S8VS-09024B [OMRON]

Switch mode Power Supply (Visible and Slim New Din Rail Power Supply); 开关模式电源(可见光和超薄新导轨式电源供应器)
S8VS-09024B
型号: S8VS-09024B
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Switch mode Power Supply (Visible and Slim New Din Rail Power Supply)
开关模式电源(可见光和超薄新导轨式电源供应器)

电源电路 开关
文件: 总24页 (文件大小:758K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
SSwi8tchVmoSde Power Supply  
Visible and Slim New Din Rail Power Supply  
Ultra-compact size (40 (W) × 95 (H) mm) (60-W Model)  
Displayed on 3-digit, 7-segment LED shows many status  
(voltage, current etc.) of power supply.  
Approved standards: UL508/60950, CSA C22.2 No.14/60950,  
EN50178 (=VDE0160), EN60950 (=VDE0806)  
Model Number Structure  
I Model Number Legend  
S8VS- @@@@@@  
1
2
3
1. Power Ratings  
060: 60 W  
090: 90 W  
2. Output voltage  
24: 24 V  
3. Configuration  
None: Standard Power Supply  
A:  
B:  
With maintenance forecast monitor  
With total run time monitor  
Ordering Information  
Power ratings  
60 W  
Type  
Output voltage  
24 V  
Output current  
2.5 A  
Model number  
S8VS-06024  
Standard type  
With maintenance forecast monitor type  
With total run time monitor type  
Standard type  
S8VS-06024A  
S8VS-06024B  
S8VS-09024  
S8VS-09024A  
S8VS-09024B  
90 W  
3.75 A  
With maintenance forecast monitor type  
With total run time monitor type  
Switch mode Power Supply S8VS  
L-55  
Specifications  
I Ratings/Characteristics  
Power ratings  
60 W  
90 W  
Type  
Standard  
Maintenance  
forecast monitor  
Total run time  
monitor  
Standard  
80ꢀ min.  
Maintenance  
forecast monitor  
Total run time  
monitor  
Item  
Efficiency (typical)  
78ꢀ min.  
Input  
Voltage  
Frequency  
Current  
100 to 240 VAC (85 to 264 VAC)  
50/60 Hz (47 to 450 Hz)  
100 V input 1.7 A  
200 V input 1.0 A  
2.3 A  
1.4 A  
Power factor correction  
Conforms to EN61000-3-2 A-14  
100 V input 0.5 mA max.  
200 V input 1.0 mA max.  
Leakage  
current  
Inrush current 100 V input 25 A max.  
(See note 1.)  
200 V input 50 A max.  
Output  
Voltage adjustment range  
Ripple  
Input variation influence  
Load variation influence  
(rated input voltage)  
10ꢀ to 15ꢀ (with V.ADJ)  
2.0ꢀ (p-p) max. (at rated input/output voltage)  
0.5ꢀ max. (at 85 to 264 VAC input, 100ꢀ load)  
1.5ꢀ max. (with rated input, 0 to 100ꢀ load)  
Temperature variation influence 0.05ꢀ/°C max.  
Start up time (See note 1.) 1,000 ms max.  
500 ms max.  
1,000 ms max.  
(at rated input/output voltage)  
500 ms max.  
(at rated input/output voltage)  
20 ms min. (at rated input/output voltage)  
Additional Overload protection (See note 1.) 105ꢀ to 160ꢀ of rated load current, inverted L drop, intermittent, automatic reset  
Hold time (See note 1.)  
function  
Overvoltage protection (See note 1.) Ye s  
Output voltage indication (See note 2.) No  
Output load indication (See note 2.) No  
Peak-hold load indication (See note 2.) No  
Maintenance forecast monitor No  
indication (See note 2.)  
Yes (selectable) (See note 3.)  
Yes (selectable) (See note 4.)  
Yes (selectable) (See note 5.)  
No  
No  
No  
No  
Yes (selectable) (See note 3.)  
Yes (selectable) (See note 4.)  
Yes (selectable) (See note 5.)  
Yes (select-  
able)  
No  
Yes  
No  
(selectable)  
Yes (open collector  
output), 30 VDC max.,  
50 mA max.  
Maintenance forecast  
monitor output  
No  
No  
Total run time monitor  
indication (See note 2.)  
Total run time monitor  
output  
No  
No  
Yes  
(selectable)  
No  
No  
Yes  
(selectable)  
Yes (open collector  
output), 30 VDC max.,  
50 mA max.  
Undervoltage alarm  
indication (See note 2.)  
No  
Yes (selectable)  
Yes (selectable)  
Undervoltage alarm output No  
terminals  
Yes (open collector output),  
30 VDC max., 50 mA max.  
Parallel operation  
Series operation  
No  
Yes (with external diode)  
Other  
Ambient temperature  
Ambient humidity  
Dielectric strength  
Operating: Refer to the derating curve in Engineering Data. (with no icing or condensation) Storage: 25 to 65°C  
Operating: 25ꢀ to 85ꢀ; Storage: 25ꢀ to 90ꢀ  
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)  
2.0 kVAC for 1 min. (between all inputs and GR terminals; detection current: 20 mA)  
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and GR terminals; detection current: 20 mA)  
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)  
100 Mmin. (between all outputs/ alarm outputs and all inputs/ GR terminals) at 500 VDC  
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions  
150 m/s2, 3 times each in X, Y, and Z directions  
Yes (color: green)  
Conforms to FCC Class A, EN50081-2  
Conforms to EN50081-2  
Insulation resistance  
Vibration resistance  
Shock resistance  
Output indicator  
Electromagnetic interference  
EMI  
Approved standards  
UL: UL508 (Listing; Class 2: Per UL1310), UL60950  
cUL: CSA C22.2 No.14, No.60950 (Class 2)  
UL: UL508 (Listing), UL60950  
cUL: CSA C22.2 No.14, No.60950  
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806) EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0806)  
Weight  
330 g max.  
490 g max.  
Note: 1. Refer to the Engineering Data section on page 59 for details.  
2. Displayed on 7-segment LED.  
3. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: 2ꢀ ( 1 digit for output voltage value)  
4. Resolution of output load indication: 0.1 A, Precision of output load indication: 5ꢀ ( 1 digit for output load value)  
5. Resolution of Peak-hold load indication: 0.1 A, Precision of Peak-hold load indication: 5ꢀ ( 1 digit for output load value), width of Peak-  
hold load indication: 10 ms  
L-56  
Switch mode Power Supply S8VS  
Connections  
I Block Diagram  
S8VS-06024 (60 W)  
S8VS-06024A (60 W)  
S8VS-06024B (60 W)  
(See note.)  
Display circuit  
Switch  
Arithmetic  
operation circuit  
Rectifier/smoothing circuit  
Fuse 3.15 A  
AC (L)  
+V  
DC OUTPUT  
V  
INPUT  
Noise filter  
AC (N)  
Rectifier/  
smoothing  
circuit  
Rectifier/smoothing circuit  
Inrush  
current  
protection  
circuit  
Drive control  
circuit  
Overcurrent  
circuit  
Current detection  
circuit  
Detection  
circuit  
Overvoltag  
detection circuit  
Photo coupler  
Note: The circuits within the dotted line are for the S8VS-06024@ Model only.  
S8VS-09024 (90 W)  
S8VS-09024A (90 W)  
S8VS-09024B (90 W)  
(See note.)  
Display circuit  
Switch  
Alarm  
DC LOW  
Arithmetic  
operation circuit  
Yrs  
Rectifier/smoothing circuit  
Common  
Photo coupler  
Fuse 4.0 A  
AC (L)  
+V  
INPUT  
DC OUTPUT  
Noise filter  
AC (N)  
V  
Rectifier/  
smoothing  
circuit  
Rectifier/smoothing circuit  
Inrush  
current  
protection  
circuit  
Drive control  
circuit  
Overcurrent  
circuit  
Current detection  
circuit  
Detection  
circuit  
Overvoltag  
detection circuit  
Photo coupler  
Note: The circuits within the dotted line are for the S8VS-09024@ Model only.  
Switch mode Power Supply S8VS  
L-57  
I Installation  
60-W Model  
S8VS-06024  
S8VS-06024@  
1
2
1
2
6
7
8
4
5
4
5
3
3
90-W Model  
S8VS-09024  
S8VS-09024@  
1
2
1
2
7
6
8
9
10  
4
5
4
5
11 13  
12  
3
3
No.  
1
Name  
AC Input terminals  
(L), (N)  
Ground terminals  
(GR)  
DC Output terminals Connect the load lines to these  
(V), (+V)  
Output indicator  
(DC ON: Green)  
Output voltage  
adjuster (V.ADJ)  
Function  
Connect the input lines to these  
terminals. (See note 1.)  
No.  
8
Name  
Mode Key (See note 2.)  
Function  
Use the Mode Key to change the  
indicated parameter or reset the  
peak hold current value.  
Use the Up Key to change to the  
setting mode or to increase the set  
value.  
Use the Down Key to change to  
the setting mode or to decrease  
the set value.  
2
3
4
5
6
7
Connect the ground line to this terminal.  
9
Up Key (See note 3.)  
terminals.  
10 Down Key (See note 3.)  
Lights while a direct current (DC) output  
is ON.  
Use to adjust the voltage.  
11 Alarm Undervoltage alarm Outputs when a drop in the  
output output terminal (DC output voltage is detected.  
terminal LOW) (See note 3.) (at voltage drop: OFF)  
Main display  
(See note 2.)  
Operation  
indicator  
Indicates the measurement or set value.  
12  
Maintenanceforecast Outputs when the maintenance  
monitorterminal(Yrs) forecast has reached the set  
(S8VS-09024A)  
Total run time monitor  
output terminal (Kh)  
(S8VS-09024B)  
V
Lights up when the output voltage is  
indicated. Blinks during setup of  
undervoltage alarm value.  
value.  
(See note 2.)  
A
Lights up during indication of output current.  
Apk Lights up during indication of peak hold current.  
Yrs Lights up during indication of maintenance  
forecast monitor. Blinks during setup of  
maintenance forecast monitor setting.  
(S8VS-0024A)  
(See note 3.)  
13  
Common terminal  
for alarm output  
(See note 3.)  
Terminal (emitter) shared for  
alarm outputs (11) and (12).  
Kh  
Lights up during indication of total run  
time monitor. Blinks during setup of total  
run time monitor. (S8VS-0@024B)  
Note: 1. The fuse is located on the (L) side.  
2. S8VS-@@@24@ only.  
3. S8VS-09024@ Model only.  
L-58  
Switch mode Power Supply S8VS  
Engineering Data  
I Derating Curve  
I Overvoltage Protection  
The Power Supply is provided with an overvoltage protection function  
that protects the load and the Power Supply from possible damage  
by overvoltage. When an excessive voltage is output, the output volt-  
age is shut OFF. Reset the Power Supply by turning it OFF for at  
least three minutes and then turning it back ON again.  
120  
100  
80  
60  
Overvoltage protection  
operating  
40  
+15%  
20  
0
Variable range  
Rated output  
voltage  
10%  
20 10  
0
10 20 30 40 50 60 70 80  
Ambient temperature (˚C)  
Installation  
0V  
Upper  
Upper  
Note: Do not turn ON the power again until the cause of the overvolt-  
age has been removed.  
I Inrush Current, Start Up Time,  
Hold Time  
Standard mounting  
Face-up mounting  
Input ON  
Input OFF  
Note: 1. Use standard mounting only. Using any other mounting  
method will prevent proper heat dissipation and may result  
in deterioration or damage of internal elements. Or, the re-  
maining service life notice function cannot work properly.  
AC input  
voltage  
2. If there is a derating problem, use forced air-cooling. The  
ambient temperature is specified for a point 50 mm below  
the power supply.  
Inrush current on input application  
AC input  
current  
I Overload Protection  
96.5%  
90%  
The Power Supply is provided with an overload protection function  
that protects the load and the power supply from possible damage by  
overcurrent. When the output current rises above 105ꢀ min. of the  
rated current, the protection function is triggered, decreasing the out-  
put voltage. When the output current falls within the rated range, the  
overload protection function is automatically cleared.  
Output  
voltage  
Start up time (1,000 ms max.)  
Hold time (20 ms min.)  
Intermittent operation  
0
50  
100  
Output current (%)  
Note: Do not allow the short-circuited or overcurrent state to continue  
for more than 20 s, otherwise internal elements may deteriorate  
or be destroyed.  
Switch mode Power Supply S8VS  
L-59  
I Undervoltage Alarm Function (Indication and Output)  
When output voltage drop is detected, an alarm (a01) and lowest  
output voltage value are indicated alternately. The preset value of  
AC input  
detection voltage can be changed in the setting mode.  
(S8VS-06024@: The value of detection voltage is fixed at 20V)  
Detection value  
of Undervoltage  
alarm  
Output  
voltage  
Further, the alarm is output from the transistor ((11) DC LOW) to an  
external device with the S8VS-09024A/B.  
(Upon output voltage alarm: OFF; with no continuity across (11) and  
Undervoltage  
output  
(13))  
:
Main display  
Operation  
mode  
Lowest value of  
output voltage  
Voltage indication  
In the case that the  
output voltage drops  
below the set value (19V)  
and an alarm is issued  
Note: Operation begins after about three seconds since the AC pow-  
er is supplied.  
Note: 1. Operation begins after about two seconds since the AC  
power is supplied.  
2. The alarm is not indicated in the setting mode.  
3. Press the  
((8) Mode Key) after the output voltage is re-  
stored, to reset alarm indication.  
4. The undervoltage alarm function monitors the output termi-  
nal voltage of the power supply unit. To check the voltage  
accurately, measure the voltage at the load end.  
Engineering Data (S8VS-@@@24@ Only)  
I Mode Change  
I Operation Mode  
Various states of the power supply unit are indicated.  
Power-ON  
Model indication  
Operation mode  
Output voltage  
Key Press and hold for  
Press and hold  
three seconds or more.  
Or no key operation for 30 seconds or more.  
Up or Down Key for  
three seconds or more.  
Setting mode  
Output current  
Note: No setting mode is provided for the S8VS-06024@.  
Peak hold current  
Maintenance forecast monitor  
(S8VS-@@@24A)  
or total run time monitor  
(S8VS-@@@24B)  
Note: The output voltage will be displayed when the power supply is  
first turned on after it is received from the factory. Thereafter,  
the output voltage will be indicated in the same display when  
shutting down.  
L-60  
Switch mode Power Supply S8VS  
I Setting Mode  
(Except for S8VS-06024@)  
Set various parameters of the power supply unit.  
I Total Run Time Monitor  
Indication and Alarm Output  
(S8VS-@@@24B)  
The cumulative running hours of the power supply unit are monitored  
as total run time. When the total run time reaches the predetermined  
alarm set value, an alarm (a02) and the total run time monitor are  
indicated alternately with an output issued from the transistor ((12)  
Kh) to an external device. (The output is turned off when the total run  
time reaches the alarm set value; with no continuity across (12) and  
(13).)  
*
Undervoltage  
18.5 to 20.0 to 27.5 (V)  
alarm  
0.1V intervals  
*
Maintenance  
0.0 to 0.5 to 5.0 (years)  
The alarm set value can be changed in the setting mode.  
forecast monitor  
0.5 year intervals  
(S8VS-09024A)  
or Total run time  
monitor alarm  
In the case that the total  
run time reaches the  
set value (88kh) and an  
alarm is issued  
*
1 to 50 to 150 (kh)  
(S8VS-09024B)  
1 kh intervals  
Note: 1. The total run time cannot be reset. To reset the alarm, in-  
crease the alarm set value beyond the value indicated as to-  
tal run time.  
* The reverse video indicates  
the shipment setting.  
Note: 1. Press and hold the (9) Up Key or (10) Down Key for two sec-  
Ex.) If a customer decided to change the load at 5,000  
hours, when they turn the unit again the timing will start at  
5,000 hours and on.  
onds or more to increase or decrease the value rapidly.  
2. The S8VS-06024@ is not provided with the setting mode  
and its parameters are fixed at the shipment setting.  
2. The alarm function (setting, indication, and output) is not  
provided for S8VS-06024B.  
I Peak Hold Current Reset  
Operation mode  
Key 3 seconds or more  
Reset  
2 seconds  
Peak hold current  
value measurement  
starts  
Note: The peak hold current value is not reset in the setting mode.  
I Self-Diagnostics Function  
(6) Main display  
Description  
Output state  
No change  
Restoration method  
Automatic restoration  
Setting after restoration  
Noise detected in voltage or current  
No change  
---  
Overheated  
(12) OFF  
Automatic restoration  
No change  
h%t  
Undervoltage alarm set value memory (11) OFF  
error  
Press and hold the (9) Up Key or (10)  
Shipment setting or  
e01  
Down Key for three seconds and check value set in the setting  
the set value of the corresponding point. mode again  
The set value must return to the  
Memory error of alarm set value of  
maintenance forecast monitor or total  
run time monitor  
(12) OFF  
e02  
shipment setting  
Other memory error  
(11) (12) OFF  
Turn the AC input off then on again.  
If the product is not reset, contact the  
dealer.  
No change  
e03  
Note: 1. External noise is probable as a cause of ---, e01, e02and e03errors.  
2. Operation out of the derating curve area, ventilation error, and incorrect mounting direction are probable as a cause of h%terror.  
3. If the h%terror state continues for about three hours, the maintenance forecast monitor function (S8VS-@@@24A only) becomes invalid.  
The indication for maintenance forecast monitor remains as h%teven after the overheat condition is removed, and the Yrs output (12)  
remains OFF (with no continuity across (12) and (13)).  
Replace the power supply if this condition occurs even if the output is correct, as internal parts may be deteriorated.  
4. The h%terror detection function is only for the S8VS-@@@24A.  
Switch mode Power Supply S8VS  
L-61  
I Undervoltage Alarm Indication  
This indicator lights when the output voltage is insufficient.  
I Maintenance Forecast  
Displays when the maintenance forecast has reached the set value.  
Operation  
Mode  
Operation  
Mode  
The maintenance forecast  
has reached the set value.  
Undervoltage occurs.  
Maintenance  
forecast  
monitor  
Undervoltage  
alarm  
*
*
Remaining time  
until replacement  
Output voltage lower limit  
* This indicator alternately  
displays alarm (  
and the output voltage  
lower limit.  
)
* This indicator alternately  
Output  
voltage  
Output  
current  
displays alarm (  
)
and the maintenance  
time until replacement.  
Peak-hold  
current  
Output  
current  
Maintenance  
forecast  
monitor  
Peak-hold  
current  
Note: The display changes to the output voltage display when the  
voltage is restored to the set value or higher.  
I Indication and Output  
When the product is purchased, fulwill be indicated. As electro-  
lytic capacitors deteriorate, indication changes to hlf. After the  
remaining time to maintenance is reduced to two years, indication  
automatically changes to a value, which decreases from 1.5to 1.0”  
to 0.5to 0(year) as the running hours increase.  
I Multiple Alarms  
When two or more different alarms occur at the same time  
Operation Mode  
If the maintenance forecast monitor setting is set to a value larger  
than two years, value indication automatically begins after the  
remaining time to maintenance is reduced to the set years.  
If the remaining time becomes smaller than setting L (which can be  
set arbitrarily between 0 and 5.0 years), an alarm (a02) and the  
remaining time are indicated alternately.  
Undervoltage  
alarm  
The indication shifts  
alternately in the direction  
of the arrow every 2 s.  
*
*
With the S8VS-09024A, an output is given to an external device from  
a transistor ((12) Yrs) to notify of the replacement timing, together  
with indication. (The output is turned off after the replacement timing  
is reached; with no continuity across (12) and (13).)  
Maintenance  
forecast monitor  
In the case that the  
remaining time is reduced  
to smaller than 0.5 year  
and an alarm is issued.  
* When undervoltage alarm is indicated: Press  
When the maintenance forecast monitor or overheat alarm is indicated:  
output load indication  
Press  
undervoltage alarm indication  
Note: 1. The remaining time to maintenance is based on continuous  
operation, not including the time when the power supply is  
turned off, and so may take longer to reach than the actual  
time indicated.  
2. Until the power supply has been turned for about one month  
in total, indication is fixed at fulto estimate the extent of  
deterioration, while the output remains turned on (with con-  
tinuity across (12) and (13)).  
L-62  
Switch mode Power Supply S8VS  
I Maintenance Forecast Monitor Function  
The power supply unit is equipped with electrolytic capacitors.  
The maintenance forecast monitor function shows an approximate  
period left for maintenance of the power supply unit due to deteriora-  
tion of electrolytic capacitors. When the period left for maintenance  
that the power supply forecasts reaches the set value, an alarm is  
indicated and an output signal is triggered.  
The electrolyte inside the electrolytic capacitor penetrates the seal-  
ing rubber and evaporates as time passes since it is manufactured,  
which causes deterioration of characteristics such as decreasing the  
capacitance, etc.  
Use this function to know the approximate replacement timing of the  
power supply unit.  
Due to this deterioration of the characteristics of the electrolytic  
capacitor, the power supply unit decreases its performance as time  
passes.  
Note: The maintenance forecast monitor function indicates an ap-  
proximate period left for maintenance, based on deterioration  
of the electrolytic capacitor. It does not predict failures caused  
by other reasons.  
Relationship Between Indicated Values and Output of Set Values  
L: Maintenance forecast set value  
(See note.) 0.0 to 5.0, 0.5 steps  
In case of setting L between 2.5 and 5 years.  
Initial capacity  
(L0.5)  
"1.0" is displayed on the main display for the  
duration that the maintenance forecast up to  
replacement satisfies the condition 1.0 T < 1.5.  
Capacity level  
at replacement  
5.0  
2.5  
2.0  
1.5  
1.0  
0.5  
0
Capacity of Capacitor  
Main display  
T: Maintenance time  
until replacement  
L=2.5  
Maintenance forecast monitor output  
L=0.5  
The numerical value  
decreases with time.  
Note: This function can be set only on the S8VS-09024A Model.  
I Principle of Operation  
I Reference Value  
The deterioration speed of the electrolytic capacitor varies consider-  
ably according to the ambient temperature. (Generally the speed fol-  
lows Rule of Two for every 10°C; for every 10°C increase in  
temperature the rate of degradation doubles according to Arrheniuss  
equation.) The S8VS-0@024A monitors the temperature inside the  
power supply, and calculates the amount of deterioration according  
to the running hours and inside temperature. Judging by this amount  
of deterioration, the power supply will give the alarm indication and  
output when the period left for maintenance reaches the set value.  
Item  
Value  
Definition  
Reliability 135,000 hrs MTBF stands for Mean Time Between  
(MTBF)  
min.  
Failures, which is calculated according to  
the probability of accidental device fail-  
ures, and indicates reliability of devices.  
Therefore, it does not necessarily repre-  
sent a life of the product.  
Life  
expectancy  
10 yrs. min. The life expectancy indicates average op-  
erating hours under the ambient tempera-  
ture of 40°C and a load rate of 50ꢀ.  
Normally this is determined by the life ex-  
pectancy of the built-in aluminum electro-  
lytic capacitor.  
Note: 1. Due to degradation of internal electronic parts, replace the  
power supply at least once every 15 years even if indication  
and output of maintenance forecast monitor are not issued.  
2. The maintenance forecast is accelerated or decelerated ac-  
cording to operating conditions. Periodically check indica-  
tion.  
Note: The maintenance forecastis the service life (the power sup-  
plys internal temperature is monitored at all times) of the inter-  
nal electrolytic capacitor in actual operating conditions, and  
varies according to the customers operating conditions. 15  
years is taken as the maximum period of the maintenance fore-  
cast.  
Switch mode Power Supply S8VS  
L-63  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
S8VS-06024 (60 W)  
S8VS-06024A (60 W)  
S8VS-06024B (60 W)  
Five, M4  
with square washer  
11.3  
97  
10  
35.4  
95  
74  
1
40  
Track stopper  
4.5  
(Sliding: 15 max.)  
108.3  
Note: The photo is the S8VS-06024A Model.  
S8VS-09024 (90 W)  
S8VS-09024A (90 W)  
S8VS-09024B (90 W)  
Five, M4  
with square washer  
10.8  
110.5  
10  
34.9  
94  
115  
1
50  
Track stopper  
4.5  
(Sliding: 15 max.)  
121.3  
Screwless block (2.5 mm pitches)  
Note: The photo is the S8VS-09024A Model.  
I DIN Track (Order Separately)  
Note: All units are in millimeters unless otherwise indicated.  
Mounting Track (Material: Aluminum)  
PFP-100N  
PFP-50N  
4.5  
0.15  
7.3  
0.3  
0.15  
27  
35  
15 25  
25  
25  
25  
15(5) *  
1
10  
10  
1,000 (500) *  
*Values in parentheses  
are for the PFP-50N.  
Mounting Track (Material: Aluminum)  
16  
4.5  
PFP-100N2  
0.3  
35  
27 24  
29.2  
1.5  
15 25  
25  
25  
25 15  
1
10  
10  
1,000  
L-64  
Switch mode Power Supply S8VS  
Precautions  
Operating and Storage Environments  
Do not use or store the Power Supply in the following locations.  
Doing so may result in failure, malfunction, or deterioration of perfor-  
mance characteristics.  
!Caution  
Do not disassemble the product or touch internal parts.  
Electric shock may be caused.  
Do not touch the product during power-on, and immediately after  
poweroff. Hot surface may cause heat injury.  
Do not use in locations subject to direct sunlight.  
Do not use in locations where the ambient temperature exceeds  
Tighten the terminal screw with torque 1.08 N·m.  
A loose screw may cause fire.  
the range of the derating curve.  
Do not use in locations where the humidity is outside the range  
25ꢀ to 85ꢀ, or locations subject to condensation due to sudden  
temperature changes.  
Do not store in locations where the ambient temperature is outside  
the range 25 to 65°C or where the humidity is outside the range  
25ꢀ to 90ꢀ.  
Install the terminal cover.  
Electric shock may be caused if not installed.  
Mounting  
Do not use locations where liquids, foreign matter, corrosive gases,  
or flammable gases may enter the interior of products.  
Be sure to allow convection in the atmosphere around devices when  
mounting. Do not use in locations where the ambient temperature  
exceeds the range of the derating curve.  
S8VS-@@@24A Model Only  
Satisfy the following conditions when storing the Power Supply for  
long periods of time to maintain its remaining service life function.  
When cutting out holes for mounting, make sure that cuttings do not  
enter the interior of the products.  
Before turning the Power Supply ON, be sure to remove sheets that  
were used as covers during mounting, and make sure that heat  
release is not obstructed.  
When storing for more than three months, store within an ambient  
temperature range of 25 to +30°C and the humidity range of 25 to  
70ꢀ.  
*1  
Periodic Inspection (S8VS-09024A  
Model Only)  
Under general operating conditions, the remaining service life func-  
tion starts to work from several to ten and several years after start of  
use. When the Power Supply is used for long periods of time, peri-  
odically follow the procedure below to check that the remaining ser-  
vice life function ((12)Yrs) is working properly.  
*1. Convection of air  
*2. 20 mm min.  
*2  
*1  
1. Set to the Power Supply to the Run Mode.  
Wiring  
2. Make sure that output ((12)Yrs) is ON (electrical continuity across  
terminals (12) and (13)).  
Ground the product (GR) completely. Failure to do so could cause  
electric shock or malfunction.  
3. In the Run Mode, hold down the Down Key (10) and the Mode  
Key (8) for at least three seconds at the same time.  
The main display ((6)) changes to a02.  
Ensure that input and output terminals are wired correctly.  
Do not apply more than 100N force to the terminal block when tight-  
ening it.  
This function is working properly if output ((12)Yrs) is OFF (no  
electrical continuity across terminals (12) and (13)).  
4. Release the key to return to the regular mode.  
Be sure to remove the sheet covering the product for machining  
before power-on.  
Note: DC output is also maintained during periodic inspection.  
Recommended Wire Type  
1
2
Model  
Recommended wire size  
S8VS-06024@  
AWG14 to 20  
(Cross section 0.517 to 2.081mm2)  
S8VS-09024@  
AWG14 to 18  
(Cross section 0.823 to 2.081mm2)  
6
7
Alarm output terminal: AWG22 to 28  
(Cross section 0.081 to 0.326mm2)  
8
9
10  
Installation Environment  
Do not use the Power Supply in locations subject to shocks or vibra-  
tions. In particular, install the Power Supply as far away as possible  
from contactors or other devices that are a vibration source.  
4
5
Install the Power Supply well away from any sources of strong, high-  
frequency noise.  
11 13  
12  
3
Switch mode Power Supply S8VS  
L-65  
Note: 1. Connect the diode as shown in the figure. If the load is  
short-circuited, a reverse voltage may be applied inside the  
power supply unit, causing deterioration or breakage of the  
power supply unit.  
Charging the Battery  
If a battery is to be connected as the load, mount an overcurrent lim-  
iting circuit and an overvoltage protection circuit.  
Select a diode having the following ratings.  
Output Voltage Adjuster  
Do not add unnecessary power. The output voltage adjuster (V.ADJ)  
may be damaged.  
Type  
Schottky Barrier diode  
Dielectric strength Twice the rated output voltage or  
(VRRM)  
above  
Forward current  
(IF)  
Twice the rated output current or  
above  
DIN Track Mounting  
To mount the Block on a DI track, hook portion (A) of the Block onto  
the track and press the Block in direction (B).  
2. Though products having different specifications can be con-  
nected in series, the current flowing through the load must  
not exceed the smaller rated output current.  
A
Parallel Operation  
The product is not designed for parallel operation.  
AC (L)  
+V  
B
AC (N)  
V  
To dismount the Block, pull down portion (C) with a flat-blade screw-  
driver and pull out the Block.  
AC (L)  
+V  
AC (N)  
V  
In Case There is No Output Voltage  
30 mm min.  
The possible cause for no output voltage may be the presence of an  
overload or overvoltage condition, or may be due to the functioning of  
an latching protective device. The latching protection may operate if  
a large amount of surge voltage such as a lightening surge occurs  
while turning on the power supply.  
C
Track stopper  
Series Operation  
In case there is no output voltage, please check the following points  
before contacting us:  
Two power supplies can be connected in series.  
The ( ) voltage output can be accomplished with two power supplies.  
Check the Overload Protected Status:  
AC (L)  
AC (N)  
+V  
Check whether the load is in overload status or is short-circuited.  
Remove wires to load when checking.  
V  
Attempt to clear the overvoltage or latching protection function:  
Turn the power supply off once, and leave it off for at least 3 min-  
utes. Then turn it on again to see if this clears the condition.  
AC (L)  
AC (N)  
+V  
V  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
Cat. No. T026-E1-01  
L-66  
Switch mode Power Supply S8VS  
SSwi8tchPmoSde Power Supply  
The Most Compact DIN-track-mounting  
Switch mode Power Supplies Ever with  
Capacities Up to 600 W  
Power range from 50 W up to 600 W.  
Open-frame and covered types available.  
Easily mounted to DIN track with provided Mounting Brackets.  
Models with Front-mounting Bracket available.  
Conforms to EMC standards: EN50081-1, EN50082-2, and  
EN61000-3-2.  
Maintenance-free up to 300 W due to natural ventilation.  
Protection-ON alarm indicator shows valuable protection func-  
tions in action (300-/600-W models).  
AC universal input: 100 to 240 VAC  
Approved by UL/CSA standards, EN60950 (IEC950), and  
VDE0160.  
Six-language instruction manual provided.  
Life expectancy of 10 years min.  
Finger protection terminal block meets VDE0106/P100. (Cov-  
ered type)  
Model Number Structure  
I Model Number Legend  
2. Output Voltage  
05: 5 V  
12: 12 V  
24: 24 V  
3. Configuration  
S8PS-@@@@@@@  
1
1. Power Ratings  
050: 50 W  
2
3
100: 100 W  
150: 150 W  
300: 300 W  
600: 600 W  
C:  
D:  
Covered type with Front-mounting Bracket  
Open-frame type with DIN Track Mounting Bracket  
CD: Covered type with DIN Track Mounting Bracket  
None: Open-frame type with Front-mounting Bracket  
Ordering Information  
I List of Models  
Configuration  
Input voltage  
Power ratings  
50 W  
Output voltage  
5 V  
Output current  
10 A  
Front-mounting  
Bracket  
DIN Track Mounting  
Bracket  
Covered type  
100 to 240 VAC  
S8PS-05005C  
S8PS-05012C  
S8PS-05024C  
S8PS-10024C  
S8PS-15024C  
S8PS-30024C  
S8PS-60024C  
S8PS-05005  
S8PS-05012  
S8PS-05024  
S8PS-10024  
S8PS-15024  
S8PS-05005CD  
S8PS-05012CD  
S8PS-05024CD  
S8PS-10024CD  
S8PS-15024CD  
S8PS-30024CD  
---  
12 V  
24 V  
24 V  
24 V  
24 V  
24 V  
5 V  
4.2 A  
2.1 A  
4.5 A  
6.5 A  
14 A  
27 A  
10 A  
4.2 A  
2.1 A  
4.5 A  
6.5 A  
100 W  
150 W  
300 W  
600 W  
50 W  
Open-frame type  
100 to 240 VAC  
S8PS-05005D  
S8PS-05012D  
S8PS-05024D  
S8PS-10024D  
S8PS-15024D  
12 V  
24 V  
24 V  
24 V  
100 W  
150 W  
Switch mode Power Supply S8PS  
L-67  
Specifications  
I Ratings/Characteristics  
Item  
50 W  
100 W  
150 W  
300 W  
600 W  
Efficiency (typical)  
75 to 87ꢀ (depends on the model)  
100 to 240 VAC (85 to 264 VAC)  
47 to 450 Hz  
Input  
Voltage  
Frequency  
Current (see note 1)  
0.9 or 0.45 A  
max.  
1.8 or 0.9 A  
max.  
2.7 or 1.4 A  
max.  
5.4 or 2.7 A  
max.  
10 or 5 A max.  
Power factor (see note 1)  
Leakage current (see note 1)  
Inrush current (25°C, cold start) (see note 1)  
Voltage adjustment range  
Ripple (see note 1)  
0.95 TYP.  
0.5 or 1.0 mA max.  
25 or 50 A max.  
5ꢀ to 10ꢀ  
Output  
2ꢀ (p-p) max.  
Input variation influence  
Load variation influence  
Temperature variation influence (see note 1)  
Rise time  
0.4ꢀ max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100ꢀ load)  
0.8ꢀ max. (with rated input, 0 to 100ꢀ load)  
0.05ꢀ/°C max.  
1,000 ms max. (up to 90ꢀ of output voltage at rated output voltage/current)  
20 ms min.  
Hold time (see note 1)  
Additional  
function  
Overload protection  
105ꢀ min., voltage trailing intermittent operation  
(With the 600-W model, output is turned OFF at 5 s min.)  
Overvoltage protection  
Overheat protection  
Protection-ON alarm indicator  
Parallel operation  
Yes  
No  
Yes  
Fan  
No  
Yes (Red)  
No  
Yes, 2 units max.  
Other  
Heat radiation  
Natural air-cooling  
Ambient temperature  
Operating: See the derating curve in the Engineering Data section. (with no condensation  
nor icing)  
Storage:  
25°C to 65°C (with no condensation nor icing)  
Ambient humidity  
Dielectric strength  
25ꢀ to 85ꢀ  
3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)  
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)  
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)  
Insulation resistance  
Vibration resistance  
Shock resistance  
100 Mmin. (between all output and input/GR terminals at 500 VDC)  
10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions  
300 m/s2, 3 times each in X, Y, and Z directions  
Yes (green)  
Output indicator  
Terminal screw tightening torque  
Electromagnetic interference  
EMC  
1.08 N·m (see note 2)  
Conforms to FCC Class B, EN50081-1  
(EMI):  
EN50081-1  
Emission Enclosure:  
Emission AC Mains:  
Harmonic Current:  
(EMS):  
EN55022 class B  
EN55022 class B  
EN61000-3-2  
EN50082-2  
Immunity ESD:  
EN61000-4-2: 4-kV contact discharge (level 2)  
8-kV air discharge (level 3)  
Immunity RF-interference:  
Immunity Conducted Disturbance:  
Immunity Burst:  
ENV50140:  
ENV50141:  
10 V/m (80 MHz to 1 GHz) (level 3)  
10 V (0.15 to 80 MHz) (level 3)  
EN61000-4-4: 2-kV power-line (level 3)  
2-kV output line (level 4)  
Immunity Surge:  
EN61000-4-5: between 3-kV lines  
between 4.5-kV line and FG  
Approved standards  
UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.  
Conforms to UL1950 and CSA E.B. 1402C  
Reliability (MTBF) (see note 3)  
Life expectancy (see note 4)  
Weight (see note 5)  
135,000 hrs min.  
60,000 hrs min.  
10 yrs. min. (Used at 40°C at the rated input with a 50ꢀ load, standard installation)  
420 g max.  
600 g max.  
900 g max.  
2,200 g max.  
3,500 g max.  
Mounting method  
Front-mounting Bracket or DIN Track Mounting Bracket  
Front-mounting Bracket  
Note: 1. 100ꢀ load for rated input voltage (100 VAC or 200 VAC)  
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.  
3. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates  
reliability of devices. Therefore, it does not necessarily represent a life of the product.  
4. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40°C and a load rate  
of 50ꢀ. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be noted that the life  
expectancy of the fan built into the 600-W model is not included.  
5. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)  
L-68  
Switch mode Power Supply S8PS  
Connections  
I Block Diagrams  
S8PS-050@@@@ (50 W)  
Rectifier  
+V  
AC(L)  
Fuse  
(4 A)  
Noise filter  
INPUT  
DC OUT  
AC(N)  
V  
Inrush current  
protection circuit  
Harmonic Smooth-  
Rectifier/  
smoothing  
circuit  
current  
control  
ing  
Drive control  
circuit  
Overload  
detection circuit  
Detector  
Overload  
detection circuit  
S8PS-10024@@ (100 W)  
S8PS-15024@@ (150 W)  
S8PS-30024@@ (300 W)  
Rectifier  
AC(L)  
+V  
Fuse*  
Noise filter  
INPUT  
DC OUT  
AC(N)  
V  
Inrush current  
protection circuit  
Harmonic Smooth-  
Rectifier/  
smoothing  
circuit  
current  
control  
ing  
*Fuse capacity  
100-W: 6.3 A  
150-W: 6.3 A  
300-W: 8 A  
Control circuit  
Overload  
detection circuit  
Detector  
Overload  
detection circuit  
S8PS-60024C (600 W)  
Rectifier  
+V  
AC(L)  
Fuse  
(15 A)  
Noise filter  
DC OUT  
INPUT  
AC(N)  
V  
Inrush current  
protection circuit  
Harmonic cur- Smooth-  
Rectifier/  
smoothing  
circuit  
rent control  
ing  
Control circuit  
Fan  
Detector  
Overcurrent  
detection  
Overload  
detection circuit  
Overheat  
detection  
Switch mode Power Supply S8PS  
L-69  
I Installation  
50-W Models  
100-/150-W Models  
4
5
4
5
1
3
2
1
3
2
1
5 4  
300-W Models  
600-W Models  
4
5
6
2
3
1
1. DC Output Terminals: Connect the load lines to these terminals.  
2. Input Terminals: Connect the input lines to these terminals.  
6
2
3
Note: A fuse is inserted into the AC (L) side.  
3. Ground Terminal (GR): Connect a ground line to this terminal.  
4. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON.  
5. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%.  
6. Protection-ON Alarm Indicator: The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for a  
600-W model) circuit is triggered. This indicator will also be lit when overcurrent (for a 600-W model) is detected.  
L-70  
Switch mode Power Supply S8PS  
Engineering Data  
I Derating Curve  
Open-frame Type  
Covered Type  
50- to 300-W Model  
Forced air-cooling,  
600-W Model  
50- to 150-W Model  
Forced air-cooling  
50- to 300-W Model  
Natural air-cooling  
50- to 150-W Model  
Natural air-cooling  
Ambient temperature (°C)  
Ambient temperature (°C)  
Note: 1. Forced air-cooling must be provided with an air volume of 1 m3/mm min.  
2. The derating curve shown is for standard installation. The derating curve depends on the mounting direction of the Power Supply.  
Standard Installation  
50-W Model  
20 mm min. 20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
Standard Installation  
100/150-W Model  
30 mm min.  
30 mm min.  
20 mm min.  
20 mm min.  
30 mm min.  
30 mm min.  
20 mm min.  
20 mm min.  
Standard Installation  
300-W Model  
30 mm min.  
20 mm min.  
20 mm min.  
30 mm min.  
Standard Installation  
600-W Model  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
Switch mode Power Supply S8PS  
L-71  
I Overload Protection  
I Overvoltage Protection  
The Power Supply is provided with an overvoltage protection function  
that protects the load and the Power Supply from possible damage  
by overvoltage. When the output voltage rises above a set value  
(115ꢀ of the rated output voltage), the protection function is trig-  
gered, shutting OFF the output voltage. If this occurs, reset the  
Power Supply by turning it OFF for 1 minute min. and then turning it  
ON again.  
50- to 300-W Models  
The Power Supply is provided with an overload protection function  
that protects the load and the power supply from possible damage by  
overcurrent. The protection function operates when the load current  
rises above an overcurrent set value (105ꢀ of the rated load cur-  
rent). For a short-circuit or overcurrent lasting less than 20 seconds,  
output voltage is decreased to protect equipment. When the output  
current falls within the rated range, the overload protection function is  
automatically cleared.  
Overvoltage  
protection  
operating  
Rated output  
voltage  
Variable range  
Intermittent  
operation  
0 V  
300- and 600-W Models Only  
The overvoltage protection-ON alarm indicator lights when the func-  
tion is operating.  
Rating  
Output current (%)  
Note: Do not continue using the S8PS under short-circuited or over-  
current conditions for longer than 20 seconds, otherwise the in-  
ternal elements of the S8PS may be damaged or broken.  
I Overheat Protection Function  
600-W Models  
600-W Model Only  
If an excessive current flows for 5 s or more, the output will be turned  
OFF and simultaneously protection-ON alarm indicator will be lit. To  
reset the S8PS, turn OFF the input voltage, leave the S8PS for at  
least three minutes, and then apply the input voltage again.  
If the internal temperature of the S8PS rises excessively as a result  
of fan failure or any other reason, the overheat protection circuit will  
be triggered to protect the internal elements of the S8PS and simul-  
taneously a protection-ON alarm indicator will be lit. To reset the  
S8PS turn OFF the input voltage, leave the S8PS for at least one  
minute and then apply the input voltage again.  
Note: Do not continue using the S8PS with the output terminals  
short-circuited or the overcurrent condition continued, other-  
wise the internal elements of the S8PS may be damaged or  
broken.  
I Inrush Current, Rise Time, Hold Time  
Input ON  
Input OFF  
AC input  
voltage  
Inrush current on input application  
AC input  
current  
96.5%  
90%  
Output  
voltage  
Rise time  
(1,000 ms max.)  
Hold time  
(20 ms min.)  
L-72  
Switch mode Power Supply S8PS  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
I Front-mounting Bracket Type  
The Front-mounting Bracket is provided as an accessory. Screws for fixing the Bracket to the panel are not provided.  
S8PS-050@@ (50 W)  
S8PS-050@@@C (50 W)  
11.5 max.  
Five, M4 terminal screws  
3.5 dia.  
3.5 dia.  
Three, M3 (depth: 6 max.)  
Front-mounting Bracket for 50-W Models  
Using the Mounting Bracket  
Attach the Mounting Bracket to the panel and loosely  
tighten the two screws. Insert the projected parts of the  
Bracket (b) to the square holes of the power supply (a).  
Then securely tighten the screws.  
Mounting Holes  
11  
1.5  
4.6  
15 0.2  
9
Two,  
3.5 dia.  
74  
60  
Two, M3  
60  
4.6  
11  
20  
31.5  
5
20  
4.7  
15  
20.5  
Mounting Bracket  
11.5 max.  
S8PS-10024 (100 W)  
S8PS-10024C (100 W)  
Five, M4 terminal screws  
4.5 dia.  
4.5 dia.  
Mounting holes (also on opposite side)  
Three, M4 (depth: 4 max.)  
Switch mode Power Supply S8PS  
L-73  
S8PS-15024 (150 W)  
S8PS-15024C (150 W)  
11.5 max.  
Five, M4 terminal screws  
4.5 dia.  
Mounting holes (also on opposite side)  
4.5 dia.  
Three, M4 (depth: 6 max.)  
Front-mounting Bracket for 100/150-W Models  
Dimensions with Mounting Bracket  
Using the Mounting Bracket  
Appearance and Mounting Dimensions  
Mounting Bracket  
5 dia.  
115 max.  
Two, 5 dia.  
Eight, M4 (depth: 8 max., also for the opposite side)  
Seven, M4 terminal screws  
(14)  
S8PS-30024C (300 W)  
Four, M4 (depth: 8 max.)  
L-74  
Switch mode Power Supply S8PS  
Seven, M4 (depth: 8 max.)  
S8PS-60024C (600 W)  
Eight, M4 (depth: 8 max., also for the opposite side)  
Four, M4 (depth: 8 max., opposite side only)  
Four, M4  
(depth: 8 max.)  
Using the Mounting Bracket  
Front-mounting Bracket for 300/600-W Models  
Note: Four screws for attaching the Bracket to  
Appearance and Mounting  
Dimensions  
Dimensions with Mounting Bracket  
300-W models  
the Power Supply Unit are provided.  
10 dia.  
300-W models  
Two, 5 dia.  
Note: Mount the Unit 21.6 mm away from the  
mounting surface in order to provide air  
ventilation on the rear side.  
Four, M4  
600-W models  
600-W models  
Note: Mount the Unit 28 mm away from the mount-  
ing surface in order to provide air ventilation  
on the rear side.  
Four, M4  
Switch mode Power Supply S8PS  
L-75  
I DIN Track Mounting Bracket Type  
DIN Track Mounting Bracket  
DIN Track Mounting Bracket is  
attached to the Power Supply  
Unit when the Unit is shipped.  
S8PS-050@@D (50 W)  
S8PS-050@@@CD (50 W)  
11.5 max.  
Five, M4 terminal screws  
5.6  
3.5 dia.  
(With slide: 9 max.)  
S8PS-10024D (100 W)  
S8PS-10024CD (100 W)  
11.5 max.  
Five, M4 terminal screws  
4.5 dia.  
5.6  
(With slide: 9 max.)  
S8PS-15024D (150 W)  
S8PS-15024CD (150 W)  
11.5 max.  
Five, M4 terminal screws  
5.6  
4.5 dia.  
(With slide: 9 max.)  
L-76  
Switch mode Power Supply S8PS  
(14)  
S8PS-30024CD (300 W)  
Seven, M4 terminal screws  
5.6  
(With slide: 9 max.)  
I Accessories  
Mounting Track (Order Separately)  
PFP-100N/PFP-50N  
PFP-100N2  
16  
7.3 0.15  
35 0.3  
4.5  
4.5  
27  
29.2  
24  
35 0.3  
27 0.15  
1
15 25  
25  
25  
25 15  
15 25  
25  
25  
25  
1
1.5  
10  
10  
10  
10  
1,000 (500)  
(see note)  
15 (5)  
(see note)  
1,000  
Note: The values shown in parentheses are for the  
PFP-50N.  
Switch mode Power Supply S8PS  
L-77  
Precautions  
Parallel Operation  
Only 300- and 600-W models can be in parallel operation provided  
that they are operated under 90ꢀ of the ratings. Do not operate any  
other models in parallel.  
!Caution  
Be sure to connect the grounding line. Not doing so may result in  
electric shock.  
!WARNING  
Make sure that the thickness and the length of all wires connected to  
the load are the same to ensure that the wires will have no voltage  
drop differences.  
Do not attempt to disassemble the Power Supply or touch its inter-  
nal parts while power is being supplied. Doing so may result in  
electric shock.  
Do not touch the terminals of the Power Supply within one minute  
after power has been turned OFF. Doing so may result in electric  
shock due to a residual voltage.  
+ V  
INPUT  
Do not touch the S8PS or heat radiation fin while the power is be-  
ing supplied or immediately after the power is turned OFF. Other-  
wise, a skin burn may result from the hot Switching Power Supply  
or radiator.  
V  
+ V  
INPUT  
Mounting  
V  
To improve and maintain the reliability of the Power Supply over a  
long period of time, adequate consideration must be given to heat  
radiation.  
Fan Replacement  
The service life of the fan is approximately 50,000 hours (at 25°C).  
The service life varies, however, depending on the ambient tempera-  
ture or other surrounding environmental conditions such as dust. As  
a preventive maintenance measure, replace the fan within two years  
if it is used at an ambient temperature of 40°C.  
The Power Supply is designed to radiate heat by means of natural  
air-flow. Therefore, mount the Power Supply so that air flow takes  
place around the Power Supply.  
When mounting the Power Supply, mounting it to a metal plate is rec-  
ommended.  
Fans are available as replacements.  
Forced air-cooling is highly recommended.  
It is recommended that the clearance around the Power Supply be  
larger than those shown on page page 71 under Standard Installa-  
tion.  
Generating Output Voltage ( )  
An output of can be generated by using two Power Supplies as  
shown below, because the Power Supply produces a floating output.  
+ V  
Model: S82Y-JFAN  
INPUT  
INPUT  
Input  
V  
Fan Set:  
Fan (above), four M4 x 35 sems screws, instruction sheet, and pack-  
ing case  
+ V  
Replace the fan as shown in the following illustration.  
V  
Series Operation  
Only models with power ratings of 100/150 W allow series operation.  
As shown in the following diagram, the output voltage from each  
Switching Power Supply can be added.  
+V  
INPUT  
V  
+V  
INPUT  
V  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
Cat. No. T021-E1-03  
L-78  
Switch mode Power Supply S8PS  

相关型号:

S8VS-09024B-F

Power Supply Module,
OMRON

S8VS-09024BE

Greater Simplicity for Power Supply Visualization
OMRON

S8VS-09024BE-F

Power Supply Module,
OMRON

S8VS-09024BES

Switch Mode Power Supply
OMRON

S8VS-09024BES-F

Power Supply Module,
OMRON

S8VS-09024BP

Switch Mode Power Supply
OMRON

S8VS-09024BP-F

Power Supply Module,
OMRON

S8VS-09024BPS

Switch Mode Power Supply
OMRON

S8VS-09024BPS-F

Power Supply Module,
OMRON

S8VS-09024BS

Switch Mode Power Supply
OMRON

S8VS-09024BS-F

Power Supply Module,
OMRON

S8VS-09024S

Switch Mode Power Supply
OMRON