TRIO-UPS/1AC/24DC/5  
Uninterruptible power supply with integrated power  
supply unit  
INTERFACE  
Data sheet  
104103_en_00  
© PHOENIX CONTACT - 2009-09-01  
1
Description  
The TRIO-UPS/1AC/24DC/5 provides an uninterruptible  
24 V DC voltage at a maximum load current of up to 5 A in  
both an error-free AC power supply network and in the event  
of power failure.  
It is designed specifically for supplying industrial PCs (IPC).  
The power supply unit and the electronic switch-over unit are  
housed in the same housing.  
In the event of supply voltage failure, buffer mode is  
activated without interruption. In this operating mode, the  
output voltage is directly dependent on the battery voltage.  
In the event of a voltage dip, the IPC continues operating  
without interruption, thus increasing system availability.  
Uncontrolled shutdown is avoided.  
The TRIO-UPS/1AC/24DC/5 can be parameterized using a  
service PC and the UPS-CONF configuration and  
management software via an IFS-USB-PROG-ADAPTER.  
Features  
Space-saving  
The TRIO-UPS combines a power supply unit and  
electronic switch-over unit in the same housing  
Flexible  
Rechargeable battery module with 1.3, 3.4, 7.2 or 12 Ah  
Autonomous  
In the event of AC mains failure, the industrial PC  
continues operating without interruption  
Time-saving  
When the supply voltage is reapplied, the industrial PC  
starts automatically  
Parameterizable  
Can be parameterized with the PC or configuration stick  
For convenient parameter transfer between various TRIO-  
UPS devices, the IFS-CONFSTICK configuration stick is  
available as an option.  
DANGER  
Never carry out work when voltage is present.  
The device contains dangerous live elements and high levels of stored energy.  
Depending on the ambient temperature and load, the housing can become very hot.  
Make sure you always use the latest documentation.  
It can be downloaded at www.phoenixcontact.net/download.  
This data sheet is valid for all products listed under "Ordering data" on page 3.  
TRIO-UPS/1AC/24DC/5  
2
1
2
3
4
Table of contents  
Description.................................................................................................................................. 1  
Table of contents ........................................................................................................................ 2  
Ordering data.............................................................................................................................. 3  
Technical data ............................................................................................................................ 3  
4.1  
4.2  
4.3  
4.4  
4.5  
I/O data........................................................................................................................................................... 3  
Battery management ...................................................................................................................................... 4  
Signaling and switching outputs ..................................................................................................................... 5  
Ambient conditions......................................................................................................................................... 5  
Standards/approvals ...................................................................................................................................... 6  
5
6
Safety regulations....................................................................................................................... 7  
Connection, operating, and indication elements ......................................................................... 8  
6.1  
6.2  
6.3  
6.4  
6.5  
Connection terminal blocks ............................................................................................................................ 8  
Block diagram ................................................................................................................................................ 9  
Input ............................................................................................................................................................... 9  
Output .......................................................................................................................................................... 10  
LED indicators.............................................................................................................................................. 10  
7
Installation .................................................................................................................................11  
7.1  
7.2  
Narrow mounting position............................................................................................................................. 11  
Flat mounting position .................................................................................................................................. 11  
8
9
Rechargeable battery module....................................................................................................12  
Method of operation...................................................................................................................13  
9.1  
9.2  
9.3  
9.4  
9.5  
9.6  
Output voltage.............................................................................................................................................. 13  
Remote shutdown ........................................................................................................................................ 13  
Buffer time setting ........................................................................................................................................ 13  
PC mode ...................................................................................................................................................... 13  
PC idle time .................................................................................................................................................. 14  
Battery management .................................................................................................................................... 15  
10 Interfaces...................................................................................................................................15  
10.1 Config.-Port .................................................................................................................................................. 15  
10.2 IFS-USB-PROG-ADAPTER ......................................................................................................................... 15  
10.3 IFS-CONFSTICK.......................................................................................................................................... 15  
11 UPS-CONF configuration and management software ...............................................................16  
104103_en_00  
PHOENIX CONTACT  
2
TRIO-UPS/1AC/24DC/5  
3
Ordering data  
UPS system  
Description  
Uninterruptible power supply with integrated power supply unit  
Type  
TRIO-UPS/1AC/24DC/5  
Order No.  
2866611  
Pcs./Pkt.  
1
The TRIO-UPS/1AC/24DC/5 is supplied without a rechargeable battery module. The rechargeable battery module must be ordered  
separately (see accessories).  
Accessories  
Description  
Type  
Order No.  
2866417  
2866349  
2866352  
2866365  
2320403  
2811271  
2986122  
Pcs./Pkt.  
Rechargeable battery module, 24 V DC, 1.3 Ah  
Rechargeable battery module, 24 V DC, 3.4 Ah  
Rechargeable battery module, 24 V DC, 7.2 Ah  
Rechargeable battery module, 24 V DC, 12 Ah  
Configuration and management software  
USB data link cable between the UPS and IPC  
MINI-BAT/24DC/1.3AH  
QUINT-BAT/24DC/3.4AH  
QUINT-BAT/24DC/7.2AH  
QUINT-BAT/24DC/12AH  
UPS-CONF  
1
1
1
1
1
1
1
IFS-USB-PROG-ADAPTER  
IFS-CONFSTICK  
Configuration stick for parameter transfer between various  
TRIO-UPS/1AC/24DC/5 devices  
4
Technical data  
4.1  
I/O data  
Input data  
Nominal input voltage (wide-range input)  
Input voltage range (nominal load)  
100 ... 240 V AC  
85 ... 264 V AC (< 90 V AC derating: 2.5%/V)  
100 ... 350 V DC (UL508: 100 ... 250 V)  
Frequency  
45 ... 65 Hz  
Approximate current consumption (mains operation and battery charging/  
maximum)  
At 230 V AC  
At 120 V AC  
0.95 A/1.1 A  
1.7 A/1.8 A  
Inrush current limiting / I²t at 25°C  
typical < 44 A / < 1.3 A²s  
Switch-on time after applying the mains voltage  
At 230 V AC  
At 120 V AC  
150 ms  
200 ms  
Transient surge protection  
Internal input fuse  
Varistor  
T 6.3 A  
Recommended backup fuse  
Circuit breaker  
Discharge current to PE  
6 A/10 A/16 A (B characteristic)  
0.8 mA  
Output data  
Rise time  
< 100 ms  
Residual ripple  
Switching peaks  
Parallel connection to increase the buffer time  
Surge protection against internal surge voltages  
Maximum resistance to return supply  
< 10 mV  
< 25 mV  
Yes, 2  
Yes, < 35 V DC  
35 V DC  
PP  
PP  
104103_en_00  
PHOENIX CONTACT  
3
TRIO-UPS/1AC/24DC/5  
Output data in mains operation (AC input voltage present)  
Nominal output voltage U  
24 V DC  
N
Output voltage (adjustable)  
Nominal output current, > 24 V DC constant capacity (-25°C to +70°C)  
Derating (above 55°C)  
22.5 ... 29.5 V DC  
5 A  
2.5%/K  
Current limit  
Connection of capacitive loads  
6 A, approximately  
Yes, unlimited  
Control deviation  
< 1% (static load change 10 ... 90%)  
Approximate efficiency (mains operation and battery charging)  
At 230 V AC  
At 120 V AC  
88%  
86%  
Approximate power dissipation (mains operation and battery charging)  
At 230 V AC  
At 120 V AC  
16 W  
20 W  
Output data in battery operation (AC input voltage not present)  
Nominal output voltage U  
24 V DC  
N
Output voltage (U  
= U  
- 0.5 V )  
27.9 ... 19.2 V DC - 0.5 V  
5 A  
2.5%/K  
6 A, approximately  
Yes, 3300 µF  
> 86%  
OUT  
BAT  
Nominal output current (-25°C to +70°C)  
Derating (above 55°C)  
Current limit  
Connection of capacitive loads  
Efficiency  
Power dissipation  
Maximum no load  
2 W  
4 W  
Maximum nominal load  
Maximum buffer time (adjustable per minutes)  
Overload fuse (electronic)  
Remote shutdown  
0.5; 1; 2; 3; 5; 10; 15; 20; PC mode  
Yes  
Yes  
4.2  
Battery management  
Battery management  
Charging characteristic curve  
I/U  
1
Charging current (preset/minimum/maximum)  
1.0 A/0.2 A/1.5 A  
27,6 V DC / 25 V DC / 30 V DC  
42 mV/K / 0 mV/K / 200 mV/K  
60 s  
12 h/4 h/200 h  
19.2 V DC / 18 V DC / 21 V DC  
1
End-of-charge voltage (preset/minimum/maximum)  
1
Temperature compensation (preset/minimum/maximum)  
Battery presence check/time interval  
1
Battery quality check (preset/minimum/maximum)  
1
Protection against total discharge (preset/minimum/maximum)  
"Battery almost flat" alarm signaling threshold (preset/minimum/maximum) 20.4 V DC / 18 V DC / 30 V DC  
1
1
Can be adjusted via UPS-CONF software  
104103_en_00  
PHOENIX CONTACT  
4
TRIO-UPS/1AC/24DC/5  
4.3  
Signaling and switching outputs  
Status indicators  
Mains voltage OK (Power in OK)  
Alarm  
Green LED, static ON  
LED indicator  
Red LED, static ON  
24 V DC, active high  
200 mA  
Switching output  
Current limit (internal)  
Battery operation (Battery Mode)  
LED indicator  
Yellow LED, static ON  
24 V DC, active high  
200 mA  
Switching output  
Current limit (internal)  
1
Signal options  
Bat.-Mode, Bat.-Mode Delayed  
Battery charging (Battery Charge)  
LED indicator  
Yellow LED, flashing  
24 V DC, active high  
200 mA  
Switching output  
Current limit (internal)  
1
Signal options  
Bat.-Charge, Bat.-Mode, Bat.-Mode Delayed, battery almost flat  
1
Can be adjusted via UPS-CONF software  
4.4  
Ambient conditions  
Climatic requirements  
Ambient temperature  
Operation (> 55°C derating)  
Storage/transport  
-25°C ... +70°C  
-40°C ... +80°C  
Humidity at +25°C, no condensation  
Pollution degree according to EN 50178  
Climatic class  
95%  
2
3K3  
Mechanical requirements  
Vibration (operation)  
< 15 Hz, amplitude ±2.5 mm according to IEC 60068-2-6  
15 Hz ... 150 Hz, 2.3g, 90 min.  
Shock according to IEC 60068-2-27  
30g in each direction  
General data  
Insulation voltage I/O (type/routine test)  
Input/PE (type/routine test)  
Output/PE (routine test)  
Mounting position according to  
Degree of protection  
4 kV AC/2 kV AC  
2 kV AC/2 kV AC  
500 V DC  
EN 60715  
IP20  
Protection class (with PE connection)  
MTBF according to IEC 61709 (SN 29500)  
Material  
Dimensions (W/H/D)  
Weight  
I
> 500,000 h  
Aluminum (AlMg3)/zinc-plated sheet steel  
60 mm x 130 mm x 118 mm  
1.1 kg  
104103_en_00  
PHOENIX CONTACT  
5
TRIO-UPS/1AC/24DC/5  
4.5  
Standards/approvals  
Standards/approvals  
Electrical equipment of machines  
(surge voltage category III)  
EN 60204  
Safety transformers for switched-mode power supply units  
IEC 61558-2-17  
Electrical safety  
EN 60950/VDE 0805  
UL/C-UL Recognized UL 60950 u  
(of information technology equipment)  
Industrial control equipment  
Electronic equipment for use in  
power installations  
UL/C-UL Listed UL 508  
EN 50178 (VDE 0160)  
U
PELV/SELV  
Safe isolation  
PELV (EN 60204)/SELV (IEC 60950)  
VDE 0100-410  
Protection against electric shock  
DIN 57100-410  
Protection against electric shock, basic requirements for safe isolation in  
electrical equipment  
DIN VDE 0106-101  
Limitation of mains harmonic currents  
EN 61000-3-2  
Conformance with EMC Directive 2004/108/EC, noise immunity according to 2006/95/EC  
(electromagnetic compatibility)  
Noise immunity according to EN 61000-6-2  
Electrostatic discharge according to EN 61000-4-2  
Housing  
Level 3  
Contact discharge  
Air discharge  
Remark  
6 kV  
8 kV  
Criterion B  
Level 3  
80 MHz ... 2 GHz  
10 V/m  
Electromagnetic HF field according to EN 61000-4-3 Housing  
Frequency range  
Field strength  
Remark  
Input  
Output  
Signal  
Criterion A  
Fast transients (burst) according to EN 61000-4-4  
4 kV (Level 4 - asymmetrical: Cable to ground)  
2 kV (Level 4 - asymmetrical: Cable to ground)  
1 kV (Level 4 - asymmetrical: Cable to ground)  
Criterion B  
Remark  
Surge current loads (surge) according to EN 61000-4-5 Input  
Output  
4 kV (Level 4 - asymmetrical: Cable to ground)  
2 kV (Level 4 - asymmetrical: Cable to cable)  
2 kV (Level 3 - asymmetrical)  
1 kV (Level 3 - symmetrical)  
2 kV (Level 3 - asymmetrical)  
Criterion B  
Signal  
Remark  
Conducted interference according to EN 61000-4-6  
Noise emission according to EN 61000-6-3  
Input/output/signal  
Frequency range  
Voltage  
Level 3  
10 kHz ... 80 MHz  
10 kV  
Criterion A  
Remark  
Radio interference voltage according EN 55011 (EN 55022) Class B, industrial and residential  
to EN 55011 applications  
104103_en_00  
PHOENIX CONTACT  
6
TRIO-UPS/1AC/24DC/5  
5
Safety regulations  
Installation notes  
NOTE:  
The device must only be installed, operated,  
and maintained by qualified personnel.  
Follow the installation instructions.  
When installing and operating the device, the  
applicable safety directives (including  
national safety directives), accident  
prevention regulations, as well as general  
technical regulations, must be observed.  
For the safety data, please refer to the  
package slip and certificates (conformity  
assessment, other approvals, if necessary).  
Do not repair the device yourself, replace it  
with an equivalent device.  
Repairs may only be carried out by the  
manufacturer. The manufacturer is not liable  
for damage resulting from violation.  
The IP20 degree of protection (IEC 60529/  
EN 60529) of the device is intended for use in  
a clean and dry environment.  
The device must not be subject to  
mechanical strain and/or thermal loads,  
which exceed the limits described.  
Connection notes  
NOTE: Electrostatic discharge  
The device contains components that can be  
damaged or destroyed by electrostatic discharge.  
When handling the device, observe the  
necessary safety precautions against  
electrostatic discharge (ESD) according to  
EN 61340-5-1 and EN 61340-5-2.  
104103_en_00  
PHOENIX CONTACT  
7
TRIO-UPS/1AC/24DC/5  
6.1  
Connection terminal blocks  
6
Connection, operating, and indication  
elements  
Use a screwdriver with the correct blade width for wiring. For  
reliable and safe-to-touch connections, strip 8 mm off the  
cable ends.  
The following cable cross-sections can be connected:  
Terminal Rigid Stranded AWG  
block  
Tightening  
torque  
No.  
[mm²]  
[mm²]  
[Nm]  
[lb in]  
1 - 3,  
5 - 7,  
!
0.2 - 2.5 0.2 - 2.5 24 - 12 0.5 - 0.6 3.5 - 4.5  
+
+
5
A
3
la  
rm  
B
a
6
t.-  
M
ode  
Ba  
t.-  
C
harg  
e
R
em  
Output  
o
te  
7
In order to comply with UL approval, use copper  
cables that are designed for operating  
temperatures >75°C.  
R1  
OFF  
R
24V  
DC  
A
e
m
ote  
ON  
5
R
2
DC  
B
attery  
+
11  
2
Adjust  
22.5-29.5  
TR  
Custom  
(Default  
t
m
a
x
m
V
4
0
1
in  
.5)  
2
8
PC-M  
3
ode  
5
20  
10  
Alarm  
15  
L
Bat.-Mode  
12  
8
( + )  
( - )  
Bat.-Charge  
Power  
N
in  
OverloOaKd  
Input  
100-240  
Config.-Port  
9
AC  
1
V
U
1. P  
S DA  
Press  
T
2.  
A S  
n
Insert  
Butto T  
IC  
STICKSTICK  
1.  
Insert  
Press  
andK  
within  
10  
DATA  
2.  
4sec  
STICKUPS  
Button  
>
6sec  
13  
14  
Figure 1  
TRIO-UPS/1AC/24DC/5 structure  
No. Description  
1
2
3
4
5
6
7
8
9
0
!
"
100 ... 240 V AC input  
24 V rechargeable battery module connection  
24 V DC output, buffered  
22.5 ... 29.5 V DC potentiometer  
Active switching output: Alarm  
Active switching output: Bat.-Mode  
Active switching output: Bat.-Charge  
Red LED indicator: Alarm  
Yellow LED indicator: Bat.-Mode/Bat.-Charge  
Green LED indicator: Power in OK/Overload  
Remote shutdown (R1, R2)  
Buffer time setting  
0.5 ... 20 minutes, PC mode, unlimited  
§
$
Config.-Port  
"Confirm" button  
104103_en_00  
PHOENIX CONTACT  
8
TRIO-UPS/1AC/24DC/5  
6.2  
Block diagram  
Config.-Port  
Confirm  
J
IFS  
t...[min]  
2x 12V  
Remote  
On/Off  
R1  
R2  
Battery  
Alarm  
Bat.-Mode  
Bat.-Charge  
L (+)  
N (-)  
Output DC  
24 V 5 A  
PS  
Figure 2  
Block diagram for the TRIO-UPS/1AC/24DC/5  
6.3  
Input  
Network type  
The 100 ... 240 V AC connection is made using the L (+) and  
N (-) screw connections.  
Device installation must be carried out according to the  
regulations of EN 60950. It must be possible to switch off the  
device using a suitable disconnecting device outside the  
power supply.  
The device can be connected to single-phase AC networks  
or to two of the phase conductors of three-phase systems  
(TN, TT or IT networks according to VDE 0100-300/IEC  
60364-3) with nominal voltages of 100 V AC ... 240 V AC.  
For operation using two phase conductors of a  
three-phase system, an all-pole disconnecting  
device must be provided.  
For example, primary side line protection could  
be used.  
TN-S  
TN-C  
An internal fuse is provided for device protection. Additional  
device protection is not required.  
L
L
N
PEN  
PE  
If an internal fuse is blown, this is due to a device  
fault. In this case, send the device to Phoenix  
Contact for inspection.  
L
N
L
N
+
-
+
-
TT  
iT  
L1  
L2  
L3  
L
N
L
N
L
N
+
-
+
-
Figure 3  
Single-phase network systems  
104103_en_00  
PHOENIX CONTACT  
9
TRIO-UPS/1AC/24DC/5  
6.4  
Output  
The signal outputs are connected via the "Alarm", "Bat.-  
Mode", and "Bat.-Charge" terminal blocks. There are three  
LED status indicators and three active switching outputs for  
function monitoring.  
The 24 V DC connection is made using the "OUT DC 24 V,  
+, -" screw connections. The output voltage set upon  
delivery is 24 V DC. The output voltage can be set from  
22.5 V DC to 29.5 V DC on the potentiometer.  
Description  
The UPS is switched off or the UPS  
is operating in mains mode, battery  
1
mode is deactivated (remote),  
battery management is still active  
+
+
The UPS is starting mains  
operation, for the LED test all LEDs  
3
Alarm  
Bat.-  
Mode  
Bat.-  
2
are switched on and off again once  
before the current operating state is  
indicated  
The UPS is operating in mains  
mode, the battery is OK and  
charged  
The UPS is operating in mains  
mode, the battery is OK and is  
charging (charge < 85% of nominal  
capacity)  
Charge  
Remote  
Output  
R1  
RemotOeFF  
24V  
DC  
5A  
ON  
R2  
+
DC  
Battery  
Adjust  
22.5-29.5  
TR  
Custom  
t
min(D  
a
u
l
max  
e
f
4
V
t
0
1
.5  
)
2
8
3
4
PC-M  
3
ode  
5
20  
10  
Alarm  
15  
L
Bat.-Mode  
( + )  
( - )  
Bat.-Charge  
Power  
N
in  
OverloOaKd  
1
Input  
100-240  
Config.-Port  
UPS  
AC  
V
1.  
DATA  
Press  
2.  
Insert  
Butto  
S
n
TICK  
STICKSTICK  
and  
within  
1.  
Insert  
DATA  
2.  
Press  
4sec  
STICKUPS  
Button  
>
6sec  
The UPS is operating in battery  
mode, the battery voltage UBAT  
is > 20.4 V  
The UPS is operating in battery  
mode, the battery is almost flat  
(battery voltage UBAT is < 20.4 V)  
UPS protection against total  
discharge has terminated battery  
mode  
(battery voltage UBAT = 19.2 V) and  
continues indication for a maximum  
of 10 hours  
5
6
Figure 4  
Connection  
No. Description  
1
3
4
100 ... 240 V AC input  
24 V DC output, buffered  
22.5 ... 29.5 V DC potentiometer  
7
6.5  
LED indicators  
The UPS is operating in mains  
8
9
8
9
mode, the battery is faulty  
The UPS has been overloaded in  
mains mode, the battery is OK and  
charged  
The UPS has been overloaded in  
mains mode, the battery is faulty  
10  
10  
Figure 5  
LED indicators  
Key  
LED OFF  
LED ON  
No. Description  
8
9
0
Red LED indicator: Alarm  
Yellow LED indicator: Bat.-Mode/Bat.-Charge  
Green LED indicator: Power in OK/Overload  
LED flashing  
104103_en_00  
PHOENIX CONTACT 10  
TRIO-UPS/1AC/24DC/5  
7.2  
Flat mounting position  
7
Installation  
A flat mounting position can be achieved by mounting the  
module onto the DIN rail at a 90° angle. Mount the DIN rail  
adapter (UTA 107) as shown in the figure. The screws that  
were previously used to secure the UTA must be used: Torx  
T10 (0.8 Nm ... 0.9 Nm tightening torque).  
A minimum spacing between other devices does not have to  
be observed in order to ensure correct device function.  
7.1  
Narrow mounting position  
The power supply unit can be snapped onto all DIN rails  
according to EN 60715 and must be mounted horizontally  
(connection terminal blocks facing upwards and  
downwards).  
Mounting  
Position the module with the DIN rail guideway on the top  
edge of the DIN rail and then snap it downwards.  
B
A
Figure 8  
Modification for flat mounting position  
Figure 6  
Mounting the TRIO-UPS/1AC/24DC/5  
Removal  
Release the snap-on catch using a screwdriver and then  
detach the module from the bottom edge of the DIN rail.  
B
A
Figure 7  
Removing the TRIO-UPS/1AC/24DC/5  
104103_en_00  
PHOENIX CONTACT 11  
TRIO-UPS/1AC/24DC/5  
8
Rechargeable battery module  
The batteries are sealed, maintenance-free  
lead AGM batteries, which are intended for  
operating temperatures of 0°C ... 40°C.  
They have a service life of six to nine years at an  
ambient temperature of 20°C.  
The rechargeable battery module is connected to the power  
supply unit via the "Battery +" and "Battery -" terminal blocks  
2.  
NOTE: Risk of short circuit  
The fuse for the rechargeable battery module  
must be removed when installing or replacing the  
module.  
In order to ensure immediate availability, all  
batteries are supplied fully charged. Startup  
should be carried out at the latest after nine  
months at 20°C ... 30°C, or after six months at  
30°C ... 40°C.  
The following rechargeable battery modules are  
recommended:  
Rechargeable battery  
module  
Fuse  
Recom-  
mended  
charging  
current  
1
2
3
4
MINI-BAT/24DC/1.3Ah  
15 A  
0.8 A 2  
1.0 A 2  
QUINT-BAT/24DC/3.4Ah 1 25 A  
QUINT-BAT/24DC/7.2Ah1 2 x 25 A 1.5 A 2  
QUINT-BAT/24DC/12Ah1 2 x 25 A 1.5 A 2  
1
2
Connection via plug connector, 14 mm  
Can be adjusted via UPS-CONF software  
30  
4
10  
t [h]  
1
60  
10  
3
1
2
1 = 1.3Ah  
2 = 3.4Ah  
3 = 7.2Ah  
4 = 12Ah  
t [min]  
1
0
0.5  
1
1.5  
2
2.5  
3
3.5  
4
4.5  
5
I [A]  
Figure 9  
Characteristic curves for the rechargeable  
battery modules  
Battery mode can be exited after a predefined time has  
elapsed or by means of external shutdown. If the device is  
to be shut down after a specific time has elapsed, the time  
can be set via the selector switch " on the front of the  
device. When the supply voltage is reapplied, the device  
can switch to battery mode again.  
104103_en_00  
PHOENIX CONTACT 12  
TRIO-UPS/1AC/24DC/5  
To set the parameters, an Interface interface (IFS) is used  
for data exchange between the TRIO-UPS and a suitable  
user interface on the IPC. The user is supported by help  
texts and graphics for the individual parameters.  
As an option, parameterization can be carried out using an  
IFS-CONFSTICK. Here, a parameter record is transferred  
from the TRIO-UPS to the IFS-CONFSTICK. This  
parameter record can then be written to any other  
TRIO-UPS.  
9
Method of operation  
9.1  
Output voltage  
In mains operation (AC input voltage present) the output  
voltage of the TRIO-UPS corresponds to the setting at the  
potentiometer 4. In the event of supply voltage failure,  
battery mode is activated without interruption. The output  
voltage is now directly dependent on the battery voltage and  
is UBAT - 0.5 V.  
In "PC mode", the UPS function follows a parameterizable  
chronological sequence of delay time, IPC shutdown, and  
IPC idle time.  
9.2  
Remote shutdown  
If the connected load cannot be supplied from the power  
storage device in the event that the AC voltage fails, the  
UPS can be disabled via R1/R2. This shutdown can be  
performed during mains operation or while battery mode is  
active.  
UPS active, remote shutdown deactivated, default upon  
delivery:  
Delay time:  
If the mains voltage is not applied again within the first 60  
seconds of battery mode, for example, "Bat.-Mode" is  
indicated in order to shut down an IPC with a delay.  
IPC shutdown:  
Terminal points "R1" and "R2" are short circuited (with  
plug-in bridges by default upon delivery) OR 24 V DC is  
present at terminal point "R2".  
If the supply voltage fails, the TRIO-UPS switches to  
battery mode. UPS not active, remote shutdown  
activated:  
Shutdown is performed via a data cable to the IPC. The IPC  
must be connected to the UPS via a USB data cable.  
The IPC is supplied by the TRIO-UPS for a parameterizable  
period of time, e.g., 2 minutes.  
Terminal points "R1" and "R2" are not short circuited  
AND 0 V DC is present at terminal point "R2".  
All LEDs are OFF.  
If the supply voltage fails, the TRIO-UPS does not  
switch to battery mode, the device shuts down.  
The connected loads are supplied and the  
rechargeable battery module is charged as long as the  
supply voltage is present.  
9.3  
Buffer time setting  
The time after which battery mode is exited is set via the "  
selector switch on the front of the device:  
0.5 to 20 minutes  
Parameterizable time via software  
("CUSTOM" switch position, default: 0.5 minutes)  
Unlimited (buffering with the total stored energy)  
PC mode (see Section 9.4 "PC mode" )  
9.4  
PC mode  
In "PC mode", the UPS function follows a chronological  
sequence that can be parameterized via the software and  
individually optimized for the relevant IPC solution.  
Requirements: IFS-USB-PROG-ADAPTER data cable  
(Order No. 2811271) and UPS-CONF software  
(Order No. 2320403).  
104103_en_00  
PHOENIX CONTACT 13  
TRIO-UPS/1AC/24DC/5  
9.5  
PC idle time  
Once the "PC shutdown" time has elapsed, the output voltage is switched off, e.g., for 30 seconds (also when the mains  
voltage is applied again).  
Power comes back on during set delay time  
120/230V  
0V  
AC input  
1
3
24V  
0V  
DC output  
24V  
0V  
Bat. mode delayed:  
Active switching output  
(can be parameterized)  
6
LED green  
ON  
10  
9
POWER IN OK  
OFF  
ON  
LED gelb  
Bat.-Mode  
OFF  
ON  
PC response  
OFF  
Delay time  
PC shutdown  
Power comes back on during set time PC shutdown  
AC input  
DC output  
120/230V  
0V  
1
24V  
3
6
0V  
24V  
Bat. mode delayed:  
Active switching output  
(can be parameterized)  
0V  
ON  
LED green  
10  
9
POWER IN OK  
OFF  
ON  
LED yellow  
Bat. mode  
OFF  
ON  
PC response  
OFF  
PC shutdown  
PC  
Delay time  
idle time  
Figure 10  
Time diagrams  
104103_en_00  
PHOENIX CONTACT 14  
TRIO-UPS/1AC/24DC/5  
9.6  
Battery management  
10.3 IFS-CONFSTICK  
Battery management of the TRIO-UPS is divided into two  
checks that are performed cyclically during normal  
operation.  
The IFS-CONFSTICK is a multi-functional memory block for  
easy storage and back up of configuration and parameter  
data.  
Battery presence check  
Transferring parameters to the IFS-CONFSTICK  
The battery presence check is used to detect a correctly  
installed battery. If this is not the case, the check is failed  
and the green 0 and red 8 LED indicators are controlled  
statically.  
To transfer parameters, proceed as follows:  
1. Press and hold down the "Confirm" button.  
2. You now have four seconds to carefully insert the  
IFS-CONFSTICK in the "Config.-Port" on the  
TRIO-UPS, taking care to observe the connection  
direction.  
Battery quality check  
The battery quality check is a lifecycle test. It enables  
conclusions to be drawn, e.g., regarding the maximum  
lifecycle of the battery if the maximum charging time has  
been exceeded. In this case, the green 0 and red 8 LED  
indicators are controlled statically.  
3. Parameter transfer is started and indicated by the cyclic  
control of the three LED indicators. Sequence: Red -  
Yellow - Green  
a) Error-free transfer:  
Green LED indicator ON  
b) Transfer error:  
Red LED indicator ON  
10 Interfaces  
Transferring parameters to the TRIO-UPS  
10.1 Config.-Port  
To transfer parameters, proceed as follows:  
The TRIO-UPS is connected to the USB connection on the  
service PC via the "Config.-Port" using the IFS-USB-PROG-  
ADAPTER data cable.  
1. Carefully insert the IFS-CONFSTICK in the "Config.-  
Port" on the TRIO-UPS, taking care to observe the  
connection direction.  
10.2 IFS-USB-PROG-ADAPTER  
1. Press and hold down the "Confirm" button for at least  
six seconds.  
The programming adapter (Order No. 2811271) represents  
the interface between the service PC and the TRIO-UPS  
and is required in order to parameterize the TRIO-UPS.  
2. Parameter transfer is started and indicated by the cyclic  
control of the three LED indicators. Sequence: Green -  
Yellow - Red  
a) Error-free transfer:  
Green LED indicator ON  
b) Transfer error:  
1
7
2
X
11  
X
X
X
X
8
B
2
S
X
X
U
X
X
X
.
o.:  
.-N  
o
N
l
ia  
r
e
IFS-USB-PROG-ADAPTER  
rd  
O
S
Red LED indicator ON  
m
o
c
.
t
c
ta  
n
o
c
y
n
ix  
n
e
o
h
a
r
te  
m
r
p
.
e
p
a
e
c
G
,
d
a
f
r
e
A
rg  
t
in  
.
e
g
b
in  
w
w
m
m
lo  
w
m
ra  
B
5
2
g
8
ro  
2
3
-P  
B
S
U
The following can be parameterized:  
Times  
Switching outputs  
Battery management  
Figure 11  
Programming adapter  
104103_en_00  
PHOENIX CONTACT 15  
TRIO-UPS/1AC/24DC/5  
11 UPS-CONF configuration and  
management software  
The Windows-based UPS-CONF configuration and  
management software (Order No. 2320403) is used to  
parameterize the TRIO-UPS.  
The UPS-CONF configuration and management  
software can be downloaded free of charge at  
www.phoenixcontact.net/download.  
Various dialog boxes are available for parameterization.  
The current operating status of the TRIO-UPS is always  
displayed at the bottom of the dialog box.  
Figure 12  
Example, TRIO-UPS status display  
A distinction is made between the following states:  
Status  
Meaning  
Operation mode  
Preset operating mode at the  
selector switch "  
Power Source  
Power source that is currently  
active  
Battery Condition  
Device Status  
Current battery charging state  
Current state of the TRIO-UPS  
Connection to UPS Connection status between service  
PC and TRIO-UPS  
If an alarm is detected or an existing online  
connection between the IPC and TRIO-UPS is  
interrupted, the UPS-CONF dialog box is  
automatically displayed on screen.  
The status is queried cyclically.  
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0  
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300  
www.phoenixcontact.com  
104103_en_00  
16  

相关型号:

2866378

DC-DC Regulated Power Supply Module, 1 Output, 240W, Hybrid, ROHS COMPLIANT, PACKAGE
PHOENIX

2866446

Power supply unit - MINI-PS-100-240AC/24DC/1.3 - 2866446
PHOENIX

2866569

UPS - Uninterruptible Power Supplies MINI-BAT/12DC/2.6AH BATTERY ONLY
PHOENIX

2866572

UPS - Uninterruptible Power Supplies MINI-BAT/12DC/1.6AH BATTERY ONLY
PHOENIX

2866666

RECHARGEABLE BATT MODULE 24VDC
PHOENIX

286677

Fuseholders - For 3AG, 5 x 20mm, or 2AG Fuses
LITTELFUSE

2866776

QUINT-PS/24DC/48DC/ 5
PHOENIX

286677A

Analog Circuit
LITTELFUSE

286677B

Analog Circuit
LITTELFUSE

286677C

Analog Circuit
LITTELFUSE

286677D

Analog Circuit
LITTELFUSE

286677E

Analog Circuit
LITTELFUSE