 to 370 VDC *9
170 to 264 VAC).
Frequency *2
Current *3
50/60 Hz (47 to 450 Hz)
100 V input
200 V input
3.5 A max.
2.1 A max.
---
3.6 A max.
2.2 A max.
3.5 A max.
2.1 A max.
Input
Power factor
Harmonic current emissions
---
100 V input
0.5 mA max.
1 mA max.
20 A max.
40 A max.
Yes
Leakage current *3
200 V input
100 V input
200 V input
Inrush current (for a
cold start at 25°C) *3
Noise filter
Voltage adjustment range *5
Ripple *3
−10% to 15% (with V. ADJ) (48-V models: 10%)
2% (p-p) max.
Input variation influence
0.4% max. (with AC input voltage)
0.8% max. (0 to 100% load, rated input voltage)
0.05%/°C max. (at rated input and output)
500 ms max. (up to 90% of output voltage at rated input and output)
20 ms min.
Output *4 Load variation influence
Temperature variation influence
Startup time
Hold time *3
105% to 175% of rated load
105% to 175% of rated load current, voltage drop,
current, voltage drop,
Overload protection *6
intermittent, automatic reset
automatic reset
Overvoltage protection *7
Overheat protection
Yes
Additional
functions
No
Parallel operation
No
Series operation
Yes (For up to two Power Supplies; external diodes required.)
No
Protective circuit operation indicator
Refer to the derating curve in Engineering Data on page 13 (with no icing or
condensation).
Ambient operating temperature
Storage temperature
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in X, Y, Z directions
Yes (Color: Green)
Conducted Emissions
Radiated Emissions
Electrostatic Discharge
Conforms to EN 55011 Group 1 Class A and based on FCC Class A
Conforms to EN 55011 Group 1 Class A
EMI
Other
Confirms to EN61000-4-2
Radiated Electromagnetic Field Confirms to EN61000-4-3
Electrical Fast Transient/Burst
Surge
Confirms to EN61000-4-4
Confirms to EN61000-4-5
Confirms to EN61000-4-6
EMS
Conducted Disturbance
Voltage Dips/Short Interruptions Confirms to EN61000-4-11
UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
Approved standards *9
EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI
---
SEMI F47-0200 (200-VAC input)
700 g max. 600 g max.
Weight *8
800 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 15.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 15.
*7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON.
*8. The weight indicated is a for Front-mounting, Open-frame Power Supply.
*9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
6
S8JX
Input specification
100/200 V (Selected)
Item
Power ratings *1
300 W
600 W
Efficiency
82% min.
80% min.
100 to 120 VAC (allowable range: 85 to 132 VAC)
200 to 240 VAC (allowable range: 170 to 264 VAC)
(Switchable)
Voltage *2
Frequency *2
Current *3
50/60 Hz (47 to 450 Hz)
100 V input
200 V input
8 A max.
14 A max.
8 A max.
---
---
4.5 A max.
Power factor
Input
Harmonic current emissions
100 V input
0.5 mA max.
1 mA max.
Leakage current *3
200 V input
100 V input
200 V input
25 A max.
30 A max.
60 A max.
Inrush current (for a
cold start at 25°C) *3
50 A max.
Noise filter
Yes
Voltage adjustment range *5
Ripple *3
−10% to 15% (with V. ADJ)
2% (p-p) max.
0.4% max.
Input variation influence
Output *4 Load variation influence
Temperature variation influence
Startup time
0.8% max. (0 to 100% load, rated input voltage)
0.05%/°C max.
650 ms max.
20 ms min.
500 ms max.
Hold time *3
105% to 175% of rated load current, Inverted
L voltage drop, the circuit will be shut OFF
when the overload exceeds 5 s. *9
105% to 175% of rated load current,
voltage drop, intermittent, automatic reset
Overload protection *6
Overvoltage protection *7
Yes
Yes *9
Yes *9
Additional
functions
Overheat protection
No
Parallel operation
Yes (up to 5 units)
Series operation
Yes (For up to two Power Supplies; external diodes required.)
No Yes (color: red)
Protective circuit operation indicator
Ambient operating temperature
Storage temperature
Refer to the derating curve in Engineering Data on page 13 (with no icing or condensation).
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA)
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in X, Y, Z directions
Yes (Color: Green)
Conducted Emissions *3
Radiated Emissions
Electrostatic Discharge
Conforms to EN 55011 Group 1 Class A and based on FCC Class A
Conforms to EN 55011 Group 1 Class A
EMI
Other
Confirms to EN61000-4-2
Radiated Electromagnetic Field Confirms to EN61000-4-3
Electrical Fast Transient/Burst
Surge
Confirms to EN61000-4-4
Confirms to EN61000-4-5
Confirms to EN61000-4-6
EMS
Conducted Disturbance
Voltage Dips/Short Interruptions Confirms to EN61000-4-11
UL UR: UL 508 (Recognition), UL UR: UL 60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
Approved standards *10
EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI
SEMI F47-0200 (200-VAC input)
Weight *8
1,600 g max.
2,500 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 15.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 15.
*7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*8. The weight indicated is a for Front-mounting, Open-frame Power Supply.
*9. The protection-ON alarm indicator will light as soon as the output is interrupted. For resetting, turn OFF the input power, leave for more than
three minutes , and then turn it back ON again.
*10.The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
7
S8JX
Connections
Block Diagrams
S8JX-G01505@@ (15 W)
S8JX-G01512@@ (15 W)
S8JX-G01515@@ (15 W)
S8JX-G01524@@ (15 W)
AC (L)
INPUT
+V
DC OUTPUT
−V
Fuse
2.0 A
Noise
filter
AC (N)
Rectifier/
Smoothing circuit
Inrush current
protection
Rectifier
Smoothing
circuit
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overvoltage
detection circuit
Photocoupler
S8JX-G01548@@ (15 W)
AC (L)
INPUT
+V
DC OUTPUT
−V
Fuse:
2.0 A
Noise
filter
AC (N)
Inrush current
protection
Rectifier
Smoothing
circuit
Rectifier/
smoothing circuit
Drive control
circuit
Overcurrent
detection
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Photocoupler
S8JX-G03505@@ (35 W)
S8JX-G03512@@ (35 W)
S8JX-G03515@@ (35 W)
S8JX-G03524@@ (35 W)
AC (L)
INPUT
+V
DC OUTPUT
−V
Fuse
3.15 A
Noise
filter
AC (N)
Rectifier/
Smoothing circuit
Inrush current
protection
Rectifier
Smoothing
circuit
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overvoltage
detection circuit
Photocoupler
S8JX-G03548@@ (35 W)
AC (L)
INPUT
+V
DC OUTPUT
−V
Fuse:
3.15 A
Noise
filter
AC (N)
Rectifier
Inrush current
protection
Smoothing
circuit
Rectifier/
smoothing circuit
Drive control
circuit
Overcurrent
detection
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Photocoupler
8
S8JX
S8JX-G05005@@ (50 W)
S8JX-G05012@@ (50 W)
S8JX-G05024@@ (50 W)
AC (L)
INPUT
+V
DC OUTPUT
−V
Fuse
6.3 A
Noise
filter
AC (N)
Rectifier/
Smoothing circuit
Inrush current
protection
Rectifier
Smoothing
circuit
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overvoltage
detection circuit
Photocoupler
S8JX-G05048@@ (50 W)
AC (Lꢀ
+V
DC OUTPUT
−V
Fuse:
6.3 A
Noise
filter
INPUT
AC (N)
Inrush current
protection
Rectifier
Smoothing
circuit
Rectifier/
smoothing circuit
Drive control
circuit
Overcurrent
detection
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Photocoupler
S8JX-G100@@@@ (100 W)
AC (L)
INPUT
AC (N)
+V
DC OUTPUT
−V
Fuse
8 A
Noise
filter
Smoothing
circuit
Inrush current
protection
Rectifier
Rectifier/
Smoothing circuit
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overvoltage
detection circuit
Photocoupler
9
S8JX
S8JX-G15005@@ (150 W)
Rectifier/
smoothing circuit
AC (L)
INPUT
㧗V
DC OUTPUT
㧙V
Fuse:
8 A
Noise
filter
AC (N)
Inrush current protection
Rectifier/
smoothing circuit
Drive control
circuit
Overcurrent
detection
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Photocoupler
Input voltage switch
100/200 V switching
Note: Set the input voltage switch to "115V" for 100 to 120 VAC and to "230V" for 200 to 240 VAC.
S8JX-G15012@@ (150 W)
S8JX-G15024@@ (150 W)
S8JX-G15048@@ (150 W)
+V
AC (L)
INPUT
AC (N)
Fuse
10 A
Noise
filter
DC OUTPUT
−V
Smoothing
circuit
Inrush current
protection
Rectifier
Rectifier/
Smoothing circuit
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overvoltage
detection circuit
Photocoupler
10
S8JX
S8JX-G30024@@ (300 W)
Rectifier/
Smoothing circuit
+V
AC (L)
INPUT
AC (N)
Fuse
10 A
Noise
filter
DC OUTPUT
−V
Inrush current protection
Rectifier/
Smoothing circuit
100/200V (Selectable)
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overvoltage
detection circuit
Photocoupler
Parallel operation selector
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
Keep the terminals open if the input is 200 to 240 VAC.
S8JX-G60024@@ (600 W)
Rectifier/
Smoothing circuit
+V
AC (L)
INPUT
AC (N)
Fuse
10 A
Noise
filter
DC OUTPUT
−V
Inrush current protection
Rectifier/
Smoothing circuit
Fan
100/200V (Selectable)
Drive control
Circuit
Overcurrent
detection
circuit
Voltage
detection
Overheat
detection
circuit
Overvoltage
detection circuit
Photocoupler
Parallel operation selector
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC.
Keep the terminals open if the input is 200 to 240 VAC.
11
S8JX
Construction and Nomenclature
Nomenclature
15-/35-/50-/100-/150-W Models
No.
Name
DC Output
Terminals (−V), (+V)
Function
D
E
1
Connect the load lines to these terminals.
D
+V
E
A
AC Input Terminals
(L), (N)
+V
2
3
4
5
Connect the input lines to these terminals. *1
Connect the ground line to these terminals. *2
Use to adjust the voltage.
−V
A
−V
Protective Earth
C
B
C
B
Terminal (PE) (
)
AC (L)
AC (N)
AC (L)
AC (N)
Output Voltage
Adjuster (V. ADJ)
Output Indicator
(DC ON: Green)
Lights green while a direct current (DC) output is ON.
F
Switches the internal circuits according to the input
voltage.
"115V": 100 to 120 VAC
Bottom
6
Input voltage switch
"230V": 200 to 240 VAC
100 to 120 VAC
200 to 240 VAC
*1. The fuse is located on the (L) side. It is NOT user-replaceable. For a DC
power input, connect the low side to the positive (+) terminal.
*2. This is the protective earth terminal specified in the safety standards.
Always ground this terminal.
Note: The S8JX-G05024CD is
Note: The S8JX-G15005C is shown
shown above.
above.
300-W Model
600-W Model
A
FE G
E
F
AC (L)
B
−V −V +V +V
Side
+V
+V
−V
−V
A
AC (N)
D
C
H
Bottom
H
AC (L)
AC (N)
D
B
C
No.
1
Name
Function
DC Output Terminals (+V), (−V)
AC Input Terminals (L), (N)
Connect the load lines to these terminals.
Connect the input lines to these terminals. *1
Connect the ground line to these terminals. *2
2
3
Protective Earth Terminal (PE) (
Input Voltage Selector Terminals
Output Indicator (DC ON: Green)
Output Voltage Adjuster (V. ADJ)
)
4
Short-circuit the terminals if the input is 100 to 120 VAC and open the terminals if the input is 200 to 230 VAC.
Lights while a Direct Current (DC) output is ON.
5
6
It is possible to increase or decrease the output voltage.
Protection-ON Alarm Indicator
(DC ON: Red)
The red indicator will be lit if the overvoltage (for a 600-W model) or overheat protection (for a 600-W model)
circuit is triggered. This indicator will also be lit when overload (for a 600-W model) is detected.
7
8
Selector of Parallel Operation
Set the selector to PARALLEL if the Units are in parallel operation.
*1. The fuse is located on the (L) side. It is NOT user-replaceable.
*2. This is the protective earth terminal specified in the safety standards. Always ground this terminal.
Reference Values
S8JX-G15012@@ and S8JX-G15005@@
Other models
250,000 hrs
Reliability (MTBF)
Definition
240,000 hrs
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device
failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
Life expectancy
Definition
10 yrs. min.
The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load rate of 50%.
Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
12
S8JX
Engineering Data
Derating Curves (Standard Mounting)
15-/35-/50-/100-/150-W Models
Open-frame Power Supplies
Covered Power Supplies
120
120
100
80
100
80
A
A
60
60
40
40
20
0
20
0
−20 −10
0
10 20 30 40 50 60 70 80
−20 −10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
Ambient Temperature (°C)
Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the
area shown by shading Ain the above graph).
2. If there is a derating problem, use forced air-cooling.
3. For Customers Using a DC Input
When using an input voltage of less than 100 VDC, reduce the load calculated with the above derating curve by at least the following
coefficients.
35-W and 100-W (5-V or 12-V output) models: 0.8
50-W/150-W models:
15-W and 100-W (24-V or 48-V output):
0.85 (DC power cannot be input only to the S8JX-G15005@@.)
0.9
300-/600-W Models
Single Unit Operation
Parallel Operation
120
120
100
80
100
A
A
80
60
40
60
Front-mounting,
Bottom-mounting,
Solid line
40
DIN Rail mounting,
Side mounting (600W)
20
0
20
0
Dotted line
Side mounting (300W)
−20 −10
0
10 20 30 40 50 60 70 80
−20 −10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
Ambient Temperature (°C)
Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the
area shown by shading Ain the above graph).
2. If there is a derating problem, use forced air-cooling.
13
S8JX
Mounting
15-/35-/50-/100-/150-W Models
The following three mounting methods are possible.
A. Front-mounting: Refer to Mounting Bracket Provided with Front-mounting Power Supplies aon page 20.
B. Bottom-mounting
C. Side-mounting
Note: Additional mounting methods are also available using DIN Rail-mounting models.
B
C
Standard Mounting
15-/35-/50-/100-/150-W Models
Front-mounting
Bottom-mounting
Vertical Side-mounting
DIN Rail-mounting
Horizontal Side-mounting
*
*
*
*
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the
standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by
means of natural air flow.
300-W Model
Bottom-mounting
Side-mounting
Front-mounting
20mm min.
20mm min.
20mm min.
20mm min.
DIN Rail mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or
damage of internal parts. Use the standard mounting method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended.
3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply
is designed to radiate heat by means of natural air flow.
600-W Model
Front-mounting
Bottom-mounting
20mm min.
20mm min.
20mm min.
20mm min.
Side-mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally
result in deterioration or damage of internal parts. Use the standard mounting
method only.
2. When mounting the Power Supply, mounting it to a metal plate (*) is
recommended.
3. Install the Power Supply so that the air flow circulates around the Power
Supply, as the Power Supply is designed to radiate heat by means of natural
air flow.
14
S8JX
Overload Protection
The Power Supply is provided with an overload protection function that protects the power supply from possible damage by overcurrent. When the
output current rises above 105% to 175% min. of the rated current, the protection function is triggered, decreasing the output voltage. When the
output current falls within the rated range, the overload protection function is automatically cleared.
(Reference value)
15-/35-/50-/100-/150-W (12-/24-/48-V) Models
600-W Model
Intermittent operation
Output interrupted
0
50
100
Load rate (%)
0
50
100
Load rate (%)
If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously the protection-ON alarm indicator will be lit.
To reset the S8JX, turn OFF the power, leave the S8JX for at least
three minutes, and then turn it ON again.
150-W, 5-V Models
Note: 1. When a load is connected that has a built-in DC-DC
converter, the overload protection may operate at startup
and the power supply may not start.
2. Internal parts may occasionally deteriorate or be damaged
if a short-circuited or overcurrent state continues during
operation.
3. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush
current or overloading at the load end. Do not use the Power
Supply for such applications.
0
50
100
Load rate (%)
300-W Model
Intermittent operation
0
50
100
Load rate (%)
15
S8JX
Overvoltage Protection
15-/35-/50-/100-/150-W Models
Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback
circuit in the power supply fails. When an excessive voltage that is approximately 130% of the rated voltage or more is output, the output voltage
is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least seven minutes and then turning
it back ON again.
300-/600-W Models
Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback
circuit in the Power Supply fails. When an excessive voltage that is approximately 120% of the rated voltage or more is output, the output voltage
is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least three minute and then turning
it back ON again.
(Reference value)
Overvoltage protection
Operating
Rated output
Voltage
Variable range
0 V
Note: Do not turn ON the power again until the cause of the overvoltage has been removed.
Overheat Protection
600-W Model
If the internal temperature rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to shut
OFF the output voltage and simultaneously the protection-ON alarm indicator will be lit. Reset the input power by turning it OFF for at least three
minutes and then turning it back ON again.
Inrush Current, Startup Time, Output Hold Time
Input ON
Input OFF
AC input
voltage
Inrush current on input application
AC input
current
96.5%
90%
Output
voltage
Startup time
Hold time (20 ms min.)
Note: A maximum startup time of 500 ms is required (650 ms for 300 W). Construct a system configuration that considers the startup time of other
devices.
16
S8JX
Dimensions
(Unit: mm)
Front-mounting Models
S8JX-G015@@ (15 W)
S8JX-G015@@C (15 W)
S8JX-G035@@ (35 W)
S8JX-G035@@C (35 W)
5 max.
3.5
Panel mounting holes dimensions
1
10 max.
90
Label
Surface screw mounting
Two, M3
8.2
9.5
Side
Mounting
1
91
0.5
75
0.5
75
0.5
82
Five, M3.5
Cover
3.5 dia.
Two, M3
78
Bottom
Mounting
1
35.5
39.5
7.5
0.5
0.5
4.5
8.5
3.5 dia.
82
78
1
0.5
3.5
26.5
17.5
Two, M3 (Depth 4 mm max.)
0.5
50
15
S8JX-G050@@ (50 W)
S8JX-G050@@C (50 W)
5 max.
Panel mounting holes dimensions
1
100
10 max.
Label
Surface screw mounting
Two, M3
3.5
8.2
9.5
0.5
Side
75
0.5
75
Mounting
±1
92
0.5
92
Five, M3.5
Cover
3.5 dia.
Two, M3
Bottom
Mounting
8
0.5
0.5
92
92
4.5
1
1
36
40
0.5
92
4.5
3.5 dia.
3.5
Two, M3
(Depth 4 mm max.)
26.5
20
0.5
20
65
S8JX-G100@@ (100 W)
S8JX-G100@@C (100 W)
S8JX-G15024 (150 W)
S8JX-G15024C (150 W)
S8JX-G15048 (150 W)
1
150
150 W
10 max.
Panel mounting holes dimensions
5 max.
100 W
100·150 W
Surface screw mounting
Label
S8JX-G15048C (150 W)
Two, M3
3.5
8.2
9.5
Side
Mounting
0.5
75
0.5
75
1
92
Five, M3.5
Cover
0.5
141
3.5 dia.
Two, M3
8
0.5
141
141
5
5
Bottom
±1
48
Mounting
±1
50
0.5
141
0.5
Two, M3
(Depth 4 mm max.)
3.5
3.5 dia.
28
0.5
122
16
17
S8JX
S8JX-G15005 (150 W)
S8JX-G15005C (150 W)
Panel mounting holes dimensions
Surface screw mounting
178±1
5max.
12max.
2-M4
Label
10
Two, M3
3.5
13
Side
Mounting
8.2
9.5
68±0.5
92±1
68±0.5
169±0.5
Two, M3
3-M3.5
3.5 dia.
Cover
8
Bottom
Mounting
169±0.5
169±0.5
60±1
5
5
169±0.5
Two, M3
(Depth: 4 mm max.)
3.5
3.5 dia.
36
33.5
140±0.5
Input voltage switch
14
S8JX-G15012 (150 W)
S8JX-G15012C (150 W)
Panel mounting holes dimensions
Surface screw mounting
Two, M3
178±1
5max.
10max.
Label
8.2
9.5
3.5
Side
Mounting
68±0.5
92±1
68±0.5
169±0.5
Two, M3
3.5 dia.
5-M3.5
Cover
Bottom
Mounting
8
169±0.5
60±1
5
5
169±0.5
169±0.5
Two, M3
(Depth: 4 mm max.)
3.5
3.5 dia.
36
33.5
140±0.5
14
18
S8JX
S8JX-G30024C (300 W)
Eight, M4 holes
(depth: 8 max. on both sides)
20 max.
±1
4 max.
167.1
Nine, M4 terminal screws
Panel mounting holes dimensions
Surface screw mounting
Four, 4.5 dia.
10
Side
Mounting
8.6
±1
92
±0.5
50
±0.5
50
±0.5
136
21
Four, 4.5 dia.
±1
110
19
±0.5
136
Bottom
Mounting
±0.5
90
±0.5
136
±0.5
90
Four, M4 holes
(depth: 8 max.)
10
±0.5
19
136
S8JX-G60024C (600 W)
Eight, M4 holes
(depth: 8 max. on both sides)
±1
150
±0.5
24.4
8.6 10
Nine, M4 terminal screws
±1
159.8
±1
92
±0.5
50
20.9
±0.5
124
8.6 10
11
Panel mounting holes dimensions
Surface screw mounting
Four, 4.5 dia.
Four, M4 holes
(depth: 8 max.)
Side
Mounting
±0.5
50
±0.5
100
±0.5
124
Four, 4.5 dia.
Bottom
Mounting
±0.5
100
42
±0.5
137
±0.5
137
14.8
19
S8JX
Mounting Bracket Provided with Front-mounting Power Supplies a
15-/35-/50-/100-/150-W Models
S82Y-J00F Front-mounting
Bracket
Front-mounting Method
Note: Mounting screws are
Temporarily attach the enclosed mounting
bracket as shown in the illustration on the right,
hook the holes (parts a) in the Power Supply on
hooks on the mounting bracket (parts b), and
secure the Power Supply with two mounting
screws.
not provided.
Mounting
dimensions
Dimensions
1.5
0.2
4.6 15
11
b
9
Two, M3
a
60
Mounting bracket
Two, 3.5 dia.
Power Supply
74
60
4.6
b
20
11
20
31.5
5
4.7
15
20.5
a
t = 1.0
Material: Stainless steel
300-/600-W Models
Front-mounting Bracket (S82Y-J30F)
Attaching the Mounting Brackets
Dimensions with
10 dia.
Mounting Brackets
300-W Model
R2.5
300-W Model
30
15
7.5
7.5
±0.3
145
160
Two, 5 dia.
92
t = 1.6
±0.3
145
48
Note: To provide ventilation space, the body
will shift forward by 21.6 mm from the
mounting surface.
±0.2
32
Note: Mounting Brackets are provided in a set, one
for the right side and one for the left side.
±0.5
80
Four, M4
600-W Model
600-W Model
±0.3
145
Note: To provide ventilation space, the body
will shift forward by 23.6 mm from the
mounting surface.
±0.5
120
Four, M4
20
S8JX
DIN Rail-mounting Models
14.5 max.
S8JX-G015@@D (15 W)
1
1
90
10 max.
44
6 max.
S8JX-G015@@CD (15 W)
S8JX-G035@@D (35 W)
S8JX-G035@@CD (35 W)
Label
5 max.
8.2
9.5
1
91
Five, M3.5
Cover
47
98.6
7 (Sliding: 16.6 max.)
14.5 max.
S8JX-G050@@D (50 W)
S8JX-G050@@CD (50 W)
1
1
100
44
10 max.
6 max.
Label
5 max.
8.2
9.5
1
92
47
Five, M3.5
Cover
1
1
36
40
108.6
7 (Sliding: 16.6 max.)
S8JX-G100@@D (100 W)
S8JX-G100@@CD (100 W)
S8JX-G15024D (150 W)
S8JX-G15024CD (150 W)
S8JX-G15048D (150 W)
S8JX-G15048CD (150 W)
14.5 max.
1
150
150 W
10 max.
1
100 W
50
6 max.
Label
100·150 W
5 max.
8.2
9.5
1
92
Five, M3.5
Cover
47
1
158.6
48
7 (Sliding: 16.6 max.)
1
50
21
S8JX
14.5 max.
S8JX-G15005D (150 W)
S8JX-G15005CD (15 W)
6 max.
2-M4
60±1
178±1
5 max.
12 max.
Label
10
13
8.2
9.5
92±1
47
3-M3.5
Cover
7 (Sliding: 16.6 max.)
186.6
Input voltage switch
S8JX-G15012D (150 W)
S8JX-G15012CD (150 W)
14.5 max.
5 max.
6 max.
Label
60±1
178±1
10 max.
8.2
9.5
92±1
47
5-M3.5
Cover
7 (Sliding: 16.6 max.)
186.6
22
S8JX
S8JX-G30024CD (300 W)
(17.7)
Nine, M4 terminal screws
20 max.
4 max.
10.2
±1
167.1
10
8.6
±1
92
46.6
4.4 (Sliding: 10 max.)
4.6 max.
4.6 max.
±1
181.3
110
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
DIN Rail (Order Separately)
Mounting Rail
(Material: Aluminum)
0.15
7.3
4.5
Model
0.3
0.15
27
35
PFP-100N
PFP-50N
15 25
25
25
25
15 (5) *
1
10
10
1,000 (500) ∗
* Value in parentheses are for PFP-50N.
Mounting Rail
(Material: Aluminum)
16
4.5
0.3
35
27 24
29.2
1.5
Model
PFP-100N2
15 25
25
25
25 15
1
10
10
1,000
End Plate
10
6.2
1.8
M4 × 8
panhead
screw
1
35.5
35.5
50
1.8
Model
PFP-M
11.5
10
1.3
4.8
M4 spring
washer
Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
23
S8JX
Safety Precautions
Refer to Safety Precautions for All Power Supplies.
CAUTION
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or
15-/35-/50-/100-/150-W Models
repair the Product to touch the interior of the
Product.
Standard Mounting
(Front-mounting and DIN Rail-mounting)
Standard Mounting
(Bottom-mounting)
*1
*1
Minor burns may occasionally occur. Do not touch
the Product while power is being supplied or
immediately after power is turned OFF.
*1
Fire may occasionally occur. Tighten terminal screws
to the specified torque of 1.13 N·m.
For the 5-V output terminal, tighten the terminal
screw to 1.56 N·m.
*2
*3
*2
*1
Standard Mounting
(Horizontal Mounting)
*1
Minor injury due to electric shock may occasionally
occur. Do not touch the terminals while power is
being supplied. Always close the terminal cover after
wiring.
*1
*2
*3
300-W Model
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal
or conductors or any clippings or cuttings resulting
from installation work to enter the Product.
Standard Mounting
(Front-mounting and DIN Rail-mounting)
*1
Precautions for Safe Use
Mounting
• Take adequate measures to ensure proper heat dissipation to
increase the long-term reliability of the Product.
*2
*1
•
Be sure to allow convection in the atmosphere around devices when
mounting. Do not use in locations where the ambient temperature
exceeds the range of the derating curve. (except 600 W)
Standard Mounting
(Bottom-mounting)
*1
• The S8JX-@60024@ is designed to radiate heat by means of
forced air-flow. Do not cover the air holes (provided at fan mounted
side and the opposite side) to have enough air-cooling.
• The screws must not protrude beyond the following values inside
the Power Supply when screw holes provided on the chassis are
used.
15 W, 35 W, 50 W, 100 W, or 150 W: 4 mm min.
300 W or 600 W: 8 mm min.
Mounting screw tightening torque (recommended value) : 0.54 N·m.
*3
*2
• Rear mounting is possible using provided mounting bracket.
• When cutting out holes for mounting, make sure that cuttings do
not enter the interior of the Products.
600-W Model
• Improper mounting will interfere with heat dissipation and may
occasionally result in deterioration or damage of internal parts. Use
the standard mounting method only.
• The internal parts may occasionally deteriorate and be broken due
to adverse heat radiation. Do not loosen the screw on the side face
of the main body.
*1
*1
*3
• When mounting two or more Power Supplies side-by-side, allow at
least 20 mm spacing between them.
• Provide a space of at least 20 mm back and forth when mounting
300-W and 600-W models as well.
*1. Convection of air
*2. 20 mm max.
*3. Use a metal plate as the mounting surface.
• Use the metal plate as the mounting panel.
• Minor fire may occasionally occur. Set the input voltage switch to
the input voltage that is to be used (150-W, 5-V models only).
24
S8JX
Wiring
DIN Rail-mounting
• Connect the ground completely. A protective earthing terminal
stipulated in safety standards is used. Electric shock or malfunction
may occur if the ground is not connected completely.
• Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
• Do not apply more than 75 N force to the terminal block when
tightening it.
• Be sure to remove the sheet covering the Product for machining
before power-ON so that it does not interfere with heat dissipation.
• Use the following material for the wires to be connected to the
S8JX to prevent smoking or ignition caused by abnormal loads.
To mount the Power Supply to a DIN
Rail, pull down the rail stopper until
you hear it clicks open, hook portion
(A) of the Power Supply onto the DIN
Rail, press the Power Supply in
direction (B), and then push up the rail
stopper to lock the Power Supply in
place.
(A)
(B)
To dismount the Power Supply, pull
down portion (C) with a flat-blade
screwdriver and pull out the Power
Supply.
Recommended Wire Type
30 mm min.
(C)
Track stopper
AWG12 to AWG20 (a cross section of 0.517 to
15 W, 35 W
3.309 mm2)
UL-certified temperature of at least 75°C
Series Operation
Two power supplies can be connected in series. The ( ) voltage
output can be accomplished with two Power Supplies.
AWG12 to AWG16 (a cross section of 1.309 to
50W, 100W,
150 W (except
for 5 V)
3.309 mm2)
UL-certified temperature of at least 60°C or
60/75°C
Series Operation
Correct
Output Voltage ( )
Correct
AWG12 to AWG16 (a cross-section of 1.309
AC (L)
AC (N)
+V
AC (L)
AC (N)
+V
Input
side
to 3.309 mm2)
−V
−V
UL-certified temperature of at least 60°C or
60/75°C
150 W
at 5 V
AWG8 to AWG14 (a cross-section of 2.081 to
AC (L)
AC (N)
+V
AC (L)
AC (N)
+V
Output 8.368 mm2)
side
−V
−V
UL-certified temperature of at least 60°C or
60/75°C
Note: 1. If the load is short-circuited, a reverse voltage will be
generated inside the Power Supply. If this occurs the Power
Supply may possibly deteriorate or be damaged. Always
connect a diode as shown in the figure. Select a diode
having the following ratings.
AWG12 to AWG20 (a cross section of 0.517 to
3.309 mm2)
UL-certified temperature of at least 60°C or
60/75°C
300 W,
600 W
Installation Environment
Type
Schottky Barrier diode
• Do not use the Power Supply in locations subject to shocks or
vibrations. In particular, install the Power Supply as far away as
possible from contactors or other devices that are a vibration
source.
• Install the Power Supply well away from any sources of strong,
high-frequency noise and surge.
Dielectric strength (VRRM)
Forward current (IF)
Twice the rated output voltage or above
Twice the rated output current or above
2. Although Products having different specifications can be
connected in series, the current flowing through the load
must not exceed the smaller rated output current.
Parallel Operation
Ambient Operating and Storage Environments
• Store the Power Supply at a temperature of −25 to 65°C and a
humidity of 25% to 90%.
• The Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply outside the derating range (i.e., the
area shown by shading Ain the derating curve diagram on
page 13.)
• Use the Power Supply at a humidity of 25% to 85%.
• Do not use the Power Supply in locations subject to direct sunlight.
• Do not use locations where liquids, foreign matter, or corrosive
gases may enter the interior of the Product.
15-/35-/50-/100-/150-W Models
The Product is not designed for parallel operation.
Parallel Operation
Incorrect
AC (L)
+V
AC (N)
−V
AC (L)
+V
AC (N)
−V
Overload Protection
• Internal parts may possibly deteriorate or be damaged if a short-
circuited or overload state continues during operation.
• Internal parts may possibly deteriorate or be damaged if the Power
Supply is used for applications with frequent inrush current or
overloading at the load end. Do not use the Power Supply for such
applications.
300-/600-W Models
Parallel operation is possible under 80% of the rated value.
• To operate in parallel, set the switch to the "PARALLEL" side.
• The length and thickness of each wire connected to the load must
be the same so that there is no difference in voltage drop value
between the load and the output terminals of each Power Supply.
• It is desirable to set the same value on the voltage adjuster of each
Power Supply.
Charging a Battery
When connecting a battery at the load, connect an overcurrent
limiting circuit and overvoltage protection circuit.
Parallel Operation
Correct
AC (L)
+V
Output Voltage Adjuster (V.ADJ)
• The output voltage adjuster (V.ADJ) may possibly be damaged if it
is turned with unnecessary force. Do not turn the adjuster with
excessive force.
AC (N)
−V
• After completing output voltage adjustment, be sure that the output
capacity or output current does not exceed the rated output
capacity or rated output current.
AC (L)
+V
AC (N)
−V
25
S8JX
In Case There Is No Output Voltage
Fan Replacement
The possible cause for no output voltage may be that the overcurrent
or overvoltage protection has operated. The internal protection may
operate if a large amount of surge voltage such as a lightening surge
occurs while turning ON the Power Supply.
In case there is no output voltage, please check the following points
before contacting us:
600-W Model
The service life of the fan is approximately 50,000 hours (at 25°C).
The service life varies, however, depending on the ambient
temperature or other surrounding environmental conditions such as
dust. As a preventive maintenance measure, replace the fan within
approx. two years if it is used at an ambient temperature of 40°C.
Fans (S82Y-JXFAN) are available as replacements.
• Checking overcurrent protected status:
Check whether the load is in overcurrent status or is short-
circuited. Remove wires to load when checking.
• Checking overvoltage or internal protection:
Turn the power supply OFF once, and leave it OFF for at least
7 minutes. Then turn it ON again to see if this clears the condition.
Switching the AC Input Voltage between 100 and 200 VAC
150-W, 5-V Models
Fan Set:
Fan (above), instruction sheet, and packing case
The input voltage can be switched between 100 V and 200 V by using
the input voltage switch. Make the setting shown in the following
figure for the voltage that will be used. (The input voltage is factory-
set to 200 V.)
Replace the fan as shown in the following illustration.
"115V": 100 to 120 VAC
The input voltage switch is at the back
on the bottom of the Power Supply.
"230V": 200 to 240 VAC
300-/600-W Models
The input voltage can be switched between 100 and 200 V by shorting
or opening the input voltage selection terminals. Set the required
voltage as shown below. (The voltage is factory-set to 200 V.)
100-V input
200-V input
L
L
N
N
VOLTAGE SELECT
VOLTAGE SELECT
SHORT 100-120V
OPEN 200-230V
SHORT 100-120V
OPEN 200-230V
SHORT BAR
SHORT BAR
Short with the short bar.
Remove the short bar
and leave the terminals open.
Note: A 300-W model is shown above.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
26
Read and Understand this Catalog
Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have
any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year
(or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction
changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special
model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with
your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
OMRON Corporation
Tokyo, JAPAN
Industrial Automation Company
Authorized Distributor:
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
© OMRON Corporation 2009 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Printed in Japan
1110
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
CSM_9_1_0211
Cat. No. T041-E1-04
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
相关型号:
S8JX-G03512CD
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
OMRON
S8JX-G03515C
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
OMRON
S8JX-G03515CD
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
OMRON
S8JX-G03524C
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
OMRON
S8JX-G03524CD
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
OMRON
S8JX-G03548C
Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
OMRON
©2020 ICPDF网 联系我们和版权申明