Safety relay for emergency stop and safety doors up to SILCL 3, Cat. 4, PL e, 2-channel operation, automatic
or manual, monitored start, cross-circuit detection, 2 enabling current paths, US = 24 V DC, plug-in spring-cage
terminal block
The figure shows a version with a
screw connection
Why buy this product
Up to Cat.4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061
Low housing width of just 12.5 mm
Two-channel control
2 enabling current paths, 1 digital signal output
Manually monitored and automatic activation in a single device
Cross-circuit detection
Key Commercial Data
Packing unit
1 STK
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
160.000 g
85371099
Germany
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
area
Utilization restriction
Dimensions
Width
12.5 mm
Height
116.6 mm
08/30/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2700499
Safety relays - PSR-MC30-2NO-1DO-24DC-SP - 2700499
Technical data
Dimensions
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Max. permissible humidity (storage/transport)
Shock
-40 °C ... 55 °C (observe derating)
-40 °C ... 85 °C
75 % (on average, 85% infrequently, non-condensing)
75 % (on average, 85% infrequently, non-condensing)
15g
Vibration (operation)
10 Hz ...150 Hz, 2g
Maximum altitude
≤ 2000 m (Above sea level)
Input data
Rated control circuit supply voltage US
Power consumption at US
Rated control supply current IS
Inrush current
24 V DC -15 % / +10 %
typ. 1.56 W
typ. 65 mA
4 A (Δt = 200 µs at Us)
< 5 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22)
> -5 mA (with Us/Ix to S34)
> -5 mA (with Us/Ix to S22/S21)
< 10 mA (with Us/Ix to S34)
24 V DC -15 % / +10 %
Current consumption
Voltage at input/start and feedback circuit
Typical response time
< 175 ms (automatic start)
< 175 ms (manual, monitored start)
< 250 ms (when controlled via A1)
< 20 ms (when controlled via A1 or S12 and S22.)
< 500 ms
Typ. starting time with Us
Typical release time
Recovery time
Status display
3 x green LED
Maximum switching frequency
Max. permissible overall conductor resistance
Filter time
0.5 Hz
150 Ω
1 ms (at A1 in the event of voltage dips at Us)
max. 1.5 ms (at S12, S22; test pulse width)
min. 7.5 ms (at S12, S22; test pulse rate)
Test pulse rate = 5 x Test pulse width
Output data
Contact type
2 enabling current paths
AgSnO2
Contact material
08/30/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2700499
Safety relays - PSR-MC30-2NO-1DO-24DC-SP - 2700499
Technical data
Output data
Minimum switching voltage
Maximum switching voltage
Limiting continuous current
Inrush current, minimum
Maximum inrush current
Sq. Total current
12 V AC/DC
250 V AC/DC (Observe the load curve)
6 A (observe derating)
3 mA
6 A
72 A2 (observe derating)
min. 60 mW
Switching capacity
Output fuse
6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
Alarm outputs
Number of outputs
Voltage
1 (digital, PNP)
22 V DC (Us - 2 V)
max. 100 mA
Current
500 mA (Δt = 1 ms at Us)
no
Maximum inrush current
Short-circuit protection
General
Electromechanical relay with forcibly guided contacts in accordance with
IEC/EN 61810-3 (EN 50205)
Relay type
10 x 106 cycles
100% operating factor
156.8 g
Mechanical service life
Nominal operating mode
Net weight
Mounting type
DIN rail mounting
See derating curve
vertical or horizontal
IP20
Assembly instructions
Mounting position
Degree of protection
Min. degree of protection of inst. location
Control
IP54
Two-channel
PBT
Housing material
Housing color
yellow
Connection data
Connection method
Spring-cage connection
Yes
pluggable
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
0.2 mm²
1.5 mm²
0.2 mm²
1.5 mm²
08/30/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2700499
Safety relays - PSR-MC30-2NO-1DO-24DC-SP - 2700499
Technical data
Connection data
Conductor cross section AWG min.
Conductor cross section AWG max.
Stripping length
24
16
8 mm
Safety-related characteristic data
Stop category
0
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
Designation
3
IEC 61508 - Low demand
Safety Integrity Level (SIL)
Designation
3
EN ISO 13849
Performance level (PL)
Category
e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
4
Designation
EN 62061
3
Safety Integrity Level Claim Limit (SIL CL)
Standards and Regulations
Shock
15g
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
Rated insulation voltage
DIN EN 50178
250 V AC
Safe isolation, reinforced insulation 6 kV between input circuit and enabling
current path (13/14) and enabling current path (23/24)
Rated surge voltage/insulation
Basic insulation 4 kV between all current paths and housing
Degree of pollution
Overvoltage category
Vibration (operation)
2
III
10 Hz ...150 Hz, 2g
Drawings
08/30/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2700499
Safety relays - PSR-MC30-2NO-1DO-24DC-SP - 2700499
Block diagram
Block diagram
A1
S11 S12 S22 S21 S34
13 23
PSR-MC30
A1
S11
1
S22 S34
13 23
PSR-MC30
IN 1/2
K1
K2
2
PWR
3
4
24V DC
K1
K2
K1
K2
K4
10
K3
K3
K4
A2
M1
14 24
9
6
5
7
8
9
A2
S21 S12
M1
14 24
Key:
1 = Current limitation
2 = Input circuit
3 = Voltage limitation
4 = Start circuit
5 = Control circuit channel 1
6 = Control circuit signal output
7 = Control circuit channel 2
8 = Start channel 1 and 2
9 = Channel 1
10 = Diagnostics
K1, K2 ... K4 = Force-guided elementary relays
Circuit diagram
24V DC
L
S2
K1
S1
K2
A1
S34 S11
(
S12 S21 ) S22
(
13 23
K1
K2
(
)
(+)
)
( )
(GND)
PSR-MC30
A2
(
)
M1
14 24
M
K1
K2
0V
N
Classifications
eCl@ss
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 8.0
eCl@ss 9.0
27371901
27371819
27371819
27371819
08/30/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2700499
Safety relays - PSR-MC30-2NO-1DO-24DC-SP - 2700499
Classifications
ETIM
ETIM 5.0
EC001449
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / Functional Safety / GL / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
EAC 7500651.22.01.00244
Functional Safety 44-205-13755201
GL http://www.gl-group.com/newbuilding/approvals/index.html 11253-14 HH
cULus Listed