27371819 [PHOENIX]
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2;型号: | 27371819 |
厂家: | PHOENIX CONTACT |
描述: | Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 |
文件: | 总6页 (文件大小:234K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
https://www.phoenixcontact.com/pi/products/2981114
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 - 2981114
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to EN ISO
13849, single or two-channel operation, 3 enabling current paths, nominal input voltage of 24 ... 230 V AC/DC,
plug-in screw terminal blocks
Your advantages
Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508
Single and two-channel control
With inrush current reduction, therefore suitable for coupling to failsafe controllers (PSR-ESP4)
With wide-range input (PSR-ESAM4/3X1)
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356051644
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
area
Utilization restriction
Dimensions
Width
Height
Depth
45 mm
99 mm
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Max. permissible humidity (storage/transport)
-25 °C ... 85 °C
75 % (on average, 85% infrequently, non-condensing)
75 % (on average, 85% infrequently, non-condensing)
10/27/2021 Page 1 / 6
https://www.phoenixcontact.com/pi/products/2981114
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 - 2981114
Technical data
Ambient conditions
Maximum altitude
≤ 2000 m (Above sea level)
Input data
Input voltage range
24 V AC/DC ... 230 V AC/DC
0.85 ... 1.1
Input voltage range in reference to UN
Typical input current at UN
120 mA (at 24 V DC)
20 mA (at 120 V AC)
10 mA (for 230 V AC)
approx. 24 V DC
Voltage at input/start and feedback circuit
Typical response time
50 ms (manual start)
60 ms (automatic start)
500 ms (when controlled via A1)
20 ms (when controlled via S11/S12 and S21/S22)
50 ms (at 24 V DC)
110 ms (at 120 V AC)
280 ms (for 230 V AC)
∞
Typ. starting time with Us
Typical release time
Concurrence
Recovery time
1 s
Operating voltage display
Status display
1 x green LED
2 x green LEDs
Protective circuit
Surge protection Suppressor diode and varistors
0.5 Hz
Maximum switching frequency
Max. permissible overall conductor resistance
11 Ω
Output data
Contact type
3 enabling current paths
1 signaling current path
AgSnO2, + 0.2 µm Au
250 V AC/DC
Contact material
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
Inrush current, minimum
10 V AC/DC
6 A (N/O contact / N/C contact)
6 A
10 mA
2
50 A2 (ITH2 = I12 + I22 + ... + IN
192 W (24 V DC, τ = 0 ms)
384 W (48 V DC, τ = 0 ms)
80 W (110 V DC, τ = 0 ms)
66 W (220 V DC, τ = 0 ms)
)
Sq. Total current
Interrupting rating (ohmic load) max.
2000 VA (250 V AC, τ = 0 ms)
48 W (24 V DC, τ = 40 ms)
48 W (48 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
10/27/2021 Page 2 / 6
https://www.phoenixcontact.com/pi/products/2981114
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 - 2981114
Technical data
Output data
48 W (110 V DC, τ = 40 ms)
48 W (220 V DC, τ = 40 ms)
Switching capacity min.
360 mW
approx. 107 cycles
Mechanical service life
Switching capacity (360/h cycles)
4 A (24 V (DC13))
4 A (230 V (AC15))
6 A gG NEOZED
Output fuse
B6/C4A gL/gG automatic device
General
Electromechanical relay with force-guided contacts in accordance with
IEC/EN 61810-3
Relay type
Nominal operating mode
Net weight
100% operating factor
305.48 g
any
Mounting position
Mounting type
DIN rail mounting
IP20
Degree of protection
IP54
Min. degree of protection of inst. location
Housing color
IP54
yellow
Connection data
Connection method
Screw connection
Yes
pluggable
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Stripping length
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
7 mm
Screw thread
M3
Safety-related characteristic data
Stop category
0
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
Designation
3
IEC 61508 - Low demand
Safety Integrity Level (SIL)
Designation
3
EN ISO 13849
Performance level (PL)
Category
e
4
10/27/2021 Page 3 / 6
https://www.phoenixcontact.com/pi/products/2981114
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 - 2981114
Technical data
Safety-related characteristic data
Designation
EN 62061
3
Safety Integrity Level Claim Limit (SIL CL)
Standards and Regulations
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
Rated insulation voltage
DIN EN 50178/VDE 0160
250 V AC
6 kV/safe isolation, reinforced insulation and 6 kV between input circuits
and output contact current paths (13/14, 23/24, 33/34), as well as
between output contact current paths (13/14, 23/24, 33/34).
Rated surge voltage/insulation
Degree of pollution
Overvoltage category
Shock
2
III
15g
Vibration (operation)
10 Hz ... 150 Hz, 2g
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Circuit diagram
A1 S35 S10 S11 S12 13 23 33 41
»
K1
=
Logic
K2
A2
S21 S22
S33 S34
14 24 34 42
10/27/2021 Page 4 / 6
https://www.phoenixcontact.com/pi/products/2981114
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 - 2981114
Circuit diagram
L+
(L1)
Safety door
open
21
22
B1
13
14
B2
closed
41
42
A1
S10 S11 S12
(+)
13
14
23
24
33
34
S21 S22
(GND)
(
K3
K4
(
)
)
PSR-ESAM4/3x1/1x2
)
(
( )
(+)
S33 S34 S35
A2
K3
K4
M
K4
Reset
S2
K3
M
(N)
Two-channel safety door monitoring
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 9.0
27371102
27371102
27371901
27371900
27371800
27371819
27371819
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 6.0
EC001449
EC001449
EC001449
EC001449
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
30211901
39121501
39121501
39121501
39121501
UNSPSC 12.01
UNSPSC 13.2
10/27/2021 Page 5 / 6
https://www.phoenixcontact.com/pi/products/2981114
Safety relays - PSR-SCP-24-230UC/ESAM4/3X1/1X2 - 2981114
Classifications
UNSPSC
UNSPSC 19.0
39122205
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
10/27/2021 Page 6 / 6
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 202
-
VISHAY
©2020 ICPDF网 联系我们和版权申明