SmartZone™ G5 Intelligent Power
Distribution Units (iPDUs)
S P E C I F I C A T I O N S H E E T
o v e r v i e w
The Panduit® SmartZone™ G5 iPDU is more than a power distribution unit and energy meter. These iPDUs monitor
the data center power and environment (at the rack or cabinet level), by continuously scanning for electrical circuit
overloads, and physical environmental conditions that place critical IT equipment at risk. Panduit’s iPDUs provide
comprehensive, accurate, energy measurement data to efficiently use power resources, make informed capacity
planning decisions, improve uptime, measure PUE (power usage effectiveness), and drive green data center
initiatives to save energy and money.
Making the right choice in IT equipment is essential for a safe, efficient data center operation. Our full range of iPDUs,
environmental sensors, and dual locking power cords are the key to fulfilling mission‐critical data center needs.
t e c h n i c a l i n f o r m a t i o n
Dimensions:
Height Inch (mm) Width Inch (mm)
Depth Inch (mm)
1U:
1U:
1U:
2U:
1.6 (40.6)
1.7 (43.2)
1.7 (43.2)
3.4 (86.4)
17.5 (444.5)
17.5 (444.5)
17.5 (444.5)
17.5 (444.5)
2.0 (50.8)
7.8 (198.1)
10.6 (269.2)
7.8 (198.1)
0U HALF:
32.2 (817.9)
2.0 (50.8)
2.0 (50.8)
2.0 (50.8)
2.1 (53.3)
4.4 (111.8)
2.1 (53.3)
0U HALF (2 sided): 36 (914.4)
0U MID:
58.7 (1491)
0U FULL:
68.9 (1750.1)
2.0 (50.8)
2.0 (50.8)
2.1 (53.3)
4.4 (111.8)
0U FULL (2 sided): 71.7 (1821.2)
0U Full +:
0U Full Wide:
0U Full Wide +:
74.6 (1896)
68.9 (1750.1)
74.0 (1880)
2.0 (50.8)
3.3 (83.8)
3.3 (83.8)
2.1 (53.3)
2.1 (53.3)
2.1 (53.3)
Mounting:
Vertical units provide up to 48 outlets and without encroaching on the EIA
space. Horizontal units provide up to 16 outlets and mount in standard
(1U or 2U) TIA/EIA rack space.
k e y f e a t u r e s a n d b e n e f i t s
HotSwappable
Controller:
Replace the controller and display module without having to power down
the rack
Redundant Network
Access:
Specifically designed for Landlord/Tenant (Co-Lo’s) allowing for remote
access of real-time, vital statistics and operating information on two
separate, secure networks.
Hardened Security:
1GB Ethernet:
Not only Physical but hardened Digital Security; layers within the firmware
LDAP, SNMP v3, TLS, Encrypted Security; allows for Panduit PDUs to pass
standard certified security scans.
The 1G controller is compatible with the new Data Center Network switches
being deployed - reducing special network configurations/resources required
to support the iPDU.
Plug & Play Sensors:
Multi-Color PDUs:
Digital sensors not only allow for multiple sensors on the same bus; but also
identify themselves to the controller to simplify setup & commissioning.
Different color PDUs simplify power feed identification & management. The
new Panduit Intelligent PDUs are available in Black, White, Red, Blue,
Yellow or Green.
Mobile & Desktop
Friendly Web GUI:
The intelligent PDUs feature an enhanced designed web interface which
detects the type of device that you are on; and automatically adjusts the
screen for an optimal experience.
Outlet Density:
Form Factor:
Meets demands of densely packed IT equipment in rack or cabinet space
Optimal form factor enables efficient rack space utilization
Operating Temperature: 60°C ambient at full load for operational reliability in high temperature areas
(continued pg. 2)
www.panduit.com
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
k e y f e a t u r e s a n d b e n e f i t s (continued)
Cable Retention:
Innovative cable tie accepting outlets allow for secure cord retention (C13 & C19 only) using a
cable tie for added safety and security. (Panduit part number: PLT2I-C0)
Circuit Breakers:
Protects data center equipment for increased reliability by interrupting potentially hazardous circuit
over-current conditions*
Color Coded Circuits*:
Easily identify phase to outlet banks to aid in fault isolation or load balancing
External Chassis
Ground:
Meets NEC requirements and installation guidelines for IT equipment
Load Balancing:
Monitored through visual display on oLED (for 3 phase units only)
Multiple Input Plug
Options:
A full breadth offering to seamlessly interoperate with existing building power wiring schemes
Multiple Mounting
Options:
Enables simple out of the box commissioning and flexibility with Panduit cabinets and industry
standard mounting features enabling installation into third party cabinets
Mounting Buttons:
Allows tool-less mounting of rack PDUs for faster installations on vertical 0U units
Supported Metering:
Frequency, VA, PF, plus aggregate and per phase Amperage, Voltage, Wattage, and Kilowatts
per hour
* Applies to products outfitted with circuit breakers
i P D U p r o d u c t f a m i l i e s
MI Series:
Rack PDUs that have the ability for aggregate power monitoring to quickly identify potential power
issues, and reclaim available or under-utilized power capacity.
MS Series:
Rack PDUs that have the ability for aggregate power monitoring and outlet level switching
capabilities for individual outlets or a group of outlets. Enabling power sequencing, rebooting
equipment or restrict unauthorized use of individual outlets.
MPO Series:
Rack PDUs that have the ability for outlet level (and aggregate) power monitoring to quickly
identify potential power issues, and reclaim available or under-utilized power capacity at the outlet
level enabling the redeployment or decommissioning of individual servers to reclaim available or
under-utilized power capacity.
MSPO Series:
Rack PDUs that have the ability for outlet level (and aggregate) power monitoring and outlet level
switching capabilities for individual outlets or a group of outlets. Power monitoring at the individual
outlet level provides actionable management data on the power consumption of each connected
IT device enabling the redeployment or decommissioning of individual servers to reclaim available
or under-utilized power capacity. Ideal for remote power reset, and cabinet power on sequencing
and restrict unauthorized use of individual outlets.
e l e c t r i c a l s p e c i f i c a t i o n s
North America
International models
Input Voltage
• Single-Phase 120V
• Single-Phase 240V
• Single-Phase 208V
• Three-Phase Wye 240/415V
• Three-Phase Delta 208V
• Three-Phase Wye 120/208V
• Three-Phase Wye 415V
Input Current (per phase)
Input Power
North America
International models
• 15A, 20A, 30A, 50A, 60A
• 16A, 32A
North America
• 1.4 – 17.3 (kVA)
International models
• 3.7 – 22 (kVA)
Input Frequency
50/60 Hz
Output Voltage
120 - 240 VAC
Maximum output current (outlet)
IEC C13: 10A
IEC C19: 16A
NEMA 5-20R: 16A
Overload protection (where applicable)
Circuit Breakers, hydraulic magnetic
10 kAIC Circuit Breakers for all 415V models for North America
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
g e n e r a l s p e c i f i c a t i o n s
Temperature: Operating
50° to 140° F (10° to 60° C)
-4° to 140° F (-20° to 60° C)
10% to 90% non-condensing
5 to 95% RH
Temperature: Storage
Relative Humidity: Operating
Relative Humidity: Non-Operating
Relative Humidity: Storage
Elevation: Operating
5% to 95%
0 to 10,000 ft. (0 to 3000 m)
0 to 30,000 ft. (0 to 9144 m)
Elevation: Storage
Conformance Standards
North America - UL, CB Test Approved
International - CE Approved, EAC Russia Approval
Environmental Compliances
RoHS & REACH
c a b i n e t c o m p a t i b i l i t y
Panduit iPDUs can be easily installed into Panduit (or third party cabinets) by utilizing the installed mounting buttons
(18.4 mm diameter). Where necessary, a Small Diameter (14.5 mm) mounting button is available (sold separately,
p/n: MA018). Panduit PDUs feature threaded inserts on the back and both sides for the ultimate in mounting flexibility.
They safely and efficiently manage and distribute power to multiple devices through a single input power connector,
per PDU, to enhance scalability of network build outs.
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
Monitored Input - MI Series
Input
Apparent
Power
(kVA)
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
Outlet Configuration
(inches) (inches)
NA
INTL
NA
15
16
20
20
20
50
30
30
32
15
20
20
16
20
30
30
32
30
32
32
50
1U
1U
5-15P
0
0
0
0
0
3
2
2
2
0
0
0
0
0
2
2
2
2
2
2
3
1.4
3.7
1.9
1.9
3.3
8.3
2.9
5.0
7.4
1.4
1.9
1.9
3.7
3.3
2.9
5.0
7.4
5.0
7.4
7.4
8.3
8
(8)5-20R
1.7
1.7
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
2.0
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
2.1
P08D09M
P12D36M
P08D10M
P08D11M
P12D13M
P06D15M
P16D12M
P16D14M
P16D37M
P16D20M
P16D21M
P16D22M
P24D40M
P24D24M
P24D23M
P24D07M
P24D03M
P38D25M
P34D41M
P42D06M
P36D26M
IEC 60309-316P6
5-20P
12
8
(12)C13
(8)5-20R
(8)5-20R
(12)C13
(6)C19
1U
1.7
NA
1U
L5-20P
8
1.7
NA
1U
L6-20P
12
6
1.7
NA
1U
CS8265C
L5-30P
1.7
NA
2U
16
16
16
16
16
16
24
24
24
24
24
38
34
42
36
(16)5-20R
3.4
NA
2U
L6-30P
(12)C13,
(12)C13,
(16)5-20R
(16)5-20R
(16)5-20R
(20)C13,
(20)C13,
(24)5-20R
(20)C13,
(20)C13,
(32)C13,
(28)C13,
(36)C13,
(30)C13,
(4)C19
3.4
INTL
NA
2U
IEC 60309-332P6
5-15P
(4)C19
3.4
0U HALF
0U HALF
0U HALF
0U MID
0U MID
0U MID
0U MID
0U Mid
0U FULL
0U FULL
0U FULL
0U FULL
32.2
32.2
32.2
58.7
58.7
58.7
58.7
58.7
68.9
68.9
68.9
68.9
NA
5-20P
2.0
2.1
NA
L5-20P
2.0
2.1
INTL
NA
IEC 60309-316P6
L6-20P
(4)C19
(4)C19
2.0
2.1
2.0
2.1
NA
L5-30P
2.0
2.1
NA
L6-30P
(4)C19
(4)C19
(6)C19
(6)C19
(6)C19
(6)C19
2.0
2.1
INTL
NA
IEC 60309-332P6
L6-30P
2.0
2.1
2.0
2.1
INTL
INTL
NA
IEC 60309-332P6
IEC 60309-332P6
CS8265C
2.0
2.1
2.0
2.1
2.0
2.1
NA
NA
NA
NA
NA
NA
30
30
50
60
30
30
1U
1U
L15-30P
L21-30P
3
3
6
6
3
3
8.6
8.6
6
6
(6)C19
(6)C19
(6)C19
(6)C19
(18)C13,
(18)C13,
1.7
1.7
17.5
17.5
17.5
17.5
2.0
10.6
10.6
10.6
10.6
2.1
P06D16M
P06D17M
P06D18M
P06D19M
P24D27M
P24D01M
1U
CS8365C
14.4
17.3
8.6
6
1.7
1U
IEC 60309-460P9
L15-30P
6
1.7
0U MID
0U MID
24
24
(6)C19
58.7
58.7
L21-30P
8.6
(6)C19
(6)C19,
2.0
2.1
(18)C13,
(6)5-20R
NA
NA
NA
30
30
30
0U FULL
0U FULL
0U FULL
L21-30P
L15-30P
L21-30P
3
3
3
8.6
8.6
8.6
30
36
38
68.9
68.9
68.9
2.0
2.0
2.0
2.1
2.1
2.1
P30D02M
P36D08M
P38D28M
(30)C13,
(6)C19
(6)C19,
(30)C13,
(2)5-20R
NA
NA
NA
50
50
60
0U FULL
0U FULL
0U FULL
CS8365C
CS8365C
3
6
6
10.0
14.4
17.3
36
24
24
(30)C13,
(12)C13,
(12)C13,
(6)C19
68.9
68.9
68.9
2.0
2.0
2.0
2.1
2.1
2.1
P36D29M
P24D31M
P24D34M
(12)C19
(12)C19
IEC 60309-460P9
0U HALF -
2 sided
NA
NA
NA
50
60
50
CS8365C
IEC 60309-460P9
CS8365C
6
6
6
14.4
17.3
14.4
24
24
48
(18)C13,
(18)C13,
(36)C13,
(6)C19
(6)C19
(12)C19
36.0
36.0
71.7
2.0
2.0
2.0
4.4
4.4
4.4
P24D30M
P24D33M
P48D32M
0U HALF -
2 sided
0U FULL -
2 sided
0U FULL -
2 sided
NA
60
IEC 60309-460P9
6
17.3
48
(36)C13,
(12)C19
71.7
2.0
4.4
P48D35M
INTL
INTL
INTL
INTL
INTL
INTL
16
32
16
16
32
32
1U
IEC 60309-516P6
IEC 60309-532P6
IEC 60309-516P6
IEC 60309-516P6
IEC 60309-532P6
IEC 60309-532P6
0
6
0
0
6
6
11.0
22.0
11.0
11.0
22.0
22.0
6
(6)C19
1.7
1.7
17.5
17.5
2.0
10.6
10.6
2.1
P06D38M
P06D39M
P30D05M
P42D42M
P24D43M
P42D04M
1U
6
(6)C19
0U MID
0U FULL
0U FULL
0U FULL
30
42
24
42
(24)C13,
(36)C13,
(12)C13,
(30)C13,
(6)C19
(6)C19
(12)C19
(12)C19
58.7
68.9
68.9
68.9
2.0
2.1
2.0
2.1
2.2
2.1
0U FULL -
2 sided
INTL
32
IEC 60309-532P6
6
22.0
48
(36)C13,
(12)C19
71.7
2.0
4.4
P48D44M
(continued pg. 5)
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
Monitored Input - MI Series (continued)
Input
Apparent
Power
(kVA)
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
Outlet Configuration
(inches) (inches)
IEC 60309 3P+N+E 6h 30A
(IP67)
NA
30
1U
6
17.3
6
(6)C19
1.7
17.5
10.6
P06D01M
IEC 60309 3P+N+E 6h 30A
(IP44)
NA
NA
NA
30
30
30
1U
1U
6
6
6
17.3
17.3
17.3
6
6
(6)C19
(6)C19
1.7
1.7
17.5
17.5
2.0
10.6
10.6
2.1
P06D03M
P06D02M
P24D02M
NEMA L22-30P
IEC 60309 3P+N+E 6h 30A
(IP67)
0U FULL
24
(12)C13,
(12)C19
68.9
IEC 60309 3P+N+E 6h 30A
(IP44)
NA
NA
NA
30
30
30
0U FULL
0U FULL
0U FULL
6
6
6
17.3
17.3
17.3
24
24
36
(12)C13,
(12)C13,
(24)C13,
(12)C19
(12)C19
(12)C19
68.9
68.9
68.9
2.0
2.0
2.0
2.1
2.1
2.1
P24D05M
P24D04M
P36D01M
NEMA L22-30P
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP44)
NA
NA
NA
30
30
30
0U FULL
0U FULL
6
6
6
17.3
17.3
17.3
36
36
48
(24)C13,
(24)C13,
(36)C13,
(12)C19
(12)C19
(12)C19
68.9
68.9
71.7
2.0
2.0
2.0
2.1
2.1
4.4
P36D03M
P36D02M
P48D01M
NEMA L22-30P
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
NA
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
30
30
30
30
6
6
6
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
48
48
48
48
48
42
42
42
(36)C13,
(36)C13,
(48)C13
(48)C13
(48)C13
(36)C13,
(36)C13,
(36)C13,
(12)C19
(12)C19
71.7
71.7
68.9
68.9
68.9
74.6
74.6
74.6
2.0
2.0
3.3
3.3
3.3
2.0
2.0
2.0
4.4
4.4
2.1
2.1
2.1
2.1
2.1
2.1
P48D07M
P48D02M
P48D03M
P48D04M
P48D08M
P42D05M
P42D07M
P42D08M
2 sided
(IP44)
0U FULL -
2 sided
NEMA L22-30P
0U FULL -
Wide
NEMA L22-30P
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide
(IP44)
IEC 60309 3P+N+E 6h 30A
(IP67)
0U FULL +
(6)C19
(6)C19
(6)C19
0U FULL +
0U FULL +
NEMA L22-30P
IEC 60309 3P+N+E 6h 30A
(IP44)
Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America include 10 kAIC circuit breakers.
Monitored Switched - MS Series
Input
Apparent
Power
(kVA)
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
Outlet Configuration
(inches) (inches)
NA
INTL
NA
15
16
20
20
20
32
30
30
32
15
16
20
20
20
16
30
30
30
32
32
32
1U
1U
5-15P
0
0
0
0
0
2
2
2
2
0
0
0
0
0
0
2
2
2
2
2
2
1.4
3.7
1.9
1.9
3.3
7.4
2.9
5.0
7.4
1.4
3.7
1.9
1.9
3.3
3.7
2.9
5.0
5.0
7.4
7.4
7.4
8
(8)5-20R
1.7
1.7
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
2.0
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
2.1
P08E14M
P08E25M
P08E15M
P08E16M
P08E18M
P08E05M
P16E17M
P16E19M
P16E26M
P12E20M
P16E27M
P12E21M
P12E22M
P16E24M
P24E04M
P18E23M
P24E28M
P36E33M
P24E01M
P32E06M
P44E07M
IEC 60309-316P6
5-20P
8
(8)C13
1U
8
(8)5-20R
(8)5-20R
(8)C13
1.7
NA
1U
L5-20P
8
1.7
NA
1U
L6-20P
8
1.7
INTL
NA
1U
IEC 60309-332P6
L5-30P
8
(8)C13
1.7
2U
16
16
16
12
16
12
12
16
24
18
24
36
24
32
44
(16)5-20R
3.4
NA
2U
L6-30P
(12)C13,
(12)C13,
(12)5-20R
(12)C13,
(12)5-20R
(12)5-20R
(12)C13,
(20)C13,
(18)5-20R
(20)C13,
(30)C13,
(20)C13,
(24)C13,
(38)C13,
(4)C19
3.4
INTL
NA
2U
IEC 60309-332P6
5-15P
(4)C19
3.4
0U HALF
0U HALF
0U HALF
0U HALF
0U HALF
0U MID
0U MID
0U FULL
0U FULL
0U FULL
0U FULL
36.1
36.1
36.1
36.1
36.1
58.7
58.7
68.9
68.9
68.9
68.9
68.9
INTL
NA
IEC 60309-316P6
5-20P
(4)C19
2.0
2.1
2.0
2.1
NA
L5-20P
2.0
2.1
NA
L6-20P
(4)C19
(4)C19
2.0
2.1
INTL
NA
IEC 60309-316P6
L5-30P
2.0
2.1
2.0
2.1
NA
L6-30P
(4)C19
(6)C19
(4)C19
(8)C19
(6)C19
2.0
2.1
NA
L6-30P
2.0
2.1
INTL
INTL
INTL
IEC 60309-332P6
IEC 60309-332P6
IEC 60309-332P6
2.0
2.1
2.0
2.1
0U FULL -
wide
3.3
2.1
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
Monitored Switched - MS Series
Input
Apparent
Power
(kVA)
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
Outlet Configuration
(inches) (inches)
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
50
50
60
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
L15-30P
3
3
3
3
6
3
6
8.6
8.6
24
24
36
36
24
36
24
(18)C13,
(18)C13,
(30)C13,
(30)C13,
(12)C13,
(30)C13,
(12)C13,
(6)C19
68.9
68.9
68.9
68.9
68.9
68.9
68.9
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.1
P24E29M
P24E30M
P36E34M
P36E35M
P24E31M
P36E12M
P24E32M
L21-30P
L15-30P
(6)C19
(6)C19
(6)C19
(12)C19
(6)C19
(12)C19
8.6
L21-30P
8.6
CS8365C
14.4
10.0
17.3
CS8365C
IEC 60309-460P9
0U FULL -
2 sided
NA
60
IEC 60309-460P9
6
17.3
48
(36)C13,
(12)C19
71.7
2.0
4.4
P48E13M
INTL
INTL
INTL
INTL
16
16
32
32
0U FULL
0U FULL
0U FULL
IEC 60309-516P6
IEC 60309-516P6
IEC 60309-532P6
IEC 60309-532P6
0
0
6
6
11.0
11.0
22.0
22.0
24
36
24
36
(18)C13,
(30)C13,
(12)C13,
(24)C13,
(6)C19
(6)C19
(12)C19
(12)C19
68.9
68.9
68.9
68.9
2.0
2.0
2.0
3.3
2.1
2.1
2.1
2.1
P24E02M
P36E08M
P24E03M
P36E09M
0U FULL -
wide
0U FULL -
2 sided
INTL
32
IEC 60309-532P6
6
22.0
48
(36)C13,
(12)C19
71.7
2.0
4.4
P48E10M
IEC 60309 3P+N+E 6h 30A
(IP67)
NA
NA
NA
NA
NA
30
30
30
30
30
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
24
24
24
24
24
(12)C13,
(18)C13,
(24)C13
(12)C13,
(18)C13,
(12)C19
(6)C19
68.9
68.9
68.9
68.9
68.9
2.0
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
2.1
P24E05M
P24E07M
P24E08M
P24E09M
P24E10M
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(12)C19
(6)C19
(IP44)
IEC 60309 3P+N+E 6h 30A
(IP44)
IEC 60309 3P+N+E 6h 30A
NA
NA
NA
NA
NA
30
30
30
30
30
0U FULL
0U FULL
0U FULL
0U FULL
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
24
24
24
24
36
(24)C13
(12)C13,
(18)C13,
(24)C13
(24)C13,
68.9
68.9
68.9
68.9
68.9
2.0
2.0
2.0
2.0
3.3
2.1
2.1
2.1
2.1
2.1
P24E11M
P24E06M
P24E12M
P24E13M
P36E01M
(IP44)
NEMA L22-30P
NEMA L22-30P
NEMA L22-30P
(12)C19
(6)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP44)
(12)C19
(6)C19
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
36
36
36
36
36
48
48
48
48
48
48
48
48
48
48
48
48
(30)C13,
(24)C13,
(30)C13,
(24)C13,
(30)C13,
(36)C13,
(48)C13
(36)C13,
(48)C13
(36)C13,
(48)C13
(48)C13
(48)C13
(48)C13
(42)C13,
(42)C13,
(42)C13,
68.9
68.9
68.9
68.9
68.9
71.7
71.7
71.7
71.7
71.7
71.7
74.0
74.0
74.0
74.0
74.0
74.0
3.3
3.3
3.3
3.3
3.3
2.0
2.0
2.0
2.0
2.0
2.0
3.3
3.3
3.3
3.3
3.3
3.3
2.1
2.1
2.1
2.1
2.1
4.4
4.4
4.4
4.4
4.4
4.4
2.1
2.1
2.1
2.1
2.1
2.1
P36E03M
P36E04M
P36E05M
P36E02M
P36E06M
P48E01M
P48E07M
P48E08M
P48E09M
P48E02M
P48E14M
P48E04M
P48E03M
P48E11M
P48E05M
P48E06M
P48E12M
(12)C19
(6)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide
0U FULL -
Wide
0U FULL -
Wide
(IP44)
NEMA L22-30P
(12)C19
(6)C19
NEMA L22-30P
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP44)
(12)C19
(12)C19
(12)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided
0U FULL -
2 sided
0U FULL -
2 sided
0U FULL -
Wide +
(IP44)
NEMA L22-30P
NEMA L22-30P
NEMA L22-30P
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP44)
0U FULL - IEC 60309 3P+N+E 6h 30A
(6)C19
(6)C19
(6)C19
Wide +
0U FULL -
Wide +
(IP67)
NEMA L22-30P
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP44)
Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America feature 10 kAIC circuit breakers.
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
Monitored Per Outlet - MPO Series
Input
Apparent
Power
(kVA)
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
Outlet Configuration
(inches) (inches)
NA
NA
30
30
32
32
0U FULL
0U FULL
0U FULL
0U FULL
NEMA L6-30P
2
2
2
2
5.0
5.0
7.4
7.4
24
36
24
32
(20)C13,
(30)C13,
(20)C13,
(24)C13,
(4)C19
68.9
68.9
68.9
68.9
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
P24F01M
P36F15M
P24F06M
P32F10M
NEMA L6-30P
IEC 60309-332P6
IEC 60309-332P6
(6)C19
(4)C19
(8)C19
INTL
INTL
0U FULL -
wide
INTL
32
IEC 60309-332P6
2
7.4
44
(38)C13,
(6)C19
68.9
3.3
2.1
P44F11M
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
50
50
60
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
NEMA L15-30P
NEMA L21-30P
NEMA L15-30P
NEMA L21-30P
Hubbell CS8365C
Hubbell CS8365C
IEC 60309-460P9
3
3
3
3
6
3
6
8.6
8.6
24
24
36
36
24
36
24
(18)C13,
(18)C13,
(30)C13,
(30)C13,
(12)C13,
(30)C13,
(12)C13,
(6)C19
(6)C19
(6)C19
(6)C19
(12)C19
(6)C19
(12)C19
68.9
68.9
68.9
68.9
68.9
68.9
68.9
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.1
P24F02M
P24F03M
P36F16M
P36F17M
P24F04M
P36F18M
P24F05M
8.6
8.6
14.4
10.0
17.3
0U FULL -
2 sided
NA
60
IEC 60309-460P9
6
17.3
48
(36)C13,
(12)C19
71.7
2.0
4.4
P48F19M
INTL
INTL
INTL
16
16
32
0U FULL
0U FULL
0U FULL
IEC 60309-516P6
IEC 60309-516P6
IEC 60309-532P6
0
0
6
11.0
11.0
22.0
24
36
24
(18)C13,
(30)C13,
(12)C13,
(6)C19
(6)C19
(12)C19
68.9
68.9
68.9
2.0
2.0
2.0
2.1
2.1
2.1
P24F07M
P36F12M
P24F08M
0U FULL -
wide
0U FULL -
2 sided
INTL
INTL
32
32
IEC 60309-532P6
IEC 60309-532P6
6
6
22.0
22.0
36
48
(24)C13,
(36)C13,
(12)C19
(12)C19
68.9
71.7
3.3
2.0
2.1
4.4
P36F13M
P48F09M
IEC 60309 3P+N+E 6h 30A
(IP67)
NA
NA
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
30
30
30
30
30
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
6
6
6
6
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
24
24
24
24
24
24
24
24
24
(12)C13,
(18)C13,
(24)C13
(12)C13,
(18)C13,
(24)C13
(12)C13,
(18)C13,
(24)C13
(12)C19
(6)C19
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
P24F09M
P24F11M
P24F12M
P24F13M
P24F14M
P24F15M
P24F10M
P24F16M
P24F17M
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP44)
(12)C19
(6)C19
IEC 60309 3P+N+E 6h 30A
(IP44)
IEC 60309 3P+N+E 6h 30A
(IP44)
NEMA L22-30P
NEMA L22-30P
NEMA L22-30P
(12)C19
(6)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP44)
NA
NA
NA
NA
30
30
30
30
6
6
6
6
17.3
17.3
17.3
17.3
36
36
36
36
(24)C13,
(30)C13,
(24)C13,
(30)C13,
(12)C19
(6)C19
(12)C19
(6)C19
68.9
68.9
68.9
68.9
3.3
3.3
3.3
3.3
2.1
2.1
2.1
2.1
P36F01M
P36F03M
P36F04M
P36F05M
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide
(IP44)
0U FULL -
Wide
0U FULL -
Wide
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP44)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided
0U FULL -
2 sided
0U FULL -
2 sided
0U FULL -
Wide +
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP44)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide +
0U FULL -
Wide +
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP44)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
30
30
30
30
30
30
30
30
30
30
NEMA L22-30P
6
6
6
6
6
6
6
6
6
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
36
36
48
48
48
48
48
48
48
48
48
48
48
48
(24)C13,
(30)C13,
(36)C13,
(48)C13
(36)C13,
(48)C13
(36)C13,
(48)C13
(48)C13
(48)C13
(48)C13
(42)C13,
(42)C13,
(42)C13,
(12)C19
(6)C19
68.9
68.9
71.7
71.7
71.7
71.7
71.7
71.7
74.0
74.0
74.0
74.0
74.0
74.0
3.3
3.3
2.0
2.0
2.0
2.0
2.0
2.0
3.3
3.3
3.3
3.3
3.3
3.3
2.1
2.1
4.4
4.4
4.4
4.4
4.4
4.4
2.1
2.1
2.1
2.1
2.1
2.1
P36F02M
P36F06M
P48F01M
P48F07M
P48F08M
P48F13M
P48F02M
P48F10M
P48F04M
P48F03M
P48F11M
P48F05M
P48F06M
P48F12M
NEMA L22-30P
(12)C19
(12)C19
(12)C19
(IP44)
NEMA L22-30P
NEMA L22-30P
NEMA L22-30P
(6)C19
(6)C19
(6)C19
(IP67)
NEMA L22-30P
Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America feature 10 kAIC circuit breakers.
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
Monitored Switched Per Outlet - MSPO Series
Input
Apparent
Power
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
(kVA)
Outlet Configuration
(inches) (inches)
INTL
INTL
INTL
NA
16
32
16
30
30
32
32
1U
IEC 60309-316P6
0
2
0
2
2
2
2
3.7
7.4
3.7
5.0
5.0
7.4
7.4
8
(8)C13
1.7
1.7
17.5
17.5
2.0
10.6
10.6
2.1
P08G10M
P08G12M
P24G11M
P24G01M
P36G18M
P24G06M
P32G13M
1U
IEC 60309-332P6
IEC 60309-316P6
L6-30P
8
(8)C13
0U Mid
0U FULL
0U FULL
0U FULL
0U FULL
24
24
36
24
32
(20)C13,
(20)C13,
(30)C13,
(20)C13,
(24)C13,
(4)C19
58.7
68.9
68.9
68.9
68.9
(4)C19
(6)C19
(4)C19
(8)C19
2.0
2.1
NA
L6-30P
2.0
2.1
INTL
INTL
IEC 60309-332P6
IEC 60309-332P6
2.0
2.1
2.0
2.1
0U FULL -
wide
INTL
32
IEC 60309-332P6
2
7.4
44
(38)C13,
(6)C19
68.9
3.3
2.1
P44G14M
NA
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
50
50
60
60
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
L15-30P
L21-30P
3
3
3
3
6
3
6
6
8.6
8.6
24
24
36
36
24
36
24
48
(18)C13,
(18)C13,
(30)C13,
(30)C13,
(12)C13,
(30)C13,
(12)C13,
(36)C13,
(6)C19
(6)C19
(6)C19
(6)C19
(12)C19
(6)C19
(12)C19
(12)C19
68.9
68.9
68.9
68.9
68.9
68.9
68.9
71.7
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.1
4.4
P24G02M
P24G03M
P36G22M
P36G19M
P24G04M
P36G20M
P24G05M
P48G21M
L15-30P
8.6
L21-30P
8.6
CS8365C
14.4
10.0
17.3
17.3
CS8365C
IEC 60309-460P9
IEC 60309-460P9
0U FULL -
2 sided
INTL
INTL
INTL
INTL
16
16
32
32
0U FULL
0U FULL
0U FULL
IEC 60309-516P6
IEC 60309-516P6
IEC 60309-532P6
IEC 60309-532P6
0
0
6
6
11.0
11.0
22.0
22.0
24
36
24
36
(18)C13,
(30)C13,
(12)C13,
(24)C13,
(6)C19
(6)C19
(12)C19
(12)C19
68.9
68.9
68.9
68.9
2.0
2.0
2.0
3.3
2.1
2.1
2.1
2.1
P24G07M
P36G15M
P24G08M
P36G16M
0U FULL -
wide
0U FULL -
2 sided
INTL
32
IEC 60309-532P6
6
22.0
48
(36)C13,
(12)C19
71.7
2.0
4.4
P48G09M
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
IEC 60309 3P+N+E 6h 30A
(IP67)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
0U FULL
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
17.3
24
24
24
24
24
24
24
24
24
36
36
36
36
36
36
48
48
48
48
48
(12)C13,
(18)C13,
(24)C13
(12)C13,
(18)C13,
(24)C13
(12)C13,
(18)C13,
(24)C13
(24)C13,
(30)C13,
(24)C13,
(30)C13,
(24)C13,
(30)C13,
(36)C13,
(48)C13
(36)C13,
(48)C13
(36)C13,
(12)C19
(6)C19
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
68.9
71.7
71.7
71.7
71.7
71.7
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
3.3
3.3
3.3
3.3
3.3
3.3
2.0
2.0
2.0
2.0
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
4.4
4.4
4.4
4.4
4.4
P24G09M
P24G13M
P24G14M
P24G15M
P24G16M
P24G17M
P24G10M
P24G18M
P24G19M
P36G01M
P36G03M
P36G04M
P36G05M
P36G02M
P36G06M
P48G01M
P48G07M
P48G08M
P48G10M
P48G02M
(12)C19
(6)C19
NEMA L22-30P
NEMA L22-30P
NEMA L22-30P
(12)C19
(6)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide (IP44)
(12)C19
(6)C19
(12)C19
(6)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide
0U FULL -
Wide
0U FULL -
Wide
(IP44)
NEMA L22-30P
(12)C19
(6)C19
NEMA L22-30P
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP67)
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided (IP44)
(12)C19
(12)C19
(12)C19
0U FULL - IEC 60309 3P+N+E 6h 30A
2 sided
0U FULL -
2 sided
(IP44)
NEMA L22-30P
(continued pg. 9)
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
Monitored Switched Per Outlet - MSPO Series (continued)
Input
Apparent
Power
Depth (inches)
at Outlet
position
Panduit
SKU Part
No.
Current
Circuit
Breakers
Outlet
Count
Length
Width
Region per phase Form Factor
Input Plug Type
(kVA)
Outlet Configuration
(inches) (inches)
0U FULL -
NA
NA
NA
NA
NA
NA
NA
30
30
30
30
30
30
30
NEMA L22-30P
6
6
6
6
6
6
6
17.3
17.3
17.3
17.3
17.3
17.3
17.3
48
48
48
48
48
48
48
(48)C13
71.7
74.0
74.0
74.0
74.0
74.0
74.0
2.0
3.3
3.3
3.3
3.3
3.3
3.3
4.4
2.1
2.1
2.1
2.1
2.1
2.1
P48G11M
P48G03M
P48G04M
P48G12M
P48G05M
P48G06M
P48G13M
2 sided
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide +
0U FULL -
Wide +
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP44)
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide +
0U FULL -
Wide +
0U FULL - IEC 60309 3P+N+E 6h 30A
Wide + (IP67)
(48)C13
(IP67)
NEMA L22-30P
(48)C13
(48)C13
(42)C13, (6)C19
(42)C13, (6)C19
(42)C13, (6)C19
(IP67)
NEMA L22-30P
Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America feature 10 kAIC circuit breakers.
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT US/CANADA
Phone:
PANDUIT EUROPE LTD.
London, UK
cs-emea@panduit.com
Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD. PANDUIT JAPAN
PANDUIT LATIN AMERICA
Guadalajara, Mexico
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
Republic of Singapore
cs-ap@panduit.com
Phone: 65.6305.7575
Tokyo, Japan
800.777.3300
cs-japan@panduit.com
Phone: 81.3.6863.6000
cs-la@panduit.com
cs-aus@panduit.com
Phone: 52.33.3777.6000
Phone: 61.3.9794.9020
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
For more information
Visit us at www.panduit.com
©2019 Panduit Corp.
ALL RIGHTS RESERVED.
Contact Technical Support by email: techsupport@panduit.com
or by phone: (866) 405-6654
PUSP28--SA-ENG
3/2019