TRIO-UPS/1AC/24DC/5
Uninterruptible power supply with integrated power
supply unit
INTERFACE
Data sheet
104103_en_00
© PHOENIX CONTACT - 2009-09-01
1
Description
The TRIO-UPS/1AC/24DC/5 provides an uninterruptible
24 V DC voltage at a maximum load current of up to 5 A in
both an error-free AC power supply network and in the event
of power failure.
It is designed specifically for supplying industrial PCs (IPC).
The power supply unit and the electronic switch-over unit are
housed in the same housing.
In the event of supply voltage failure, buffer mode is
activated without interruption. In this operating mode, the
output voltage is directly dependent on the battery voltage.
In the event of a voltage dip, the IPC continues operating
without interruption, thus increasing system availability.
Uncontrolled shutdown is avoided.
The TRIO-UPS/1AC/24DC/5 can be parameterized using a
service PC and the UPS-CONF configuration and
management software via an IFS-USB-PROG-ADAPTER.
Features
–
Space-saving
The TRIO-UPS combines a power supply unit and
electronic switch-over unit in the same housing
–
–
Flexible
Rechargeable battery module with 1.3, 3.4, 7.2 or 12 Ah
Autonomous
In the event of AC mains failure, the industrial PC
continues operating without interruption
–
–
Time-saving
When the supply voltage is reapplied, the industrial PC
starts automatically
Parameterizable
Can be parameterized with the PC or configuration stick
For convenient parameter transfer between various TRIO-
UPS devices, the IFS-CONFSTICK configuration stick is
available as an option.
DANGER
Never carry out work when voltage is present.
The device contains dangerous live elements and high levels of stored energy.
Depending on the ambient temperature and load, the housing can become very hot.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
This data sheet is valid for all products listed under "Ordering data" on page 3.
TRIO-UPS/1AC/24DC/5
2
1
2
3
4
Table of contents
Description.................................................................................................................................. 1
Table of contents ........................................................................................................................ 2
Ordering data.............................................................................................................................. 3
Technical data ............................................................................................................................ 3
4.1
4.2
4.3
4.4
4.5
I/O data........................................................................................................................................................... 3
Battery management ...................................................................................................................................... 4
Signaling and switching outputs ..................................................................................................................... 5
Ambient conditions......................................................................................................................................... 5
Standards/approvals ...................................................................................................................................... 6
5
6
Safety regulations....................................................................................................................... 7
Connection, operating, and indication elements ......................................................................... 8
6.1
6.2
6.3
6.4
6.5
Connection terminal blocks ............................................................................................................................ 8
Block diagram ................................................................................................................................................ 9
Input ............................................................................................................................................................... 9
Output .......................................................................................................................................................... 10
LED indicators.............................................................................................................................................. 10
7
Installation .................................................................................................................................11
7.1
7.2
Narrow mounting position............................................................................................................................. 11
Flat mounting position .................................................................................................................................. 11
8
9
Rechargeable battery module....................................................................................................12
Method of operation...................................................................................................................13
9.1
9.2
9.3
9.4
9.5
9.6
Output voltage.............................................................................................................................................. 13
Remote shutdown ........................................................................................................................................ 13
Buffer time setting ........................................................................................................................................ 13
PC mode ...................................................................................................................................................... 13
PC idle time .................................................................................................................................................. 14
Battery management .................................................................................................................................... 15
10 Interfaces...................................................................................................................................15
10.1 Config.-Port .................................................................................................................................................. 15
10.2 IFS-USB-PROG-ADAPTER ......................................................................................................................... 15
10.3 IFS-CONFSTICK.......................................................................................................................................... 15
11 UPS-CONF configuration and management software ...............................................................16
104103_en_00
PHOENIX CONTACT
2
TRIO-UPS/1AC/24DC/5
3
Ordering data
UPS system
Description
Uninterruptible power supply with integrated power supply unit
Type
TRIO-UPS/1AC/24DC/5
Order No.
2866611
Pcs./Pkt.
1
The TRIO-UPS/1AC/24DC/5 is supplied without a rechargeable battery module. The rechargeable battery module must be ordered
separately (see accessories).
Accessories
Description
Type
Order No.
2866417
2866349
2866352
2866365
2320403
2811271
2986122
Pcs./Pkt.
Rechargeable battery module, 24 V DC, 1.3 Ah
Rechargeable battery module, 24 V DC, 3.4 Ah
Rechargeable battery module, 24 V DC, 7.2 Ah
Rechargeable battery module, 24 V DC, 12 Ah
Configuration and management software
USB data link cable between the UPS and IPC
MINI-BAT/24DC/1.3AH
QUINT-BAT/24DC/3.4AH
QUINT-BAT/24DC/7.2AH
QUINT-BAT/24DC/12AH
UPS-CONF
1
1
1
1
1
1
1
IFS-USB-PROG-ADAPTER
IFS-CONFSTICK
Configuration stick for parameter transfer between various
TRIO-UPS/1AC/24DC/5 devices
4
Technical data
4.1
I/O data
Input data
Nominal input voltage (wide-range input)
Input voltage range (nominal load)
100 ... 240 V AC
85 ... 264 V AC (< 90 V AC derating: 2.5%/V)
100 ... 350 V DC (UL508: 100 ... 250 V)
Frequency
45 ... 65 Hz
Approximate current consumption (mains operation and battery charging/
maximum)
At 230 V AC
At 120 V AC
0.95 A/1.1 A
1.7 A/1.8 A
Inrush current limiting / I²t at 25°C
typical < 44 A / < 1.3 A²s
Switch-on time after applying the mains voltage
At 230 V AC
At 120 V AC
150 ms
200 ms
Transient surge protection
Internal input fuse
Varistor
T 6.3 A
Recommended backup fuse
Circuit breaker
Discharge current to PE
6 A/10 A/16 A (B characteristic)
0.8 mA
Output data
Rise time
< 100 ms
Residual ripple
Switching peaks
Parallel connection to increase the buffer time
Surge protection against internal surge voltages
Maximum resistance to return supply
< 10 mV
< 25 mV
Yes, 2
Yes, < 35 V DC
35 V DC
PP
PP
104103_en_00
PHOENIX CONTACT
3
TRIO-UPS/1AC/24DC/5
Output data in mains operation (AC input voltage present)
Nominal output voltage U
24 V DC
N
Output voltage (adjustable)
Nominal output current, > 24 V DC constant capacity (-25°C to +70°C)
Derating (above 55°C)
22.5 ... 29.5 V DC
5 A
2.5%/K
Current limit
Connection of capacitive loads
6 A, approximately
Yes, unlimited
Control deviation
< 1% (static load change 10 ... 90%)
Approximate efficiency (mains operation and battery charging)
At 230 V AC
At 120 V AC
88%
86%
Approximate power dissipation (mains operation and battery charging)
At 230 V AC
At 120 V AC
16 W
20 W
Output data in battery operation (AC input voltage not present)
Nominal output voltage U
24 V DC
N
Output voltage (U
= U
- 0.5 V )
27.9 ... 19.2 V DC - 0.5 V
5 A
2.5%/K
6 A, approximately
Yes, 3300 µF
> 86%
OUT
BAT
Nominal output current (-25°C to +70°C)
Derating (above 55°C)
Current limit
Connection of capacitive loads
Efficiency
Power dissipation
Maximum no load
2 W
4 W
Maximum nominal load
Maximum buffer time (adjustable per minutes)
Overload fuse (electronic)
Remote shutdown
0.5; 1; 2; 3; 5; 10; 15; 20; PC mode
Yes
Yes
4.2
Battery management
Battery management
Charging characteristic curve
I/U
1
Charging current (preset/minimum/maximum)
1.0 A/0.2 A/1.5 A
27,6 V DC / 25 V DC / 30 V DC
42 mV/K / 0 mV/K / 200 mV/K
60 s
12 h/4 h/200 h
19.2 V DC / 18 V DC / 21 V DC
1
End-of-charge voltage (preset/minimum/maximum)
1
Temperature compensation (preset/minimum/maximum)
Battery presence check/time interval
1
Battery quality check (preset/minimum/maximum)
1
Protection against total discharge (preset/minimum/maximum)
"Battery almost flat" alarm signaling threshold (preset/minimum/maximum) 20.4 V DC / 18 V DC / 30 V DC
1
1
Can be adjusted via UPS-CONF software
104103_en_00
PHOENIX CONTACT
4
TRIO-UPS/1AC/24DC/5
4.3
Signaling and switching outputs
Status indicators
Mains voltage OK (Power in OK)
Alarm
Green LED, static ON
LED indicator
Red LED, static ON
24 V DC, active high
200 mA
Switching output
Current limit (internal)
Battery operation (Battery Mode)
LED indicator
Yellow LED, static ON
24 V DC, active high
200 mA
Switching output
Current limit (internal)
1
Signal options
Bat.-Mode, Bat.-Mode Delayed
Battery charging (Battery Charge)
LED indicator
Yellow LED, flashing
24 V DC, active high
200 mA
Switching output
Current limit (internal)
1
Signal options
Bat.-Charge, Bat.-Mode, Bat.-Mode Delayed, battery almost flat
1
Can be adjusted via UPS-CONF software
4.4
Ambient conditions
Climatic requirements
Ambient temperature
Operation (> 55°C derating)
Storage/transport
-25°C ... +70°C
-40°C ... +80°C
Humidity at +25°C, no condensation
Pollution degree according to EN 50178
Climatic class
95%
2
3K3
Mechanical requirements
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm according to IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock according to IEC 60068-2-27
30g in each direction
General data
Insulation voltage I/O (type/routine test)
Input/PE (type/routine test)
Output/PE (routine test)
Mounting position according to
Degree of protection
4 kV AC/2 kV AC
2 kV AC/2 kV AC
500 V DC
EN 60715
IP20
Protection class (with PE connection)
MTBF according to IEC 61709 (SN 29500)
Material
Dimensions (W/H/D)
Weight
I
> 500,000 h
Aluminum (AlMg3)/zinc-plated sheet steel
60 mm x 130 mm x 118 mm
1.1 kg
104103_en_00
PHOENIX CONTACT
5
TRIO-UPS/1AC/24DC/5
4.5
Standards/approvals
Standards/approvals
Electrical equipment of machines
(surge voltage category III)
EN 60204
Safety transformers for switched-mode power supply units
IEC 61558-2-17
Electrical safety
EN 60950/VDE 0805
UL/C-UL Recognized UL 60950 u
(of information technology equipment)
Industrial control equipment
Electronic equipment for use in
power installations
UL/C-UL Listed UL 508
EN 50178 (VDE 0160)
U
PELV/SELV
Safe isolation
PELV (EN 60204)/SELV (IEC 60950)
VDE 0100-410
Protection against electric shock
DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Limitation of mains harmonic currents
EN 61000-3-2
Conformance with EMC Directive 2004/108/EC, noise immunity according to 2006/95/EC
(electromagnetic compatibility)
Noise immunity according to EN 61000-6-2
Electrostatic discharge according to EN 61000-4-2
Housing
Level 3
Contact discharge
Air discharge
Remark
6 kV
8 kV
Criterion B
Level 3
80 MHz ... 2 GHz
10 V/m
Electromagnetic HF field according to EN 61000-4-3 Housing
Frequency range
Field strength
Remark
Input
Output
Signal
Criterion A
Fast transients (burst) according to EN 61000-4-4
4 kV (Level 4 - asymmetrical: Cable to ground)
2 kV (Level 4 - asymmetrical: Cable to ground)
1 kV (Level 4 - asymmetrical: Cable to ground)
Criterion B
Remark
Surge current loads (surge) according to EN 61000-4-5 Input
Output
4 kV (Level 4 - asymmetrical: Cable to ground)
2 kV (Level 4 - asymmetrical: Cable to cable)
2 kV (Level 3 - asymmetrical)
1 kV (Level 3 - symmetrical)
2 kV (Level 3 - asymmetrical)
Criterion B
Signal
Remark
Conducted interference according to EN 61000-4-6
Noise emission according to EN 61000-6-3
Input/output/signal
Frequency range
Voltage
Level 3
10 kHz ... 80 MHz
10 kV
Criterion A
Remark
Radio interference voltage according EN 55011 (EN 55022) Class B, industrial and residential
to EN 55011 applications
104103_en_00
PHOENIX CONTACT
6
TRIO-UPS/1AC/24DC/5
5
Safety regulations
Installation notes
NOTE:
–
The device must only be installed, operated,
and maintained by qualified personnel.
Follow the installation instructions.
–
–
When installing and operating the device, the
applicable safety directives (including
national safety directives), accident
prevention regulations, as well as general
technical regulations, must be observed.
–
For the safety data, please refer to the
package slip and certificates (conformity
assessment, other approvals, if necessary).
–
–
Do not repair the device yourself, replace it
with an equivalent device.
Repairs may only be carried out by the
manufacturer. The manufacturer is not liable
for damage resulting from violation.
–
–
The IP20 degree of protection (IEC 60529/
EN 60529) of the device is intended for use in
a clean and dry environment.
The device must not be subject to
mechanical strain and/or thermal loads,
which exceed the limits described.
Connection notes
NOTE: Electrostatic discharge
The device contains components that can be
damaged or destroyed by electrostatic discharge.
When handling the device, observe the
necessary safety precautions against
electrostatic discharge (ESD) according to
EN 61340-5-1 and EN 61340-5-2.
104103_en_00
PHOENIX CONTACT
7
TRIO-UPS/1AC/24DC/5
6.1
Connection terminal blocks
6
Connection, operating, and indication
elements
Use a screwdriver with the correct blade width for wiring. For
reliable and safe-to-touch connections, strip 8 mm off the
cable ends.
The following cable cross-sections can be connected:
Terminal Rigid Stranded AWG
block
Tightening
torque
No.
[mm²]
[mm²]
[Nm]
[lb in]
1 - 3,
5 - 7,
!
0.2 - 2.5 0.2 - 2.5 24 - 12 0.5 - 0.6 3.5 - 4.5
+
+
5
A
3
la
rm
B
a
6
t.-
M
ode
Ba
t.-
C
harg
e
R
em
Output
o
te
7
In order to comply with UL approval, use copper
cables that are designed for operating
temperatures >75°C.
R1
OFF
R
24V
DC
A
e
m
ote
ON
5
R
2
DC
B
attery
+
11
2
Adjust
22.5-29.5
TR
Custom
(Default
t
m
a
x
m
V
4
0
1
in
.5)
2
8
PC-M
3
ode
5
20
10
Alarm
15
L
Bat.-Mode
12
8
( + )
( - )
Bat.-Charge
Power
N
in
OverloOaKd
Input
100-240
Config.-Port
9
AC
1
V
U
1. P
S DA
Press
T
2.
A S
n
Insert
Butto T
IC
STICKSTICK
1.
Insert
Press
andK
within
10
DATA
2.
4sec
STICKUPS
Button
>
6sec
13
14
Figure 1
TRIO-UPS/1AC/24DC/5 structure
No. Description
1
2
3
4
5
6
7
8
9
0
!
"
100 ... 240 V AC input
24 V rechargeable battery module connection
24 V DC output, buffered
22.5 ... 29.5 V DC potentiometer
Active switching output: Alarm
Active switching output: Bat.-Mode
Active switching output: Bat.-Charge
Red LED indicator: Alarm
Yellow LED indicator: Bat.-Mode/Bat.-Charge
Green LED indicator: Power in OK/Overload
Remote shutdown (R1, R2)
Buffer time setting
0.5 ... 20 minutes, PC mode, unlimited ∞
§
$
Config.-Port
"Confirm" button
104103_en_00
PHOENIX CONTACT
8
TRIO-UPS/1AC/24DC/5
6.2
Block diagram
Config.-Port
Confirm
J
IFS
t...[min]
2x 12V
Remote
On/Off
R1
R2
Battery
Alarm
Bat.-Mode
Bat.-Charge
L (+)
N (-)
Output DC
24 V 5 A
PS
Figure 2
Block diagram for the TRIO-UPS/1AC/24DC/5
6.3
Input
Network type
The 100 ... 240 V AC connection is made using the L (+) and
N (-) screw connections.
Device installation must be carried out according to the
regulations of EN 60950. It must be possible to switch off the
device using a suitable disconnecting device outside the
power supply.
The device can be connected to single-phase AC networks
or to two of the phase conductors of three-phase systems
(TN, TT or IT networks according to VDE 0100-300/IEC
60364-3) with nominal voltages of 100 V AC ... 240 V AC.
For operation using two phase conductors of a
three-phase system, an all-pole disconnecting
device must be provided.
For example, primary side line protection could
be used.
TN-S
TN-C
An internal fuse is provided for device protection. Additional
device protection is not required.
L
L
N
PEN
PE
If an internal fuse is blown, this is due to a device
fault. In this case, send the device to Phoenix
Contact for inspection.
L
N
L
N
+
-
+
-
TT
iT
L1
L2
L3
L
N
L
N
L
N
+
-
+
-
Figure 3
Single-phase network systems
104103_en_00
PHOENIX CONTACT
9
TRIO-UPS/1AC/24DC/5
6.4
Output
The signal outputs are connected via the "Alarm", "Bat.-
Mode", and "Bat.-Charge" terminal blocks. There are three
LED status indicators and three active switching outputs for
function monitoring.
The 24 V DC connection is made using the "OUT DC 24 V,
+, -" screw connections. The output voltage set upon
delivery is 24 V DC. The output voltage can be set from
22.5 V DC to 29.5 V DC on the potentiometer.
Description
The UPS is switched off or the UPS
is operating in mains mode, battery
1
mode is deactivated (remote),
battery management is still active
+
+
The UPS is starting mains
operation, for the LED test all LEDs
3
Alarm
Bat.-
Mode
Bat.-
2
are switched on and off again once
before the current operating state is
indicated
The UPS is operating in mains
mode, the battery is OK and
charged
The UPS is operating in mains
mode, the battery is OK and is
charging (charge < 85% of nominal
capacity)
Charge
Remote
Output
R1
RemotOeFF
24V
DC
5A
ON
R2
+
DC
Battery
Adjust
22.5-29.5
TR
Custom
t
min(D
a
u
l
max
e
f
4
V
t
0
1
.5
)
2
8
3
4
PC-M
3
ode
5
20
10
Alarm
15
L
Bat.-Mode
( + )
( - )
Bat.-Charge
Power
N
in
OverloOaKd
1
Input
100-240
Config.-Port
UPS
AC
V
1.
DATA
Press
2.
Insert
Butto
S
n
TICK
STICKSTICK
and
within
1.
Insert
DATA
2.
Press
4sec
STICKUPS
Button
>
6sec
The UPS is operating in battery
mode, the battery voltage UBAT
is > 20.4 V
The UPS is operating in battery
mode, the battery is almost flat
(battery voltage UBAT is < 20.4 V)
UPS protection against total
discharge has terminated battery
mode
(battery voltage UBAT = 19.2 V) and
continues indication for a maximum
of 10 hours
5
6
Figure 4
Connection
No. Description
1
3
4
100 ... 240 V AC input
24 V DC output, buffered
22.5 ... 29.5 V DC potentiometer
7
6.5
LED indicators
The UPS is operating in mains
8
9
8
9
mode, the battery is faulty
The UPS has been overloaded in
mains mode, the battery is OK and
charged
The UPS has been overloaded in
mains mode, the battery is faulty
10
10
Figure 5
LED indicators
Key
LED OFF
LED ON
No. Description
8
9
0
Red LED indicator: Alarm
Yellow LED indicator: Bat.-Mode/Bat.-Charge
Green LED indicator: Power in OK/Overload
LED flashing
104103_en_00
PHOENIX CONTACT 10
TRIO-UPS/1AC/24DC/5
7.2
Flat mounting position
7
Installation
A flat mounting position can be achieved by mounting the
module onto the DIN rail at a 90° angle. Mount the DIN rail
adapter (UTA 107) as shown in the figure. The screws that
were previously used to secure the UTA must be used: Torx
T10 (0.8 Nm ... 0.9 Nm tightening torque).
A minimum spacing between other devices does not have to
be observed in order to ensure correct device function.
7.1
Narrow mounting position
The power supply unit can be snapped onto all DIN rails
according to EN 60715 and must be mounted horizontally
(connection terminal blocks facing upwards and
downwards).
Mounting
Position the module with the DIN rail guideway on the top
edge of the DIN rail and then snap it downwards.
B
A
Figure 8
Modification for flat mounting position
Figure 6
Mounting the TRIO-UPS/1AC/24DC/5
Removal
Release the snap-on catch using a screwdriver and then
detach the module from the bottom edge of the DIN rail.
B
A
Figure 7
Removing the TRIO-UPS/1AC/24DC/5
104103_en_00
PHOENIX CONTACT 11
TRIO-UPS/1AC/24DC/5
8
Rechargeable battery module
The batteries are sealed, maintenance-free
lead AGM batteries, which are intended for
operating temperatures of 0°C ... 40°C.
They have a service life of six to nine years at an
ambient temperature of 20°C.
The rechargeable battery module is connected to the power
supply unit via the "Battery +" and "Battery -" terminal blocks
2.
NOTE: Risk of short circuit
The fuse for the rechargeable battery module
must be removed when installing or replacing the
module.
In order to ensure immediate availability, all
batteries are supplied fully charged. Startup
should be carried out at the latest after nine
months at 20°C ... 30°C, or after six months at
30°C ... 40°C.
The following rechargeable battery modules are
recommended:
Rechargeable battery
module
Fuse
Recom-
mended
charging
current
1
2
3
4
MINI-BAT/24DC/1.3Ah
15 A
0.8 A 2
1.0 A 2
QUINT-BAT/24DC/3.4Ah 1 25 A
QUINT-BAT/24DC/7.2Ah1 2 x 25 A 1.5 A 2
QUINT-BAT/24DC/12Ah1 2 x 25 A 1.5 A 2
1
2
Connection via plug connector, 14 mm
Can be adjusted via UPS-CONF software
30
4
10
t [h]
1
60
10
3
1
2
1 = 1.3Ah
2 = 3.4Ah
3 = 7.2Ah
4 = 12Ah
t [min]
1
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
I [A]
Figure 9
Characteristic curves for the rechargeable
battery modules
Battery mode can be exited after a predefined time has
elapsed or by means of external shutdown. If the device is
to be shut down after a specific time has elapsed, the time
can be set via the selector switch " on the front of the
device. When the supply voltage is reapplied, the device
can switch to battery mode again.
104103_en_00
PHOENIX CONTACT 12
TRIO-UPS/1AC/24DC/5
To set the parameters, an Interface interface (IFS) is used
for data exchange between the TRIO-UPS and a suitable
user interface on the IPC. The user is supported by help
texts and graphics for the individual parameters.
As an option, parameterization can be carried out using an
IFS-CONFSTICK. Here, a parameter record is transferred
from the TRIO-UPS to the IFS-CONFSTICK. This
parameter record can then be written to any other
TRIO-UPS.
9
Method of operation
9.1
Output voltage
In mains operation (AC input voltage present) the output
voltage of the TRIO-UPS corresponds to the setting at the
potentiometer 4. In the event of supply voltage failure,
battery mode is activated without interruption. The output
voltage is now directly dependent on the battery voltage and
is UBAT - 0.5 V.
In "PC mode", the UPS function follows a parameterizable
chronological sequence of delay time, IPC shutdown, and
IPC idle time.
9.2
Remote shutdown
If the connected load cannot be supplied from the power
storage device in the event that the AC voltage fails, the
UPS can be disabled via R1/R2. This shutdown can be
performed during mains operation or while battery mode is
active.
UPS active, remote shutdown deactivated, default upon
delivery:
–
–
–
Delay time:
If the mains voltage is not applied again within the first 60
seconds of battery mode, for example, "Bat.-Mode" is
indicated in order to shut down an IPC with a delay.
IPC shutdown:
Terminal points "R1" and "R2" are short circuited (with
plug-in bridges by default upon delivery) OR 24 V DC is
present at terminal point "R2".
If the supply voltage fails, the TRIO-UPS switches to
battery mode. UPS not active, remote shutdown
activated:
Shutdown is performed via a data cable to the IPC. The IPC
must be connected to the UPS via a USB data cable.
The IPC is supplied by the TRIO-UPS for a parameterizable
period of time, e.g., 2 minutes.
Terminal points "R1" and "R2" are not short circuited
AND 0 V DC is present at terminal point "R2".
–
–
All LEDs are OFF.
If the supply voltage fails, the TRIO-UPS does not
switch to battery mode, the device shuts down.
–
The connected loads are supplied and the
rechargeable battery module is charged as long as the
supply voltage is present.
9.3
Buffer time setting
The time after which battery mode is exited is set via the "
selector switch on the front of the device:
–
–
0.5 to 20 minutes
Parameterizable time via software
("CUSTOM" switch position, default: 0.5 minutes)
–
–
Unlimited (buffering with the total stored energy)
PC mode (see Section 9.4 "PC mode" )
9.4
PC mode
In "PC mode", the UPS function follows a chronological
sequence that can be parameterized via the software and
individually optimized for the relevant IPC solution.
Requirements: IFS-USB-PROG-ADAPTER data cable
(Order No. 2811271) and UPS-CONF software
(Order No. 2320403).
104103_en_00
PHOENIX CONTACT 13
TRIO-UPS/1AC/24DC/5
9.5
PC idle time
Once the "PC shutdown" time has elapsed, the output voltage is switched off, e.g., for 30 seconds (also when the mains
voltage is applied again).
Power comes back on during set delay time
120/230V
0V
AC input
1
3
24V
0V
DC output
24V
0V
Bat. mode delayed:
Active switching output
(can be parameterized)
6
LED green
ON
10
9
POWER IN OK
OFF
ON
LED gelb
Bat.-Mode
OFF
ON
PC response
OFF
Delay time
PC shutdown
Power comes back on during set time PC shutdown
AC input
DC output
120/230V
0V
1
24V
3
6
0V
24V
Bat. mode delayed:
Active switching output
(can be parameterized)
0V
ON
LED green
10
9
POWER IN OK
OFF
ON
LED yellow
Bat. mode
OFF
ON
PC response
OFF
PC shutdown
PC
Delay time
idle time
Figure 10
Time diagrams
104103_en_00
PHOENIX CONTACT 14
TRIO-UPS/1AC/24DC/5
9.6
Battery management
10.3 IFS-CONFSTICK
Battery management of the TRIO-UPS is divided into two
checks that are performed cyclically during normal
operation.
The IFS-CONFSTICK is a multi-functional memory block for
easy storage and back up of configuration and parameter
data.
Battery presence check
Transferring parameters to the IFS-CONFSTICK
The battery presence check is used to detect a correctly
installed battery. If this is not the case, the check is failed
and the green 0 and red 8 LED indicators are controlled
statically.
To transfer parameters, proceed as follows:
1. Press and hold down the "Confirm" button.
2. You now have four seconds to carefully insert the
IFS-CONFSTICK in the "Config.-Port" on the
TRIO-UPS, taking care to observe the connection
direction.
Battery quality check
The battery quality check is a lifecycle test. It enables
conclusions to be drawn, e.g., regarding the maximum
lifecycle of the battery if the maximum charging time has
been exceeded. In this case, the green 0 and red 8 LED
indicators are controlled statically.
3. Parameter transfer is started and indicated by the cyclic
control of the three LED indicators. Sequence: Red -
Yellow - Green
a) Error-free transfer:
Green LED indicator ON
b) Transfer error:
Red LED indicator ON
10 Interfaces
Transferring parameters to the TRIO-UPS
10.1 Config.-Port
To transfer parameters, proceed as follows:
The TRIO-UPS is connected to the USB connection on the
service PC via the "Config.-Port" using the IFS-USB-PROG-
ADAPTER data cable.
1. Carefully insert the IFS-CONFSTICK in the "Config.-
Port" on the TRIO-UPS, taking care to observe the
connection direction.
10.2 IFS-USB-PROG-ADAPTER
1. Press and hold down the "Confirm" button for at least
six seconds.
The programming adapter (Order No. 2811271) represents
the interface between the service PC and the TRIO-UPS
and is required in order to parameterize the TRIO-UPS.
2. Parameter transfer is started and indicated by the cyclic
control of the three LED indicators. Sequence: Green -
Yellow - Red
a) Error-free transfer:
Green LED indicator ON
b) Transfer error:
1
7
2
X
11
X
X
X
X
8
B
2
S
X
X
U
X
X
X
.
o.:
.-N
o
N
l
ia
r
e
IFS-USB-PROG-ADAPTER
rd
O
S
Red LED indicator ON
m
o
c
.
t
c
ta
n
o
c
y
n
ix
n
e
o
h
a
r
te
m
r
p
.
e
p
a
e
c
G
,
d
a
f
r
e
A
rg
t
in
.
e
g
b
in
w
w
m
m
lo
w
m
ra
B
5
2
g
8
ro
2
3
-P
B
S
U
The following can be parameterized:
–
–
–
Times
Switching outputs
Battery management
Figure 11
Programming adapter
104103_en_00
PHOENIX CONTACT 15
TRIO-UPS/1AC/24DC/5
11 UPS-CONF configuration and
management software
The Windows-based UPS-CONF configuration and
management software (Order No. 2320403) is used to
parameterize the TRIO-UPS.
The UPS-CONF configuration and management
software can be downloaded free of charge at
www.phoenixcontact.net/download.
Various dialog boxes are available for parameterization.
The current operating status of the TRIO-UPS is always
displayed at the bottom of the dialog box.
Figure 12
Example, TRIO-UPS status display
A distinction is made between the following states:
Status
Meaning
Operation mode
Preset operating mode at the
selector switch "
Power Source
Power source that is currently
active
Battery Condition
Device Status
Current battery charging state
Current state of the TRIO-UPS
Connection to UPS Connection status between service
PC and TRIO-UPS
If an alarm is detected or an existing online
connection between the IPC and TRIO-UPS is
interrupted, the UPS-CONF dialog box is
automatically displayed on screen.
The status is queried cyclically.
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
104103_en_00
16
相关型号:
2866378
DC-DC Regulated Power Supply Module, 1 Output, 240W, Hybrid, ROHS COMPLIANT, PACKAGE
PHOENIX
©2020 ICPDF网 联系我们和版权申明